VFD-L Series Preface Thank you for choosing DELTA’s VFD-L series AC Drive. The VFD-L series is manufactured using high-quality components, material and incorporating the latest microprocessor technology available. Getting Started This manual will help in the installation, parameter setting, troubleshooting, and daily maintenance of the AC motor drive. To guarantee safe operation of the equipment, read the following safety guidelines before connecting power to the AC motor drive.
VFD-L Series CHAPTER 1 RECEIVING AND INSPECTIONS 1.1 Nameplate Information ....................................................................... 1 - 1 1.2 Model Explanation .............................................................................. 1 - 1 1.3 Serial Number Explanation................................................................. 1 - 2 CHAPTER 2 STORAGE AND INSTALLATION 2.1 Storage ...............................................................................................
VFD-L Series Group 4: Input Function Parameters ........................................................ 5-16 Group 5:Multi-step Speed and PLC (Process Logic Control) Parameter.. 5-27 Group 6: Protection Parameters............................................................... 5-32 Group 7: Motor Parameters...................................................................... 5-35 Group 8: Special Parameters ...................................................................
VFD-L Series CHAPTER 1 RECEIVING AND INSPECTION 1 This VFD-L AC drive has gone through rigorous quality control tests at the factory before shipment. After receiving the AC drive, please check for the following: Receiving ' ' ' Check to make sure that the package includes an AC drive, the User Manual, dust covers and rubber bushings. Inspect the unit to insure it was not damaged during shipment. Make sure that the part number indicated on the nameplate corresponds with the part number of your order.
VFD-L Series 1.3 Series Number Explanation: 1 T 2 10 001 P ro d u c tio n n u m b e r P ro d u c tio n w e e k P ro d u c tio n y e a r 2 0 0 2 P ro d u c tio n fa c to ry (T: Ta o y u a n , W : W u ju a n g ) If there is any nameplate information not corresponding to your purchase order or any problem, please contact your distributor. 1-2 DELTA ELECTRONICS, INC.
VFD-L Series CHAPTER 2 STORAGE AND INSTALLATION 2.1 Storage The AC drive should be kept in the shipping carton before installation. In order to retain the warranty coverage, the AC drive should be stored properly when it is not to be used for an extended period of time. Ambient Conditions: Operation Storage Transportation Pollution Degree Air Temperature: -10oC to +40oC (14oF to 104oF) Atmosphere pressure: 86 to 106 kPa Installation Site Altitude: below 1000m Vibration: Maximum 9.
VFD-L Series 2.2 Installation: CAUTION The control, power supply and motor leads must be laid separately. They must not be fed through the same cable conduit / trunking. High voltage insulation test equipment must not be used on cables connected to the drive. Improper installation of the AC drive will greatly reduce its life. Be sure to observe the following precautions when selecting a mounting location.
VFD-L Series CHAPTER 3 WIRING DANGER Hazardous Voltage Before accessing the AC drive: Disconnect all power to the AC drive. Wait five minutes for DC bus capacitors discharge. Any electrical or mechanical modification to this equipment without prior written consent of Delta Electronics, Inc. will void all warranties and may result in a safety hazard in addition to voiding the UL listing. General Wiring Information Applicable Codes All VFD-L AC drives are Underwriters Laboratories, Inc.
VFD-L Series 3.1 Basic Wiring Diagram Users must connect wiring according to the circuit diagram shown below. National and State wiring codes, when wiring the VFD-L. Please follow all M a i n C ir c u i t P o w e r 5 / 8 7 6 / 6 / 9 7 7 / 7 / : 7 5 / F a c to r y d e fa u lt s e tt i n g s è 4 .7 K è M o to r + 18V M 0 4 .
VFD-L Series 3.2 Terminal Explanations Terminal Symbol Explanation of Terminal Function R/L1, S/L2, T/L3 AC line input terminals U/T1, V/T2, W/T3 AC drive output terminals motor connections Earth Ground 3 3.3 Control Terminals Explanations W ire G a u g e :2 2 -2 4 A W G To rq u e : 4 K g f-c m RA Multi-function Input 0 MI1 Multi-function Input 1 MI2 Multi-function Input 2 MI3 Multi-function Input 3 Multi-function Relay output (N.O.
VFD-L Series 3.
VFD-L Series 3.5 Wiring Notes: PLEASE READ PRIOR TO INSTALLATION. 1. 2. CAUTION: Do not connect the AC power to the U/T1, V/T2, W/T3 terminals, as it will damage the AC drive. WARNING: Ensure all screws are tightened to the proper torque rating. 3. During installation, follow all local electrical, construction, and safety codes for the country the drive is to be installed in. 4.
VFD-L Series 11. Do not monitor the signals on the circuit board while the AC drive is in operation. 12. For the single-phase rated AC drives, the AC power can be connected to any two of the three input terminals R/L1, S/L2, T/L3. Note: This drive is not intended for the use with single-phase motors. 13. Route the power and control wires separately, or at 90 + angle to each other. 14. If a filter is required for reducing EMI (Electro Magnetic Interference), install it as close as possible to AC drive.
