Specifications

5
VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-33
5.8 Group 7: AC Drive and Motor Parameters
07 - 00 Identity Code of AC Drive Factory Setting: ##
Settings Display by model type
This parameter displays the AC drive model code.
This parameter is read-only.
07 - 01 Rated Current of AC Drive Factory Setting: ##
Settings Display by model type
This parameter displays rated output current of the AC drive. The following chart may be
used to look up the identity code, current, and hp of your drive.
KW
5.5 7.5 11 15 18.5 22 30 37 45 55 75
HP 7.5 10 15 20 25 30 40 50 60 75 100
Pr.07-00 13 15 17 19 21 23 25 27 29 31 33
Rated Current (A) 13 18 24 32 38 45 60 73 91 110 150
Max. Carried Freq. 6KHz 6KHz 6KHz
Min. Carried Freq. 4KHz 3KHz 2KHz
Factory Setting 6KHz 6KHz 4KHz
This parameter is read-only.
07 - 02
Full-load Current of Motor
a
Factory Setting: 100%
Settings 30~120% Unit: 1
This parameter selects the full load current of the motor.
Pr7-02 = (full load motor current / drive rated current)
Example: If the rated current of AC drive is 150A, full-load current of motor is 120A, then
Pr.7-02 should be set to 80%.
This parameter is used with slip compensation Pr.7-04 to Pr.7-05 and electronic thermal
relay Pr.6-06 to Pr.6-07. An incorrect setting will cause these functions to not work
incorrectly and may damage the motor and drive.
The full-load current of the motor must be equal to or less than (but not less than 50%) the
rated current of the AC drive.
07 - 03 No-load Current of Motor
a
Factory Setting: 30%
Settings 1~99% Unit: 1