Specifications
VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-6
Group 3 Output Function Parameters
Parameters Functions Settings
Factory
Setting
Customer
03-00 Multi-function Output
Terminal 1
(Relay)
00: disabled
01: Indication during operation
02: Master frequency attained
03: Zero Speed (including
shutdown)
04: Over-torque
05: External Fault
06: Low voltage detection
07: Operation Mode indication
08: Fault indication
09: Master Frequency Attained 1
10: Master Frequency Attained 2
11: Over Temperature indication
12: Drive Ready
13: External Emergency Stop
(EF1)
14: Software Braking Output
15: OL or OL1 Overload Warning
16: Low Current Indication
17: PID Feedback Error
Indication
18: PLC Program Running
19: PLC Program Step
Completed
20: PLC Program Completed
21: PLC Operation Paused
01
03-01 Reserved
03-02 Master Frequency
Attained 1
0.00~160.00 Hz 0.00
03-03 Master Frequency
Attained 2
0.00~160.00 Hz 0.00
03-04 DC Fan Control 00: Fan runs on power up.
01: Fan begins upon a RUN
command. Fan stops 1
minute after a STOP
command.
02: Fan begins upon a RUN
command. Fan stops after a
STOP command
03: Fan is controlled by
temperature.
Fan will be started at
approximate 60°C.
00