Specifications
VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-4
Group 2 Digital Output/Input Parameter
Parameters Functions Settings
Factory
Setting
Customer
a
02-00 Source of Frequency
Command
00: via keypad
01: via analog input AI1
02: via analog input AI2
03: via RS485 serial
communication
04: via External Reference
00
a
02-01 Source of Operation
Command
00: Controlled by the digital
keypad
01: Controlled by the external
terminals, keypad STOP
enabled.
02: Controlled by external
terminals, keypad STOP
disabled.
03: Controlled by the RS-485
communication interface,
keypad STOP enabled.
04: Controlled by the RS-485
communication interface,
keypad STOP disabled.
00
02-02 Stop Method 00: Stop = ramp to stop, E.F.
(External Fault) = coast to
stop
01: Stop = coast to stop, E.F. =
coast to stop
02: Stop = ramp to stop, E.F. =
ramp to stop
03: Stop = coast to stop, E.F. =
ramp to stop
00
a
02-03 PWM Carrier Frequency
Selections
1K~6KHz ##
02-04 Forward/Reverse Enable 00: Forward enabled
01: Reverse disabled
02: Forward disabled
00
02-05
2-wire/3-wire Operation
Control Modes
00: 2-wire: FWD/STOP,
REV/STOP
01: 2-wire: FWD/REV,
RUN/STOP
02: 3-wire operation
00
02-06 Line Start Lockout 00: Disabled
01: Enabled
01
02-07 Reserved