VFD-L Series CHAPTER 4 DIGITAL KEYPAD OPERATION 4.1 Description of Digital Keypad This digital keypad includes two parts: Display panel and keypad. Display panel provides the parameter display and shows operation status of the AC drive. Keypad provides programming interface between users and AC drives.
VFD-L Series Up / Down Press the “Up” or “Down” keys momentarily to change parameter settings. These keys may also be used to scroll through different operating values or parameters. Pressing the “Up” or “Down” key momentarily, will change the parameter settings in single-unit increments. To quickly run through the range of settings, press down and hold the key. 4.
VFD-L Series CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS Group 0: User Parameters 0 - 00 Identity Code of AC Motor Drive Settings None Watts / hp 115V / 230V 40W d1 100W d2 Factory setting: d # 1/4hp d3 1/2hp d4 1hp d5 2hp d6 This parameter shows the capacity of the AC drive. Users can read Pr.0-01 to check if it is the rated current of the AC drive corresponds to the identity code shown above and the current shown below.
VFD-L Series 0 - 04 Content of User Defined Unit Settings Factory Setting: d 0 d0 Display the user-defined unit (u) d1 Display the counter value (C) d2 Display the content of PLC time (1 – tt) d3 Display the DC BUS voltage (U) d4 Display the output voltage (E) This parameter can be set during operation. Note: Display the user-defined unit, where unit = H 0 - 05 User Defined Coefficient K Settings 0-05 Factory Setting: d 1.0 d 0.1 to d 160 Unit: 0.
VFD-L Series 0 - 06 Software Version Factory Setting: d #.# Setting None The software version is read-only that stores the version number of VFD-L series software. 0 - 07 Password Input Factory Setting: d 0 Settings d 0 to d 999 Unit: 1 Pr.0-07 and Pr.0-08 work together to provide data security for the AC drive. When Pr.0-08 is set to a value other than 0, a password must be entered to alter the values of parameters. The password is the number set in Pr.0-08, which ranges from 1 to 999. Pr.
VFD-L Series Group 1: Basic Parameters 1 – 00 Maximum Output Frequency (Fo. max) Settings d 50.0 to d 400 Hz Factory Setting: d 60.0 Unit: 0.1Hz This parameter determines the AC drive’s Maximum Output Frequency. All the AC drive analog inputs (0 to +10V, 4 to 20mA) are scaled to correspond to the output frequency range. 1 - 01 Maximum Voltage Frequency Settings Factory Setting: d 60.0 d 10.0 to d 400Hz Unit: 0.
VFD-L Series 1 - 04 Mid-Point Voltage (Vmid) Settings Factory Setting: d12.0 d 2.0 to d 255V Unit: 0.1V The parameter sets the Mid-Point Voltage of any V/F curve. With this setting, the V/F ratio between Minimum Frequency and Mid-Point Frequency can be determined. This parameter must be equal to or greater than Minimum Output Voltage (Pr.1-06) and equal to or less than Maximum Output Voltage (Pr.1-02). 1 - 05 Minimum Output Frequency (Fmin) Settings Factory Setting: d 1.0 d 1.0 to d 60.
VFD-L Series 1 - 08 Lower Bound of Output Frequency Settings Factory Setting: d 0 d 0 to d100% Unit: 1% The Upper/Lower Bound is to prevent operation error and machine damage. If the Upper Bound of Output Frequency is 50Hz and the Maximum Output Frequency is 60Hz, the Maximum Output Frequency will be limited to 50Hz. If the Lower Bound of Output Frequency is 10Hz, and the Minimum Output Frequency Pr.1-05 is set at 1.
VFD-L Series F re q u e n c y M ax. O utp ut F re q . P r. 1 - 0 0 T im e A c c e l/D e c e l Tim e x (M a s t e r F re q . -M i n .O u tp u t F re q .) A c tu a l A c c e l/D e c e l T im e = 1 - 13 1 - 14 1 - 15 M a x . O u t p u t F re q . Jog Accel Time Settings d 0.1 to d 600Sec This parameter can be set during operation. Factory Setting: d 10.0 Unit: 0.1Sec Jog Decel Time Settings d 0.1 to d 600Sec This parameter can be set during operation. Factory Setting: d 10.0 Unit: 0.
VFD-L Series F re q u e n c y M ax. O utp ut f re q . P r. 1 - 0 0 Jog F re q . P r. 1 - 1 4 T im e A cce l T im e P r. 1 - 1 3 J o g o p e ra tio n com m and 1 - 16 Decel T im e P r. 1 - 1 3 OFF ON Auto-Acceleration / Deceleration Settings Factory Setting : d 0 d0 Linear acceleration / deceleration. d1 Auto acceleration, linear Deceleration. d2 Linear acceleration, auto Deceleration.
VFD-L Series From the diagram shown below, the original setting accel/decel time will be for reference when the function of the S-curve is enabled. The actual accel/decel time will be determined based on the S-curve selected (d1 to d7). F re q . A c c e l/D e c e l c h a ra c te r is tic s (1 ), (2 ) D is a b lin g S c u rv e ( 3 ) , ( 4 ) E n a b lin g S c u r v e DELTA ELECTRONICS, INC.
