Specifications
VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-14
Setting Functions Descriptions
16 Low current indication The corresponding output will be closed when
the AC drives output current is lower than the
Low Current setting (Pr.06-08).
17 PID feedback error indication The corresponding output will be closed when
the PID feedback signal has an error.
18 Auto Running Command
The Output will be closed when PLC Program
is running.
19 1-Step Running Completed
The Output will be closed for 0.5 sec when
each multi-step speed is attained.
20 Auto Running Completed
The output will be closed for 0.5 sec when the
PLC program cycle has completed
21 Auto Running Paused
The output will be closed when PLC operation
is paused.
Standard relay specifications = 10A/250VAC or 12A/24VDC.
Relay delay time is 5~10 msec.
03 - 01 Reserved
03 - 02 Master Frequency Attained 1 Factory Setting: 0.00
03 - 03 Master Frequency Attained 2
Settings 0.00~160.00 Hz Unit: 0.01
An output relay may be programmed to activate when the output frequency exceeds the
desired attained frequency setting of these two parameters.
There is a
±
2Hz window of operation. If the master frequency attained is 20Hz and the
output frequency exceeds 20Hz, the corresponding output relay will be “closed”. When the
output frequency is less than 18Hz, the corresponding output relay will be “opened” as the
following diagram shows.
Frequency
Master
frequency 1
Master frequency
2 attained
Master frequency
attained
Output frequency
Frequency
command
Time
2Hz
4Hz
2Hz
2Hz
Master frequency
1 attained
Master
frequency 2