Setting Functions
Descriptions
18 PID disabled Disable PID feedback control and operate via
Master Frequency Command source Pr.02-00.
19 Run PLC Program
20 Pause PLC Program
Parameter value 32 programs Multi-Function
Input Terminal to enable the AC drive internal
PLC program. Parameter value 33 programs
an input terminal to pause the PLC program.
Note: Pr.05-00 to Pr.05-16 defines the PLC
program.
21 1st Output Frequency Gain
(Pr.04-30)
Output frequency multiplies a gain
(Pr.04-30)
H=F*(Pr.04-30)
22 2nd Output Frequency Gain
(Pr.04-31)
Output frequency multiplies a gain
(Pr.04-31)
H=F*(Pr.04-31)
23 3rd Output Frequency Gain
(Pr.04-32)
Output frequency multiplies a gain
(Pr.04-32)
H=F*(Pr.04-32)
04 - 04 Digital Input Terminal Response Time Factory Setting: 01
Settings 01~20
This parameter selects the response time of digital input terminals MI1 to MI4, EF and
FWD.
AC drive will scan the digital input terminals once every 2msec. During each scan the drive
will check the status of each terminal (open or closed).
In noisy environments, it would be advantageous to verify the terminal status several times
before executing a new command, nearly eliminating false signals.
Example: If Pr.04-04 is set to 4, the AC drive will confirm the terminal status (4+1 = 5) 5
times before a change is made. This correlates to an 8~10msec time response from input
command to execution.
It is not recommended to set this parameter to 00, since interference may cause improper
operation of the AC drive.
04 - 05 Minimum AI1 Analog Input Factory Setting: 0
04 - 06
Maximum AI1 Analog Input Factory Setting: 100
Settings 0 ~ 100% Unit: 1
04 - 07 Minimum Output that corresponds to AI1 Factory Setting: 0.00
04 - 08 Maximum Output that corresponds to AI1 Factory Setting: 100.00
Settings 0.00~100.00% Unit: 0.01