Specifications

5
VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-11
This parameter determines the display on keypad after each power up.
To program this parameter the user must first generate a Hex value with the information
above. Then using the Hex to Decimal conversion to find the corresponding Decimal value
and enter it into this parameter.
For example, a setting of 21 (decimal 21= hex 010101) will display the “H” and “REV” LEDs
and the cursor will stay at the 3rd 7-step display upon power up.
When setting to U LED, please refer to 02-09.
02 - 09 Special Display
a
Factory Setting: 00
Settings 00: A displays output current of AC drive
01: U displays DC-Bus voltage of AC drive
02: E displays RMS of output voltage
03: P displays feedback signal
04: PLC display auto procedure state
This parameter chooses the display on the keypad immediately following the “U” user
defined setting.
“MODE” key will scroll from “F”, “H”, “U”, (Pr. 02-09), FWD, and back to “F”.
Users may also use the “LEFT” key on the digital keypad to switch display content.
02 - 10 User Defined Coefficient
a
Factory Setting: 1.00
Settings 0.01~160.00 Unit: 0.01
When this parameter is set, the “H “display value = actual output frequency of AC drive x
02-10.
If output frequency of AC drive is 90Hz, set 02-10 to 2.5. When H LED lights, the value on
the display is 225.00.
02 - 11 Flying Start
a
Factory Setting: 00
Settings 00: Disabled
01: Enabled (DC braking disabled)
When the AC drive starts into a running motor (Flying Start), it may cause an over current
on the drive and may damage the motor. Using speed search upon start-up will allow the
drive to slowly find the motor speed, smoothly take control of the motor, and bring it to
command speed.
If the Flying Start feature is enabled upon start-up, the DC braking 08-01 will be disabled.