Specifications

VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-2
Parameters Functions Settings
Factory
Setting
Customer
00-02 AC Drive Status Indication 2 Bit 0~1: 00: Run led is off and
stop led is on.
01: Run led is blink
and stop led is on.
10: Run led is on and
stop led is blink.
11: Run led is on and
stop led is off.
Bit 2: 1: Jog on.
Bit 3~4: 00: Rev led is off and
FWD led is on.
01: Rev led is blink
and FWD led is on.
10: Rev led is on and
FWD led is blink.
11: Rev led is on and
FWD led is off.
Bit 5-7: Reserved
Bit 8: Master frequency source
via communication
interface
Bit 9: Master frequency source
via analog
Bit10: Running command via
communication interface
Bit11: Parameter locked
Bit12~15: Reserved
Read
00-03 Frequency Setting (F) or
Closed Loop Control Setting
Point
Read only Read
00-04 Output Frequency (H) Read only Read
00-05 Output Current (A) Read only Read
00-06 DC-BUS Voltage (U) Read only Read
00-07 Output Voltage (E) Read only Read
00-08 Output Power Factor (n) Read only Read
00- 09 Output Power (kW) Read only Read
00-10 Feedback Signal Actual
Value
Read only Read
00-11 Feedback Signal (%) Read only Read
00-12 User Target Value (Low bit)
uL 0-99.99
Read only Read
00-13 User Target Value (High bit)
uH 0-9999
Read only Read
00-14 PLC Time Read only Read
00-15 Output Reactive Power
(KVAR)
Read only Read