Specifications

5
VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-39
The allowable power loss time must in the condition that AC drive auxiliary power is working
normally. If auxiliary power is turned off in the allowable power loss time, the actual
allowable power loss time will be shorter than the parameter setting.
08 - 06
Speed Search Time Factory Setting: 0.5
Settings 0.1~5.0 Sec Unit: 0.1
This parameter determines the delay time from fault (power loss, OV, OC or BB) recovery to
start to execute the function of speed search time.
08 - 07 Maximum Speed Search Current Factory Setting: 110
Settings 30~150% Unit: 1
This parameter determines maximum current of speed search.
Maximum speed search current will have influence with synchronization attained time. The
greater this parameter is set, the faster it will be synchronization. But if the parameter
setting value is too great, it may occur over-loaded protection.
If 08-04 is set to 01: when speed search is from top downward, output frequency is
searched from master frequency command downward. Now output voltage and output
current will be added from zero. When output current is equal to 08-07 setting value, AC
drive output current will retain in a fixed value and output frequency will keep on searching
from top downward. When output frequency and output voltage is overlapped with V/F
setting frequency, AC drive will judge that is synchronization attained and accelerates from
V/F curve to master frequency command.
If 08-04 is set to 02: AC drive will accelerate according to V/F curve and won’t do any
special treatment.
Power
Input
Output
Frequency
Output
Voltage
B.B. Time
08-06
Speed Search
Speed
Synchronization
Detection
Momentary Power Loss Operation
Maximum allowable
power loss time
08-05
08-04=01
B.B.Time
08-06
Max. Allowable
Power Loss Time
08-05
08-04=02