5.4 Group 3: Output Function Parameters
03 - 00 Multi-function Output terminal 1 (Relay) Factory Setting: 01
Settings 00-21
Setting Functions Descriptions
00 Disabled
01 Indication during operation The corresponding output will be closed
during operation (including DC braking time).
02 Master frequency
attained
The corresponding output will be closed when
output frequency reaches master frequency
command.
03 Zero Speed (including shutdown) The corresponding output will be closed when
the AC drive has no output voltage signal.
04 Over-torque The corresponding output relay will be closed
when the AC drives output current exceeds
the over-torque detection level 06-04.
05 External Fault The corresponding output will be closed when
the EF is enabled. (Pr. 04-00 to 04-03)
06 Low voltage detection The corresponding output will be closed when
the DC Bus voltage drops below our threshold.
The keypad will display “Lu”.
07 Operation Mode indication The corresponding output will be closed when
the AC drives “Operation Command” is
controlled by the external terminals.
08 Fault Indication The corresponding output will be closed when
AC drive has experienced a fault.
09 Master Frequency Attained 1 The corresponding output will be closed when
the AC drives output frequency exceeds
(Pr.03-08) Master Frequency Attained 1.
10 Master Frequency Attained 2 The corresponding output will be closed when
the AC drives output frequency exceeds
(Pr.03-09) Master Frequency Attained 2.
11 Over Temperature indication The corresponding output will be closed when
the AC drive temperature exceeds its rating.
12 Drive Ready The corresponding output will be closed the
when the AC drive is ready and has no faults.
13 External Emergency Stop (EF1) The corresponding output will be closed when
multi-function input terminals (Pr.04-00 to
04-03) are set to emergency stop and then
activated.
14 Software braking output The corresponding output will be closed when
the AC drives DC bus voltage exceeds
(Pr.08-19) the braking level.
15 OL or OL1 overload warning The corresponding output will be closed upon
an overload (OL or OL1) fault.