VFD-L Series Group 2: 2 – 00 Operation Method Parameters Source of Frequency Command Factory Setting: d 0 Settings d0 Master Frequency input determined by digital keypad. d1 Master Frequency determined by analog signal DC 0V-10V (external terminal AVI). d2 Master Frequency determined by analog signal DC 4mA 20mA (external terminal AVI). d3 Master Frequency determined by Potentiometer on the digital keypad. d4 Master Frequency operated by RS-485 serial communication interface.
VFD-L Series The parameter determines how the motor is stopped when the AC drive receives a valid stop command. 1. Ramp: the AC drive decelerates the motor to Minimum Output Frequency (Pr.1-05) and then stops according to the deceleration time set in Pr.1-10 or Pr.1-12. 2. Coast: the AC drive stops output instantly upon command, and the motor free runs until it comes to a complete stop. Hz Hz F re q . F re q .
VFD-L Series From the above table, we see that the carrier frequency of PWM output has a significant influence on the electromagnetic noise, heat dissipation of the AC drive, and the acoustic noise to the motor. 2 - 04 Reverse Operation Inhibit Settings Factory Setting: d 0 d0 enable Reverse operation d1 disable Reverse operation d2 disable Forward operation The parameter determines whether the AC drive can operate in the reverse or forward directions.
VFD-L Series Group 3: Output Function Parameters 3 - 00 Desired Frequency Attained Settings Factory Setting: d 1.0 d 1.0 to d 400 Hz Unit: 0.1Hz If a Multi-function output terminal is set to function as Desired Frequency Attained (Pr.3-03=d9), then the output will be activated when the programmed frequency is attained. F re q . M a x . O u tp u t D e te c tio n ra n g e F re q . +- 2 H z D e s ire d F re q . P r.3 - 0 2 P res et F req . A tta in e d in d ic a ti o n P r.3 - 0 3 D e s ir e d F re q .
VFD-L Series The timing diagram is shown below: D is p la y (P r.0 -0 4 = d 1 ) 2ms TRG C o u n te r T r ig g e r S ig n a l M u lti - fu n c ti o n In p u t Te rm in a l 2ms T h e w id th o f trig g e r s ig n a l s h o u ld n o t b e le s s th a n 2 m s (< 2 5 0 H z ) D e s ire d C o u n te r Va lu e A tta in e d o u tp u t (P r. 3 -0 2 = d 3 ) P re s e t C o u n te r Va lu e A tta in e d o u tp u t (P r.3 -0 1 = d 5 ) N O T E : To d is p la y c o u n te r v a lu e s e t P r.
VFD-L Series d3 Zero speed: the output will be activated when Command Frequency is lower than the Minimum Output Frequency. d4 Over-Torque Detection: the output will be activated as long as the over-torque is detected. Pr.6-04 determines the Over-Torque detection level. d5 Base-Block (B.B.) Indication: the output will be activated when the output of the AC drive is shut off by external Baseblock. d6 Low Voltage Indication: the output will be activated when low voltage is detected.
VFD-L Series Group 4: Input Function Parameters 4 - 00 Potentiometer Bias Frequency Settings d 0.0 to d 350Hz This parameter can be set during the operation. Factory Setting: d0.0 Unit: 0.1Hz 4 - 01 Potentiometer Bias Polarity Factory Setting: d 0 Settings d0 Positive bias d1 Negative bias This parameter can be set during the operation. 4 - 02 Potentiometer Frequency Gain Settings Factory Setting: d 100 d 1 to d 200% Unit: 1% This parameter can be set during the operation.
VFD-L Series M ax. O u tp u t P r.1 - 0 0 F re q . 30 60Hz F a c to r y S e tti n g s P r.1 - 0 0 = 6 0 H z - - M a x . o u tp u t F re q . P r.4 - 0 0 = 0 H z - - P o te n tio m e te r b ia s fr e q . P r.4 - 0 1 = 0 - - b i a s p o la r i ty P r.4 - 0 2 = 1 0 0 % - - p o t. fr e q . g a in P r.4 - 0 3 = 0 - - p o t.
VFD-L Series Example 4: This example shows a potentiometer range of 0 to 5 Volts. M ax. O u tp u t P r.1 - 0 0 F re q . 60Hz G a in a d ju s tm e n t P r.1 - 0 0 = 6 0 H z - - M a x . o u tp u t F r e q . P r.4 - 0 0 = 0 H z - - P o te n tio m e te r b ia s fr e q . P r.4 - 0 1 = 0 - - b i a s p o la r i ty P r.4 - 0 2 = 2 0 0 % - - p o t. fr e q . g a in P r.4 - 0 3 = 0 - - p o t. R E V m o tio n e n a b l e 30Hz 0Hz 0V 30 P a ra m e te r S e tt in g s C a l c u la ti o n o f g a in 10V P r.
VFD-L Series Example 7: In this example, the potentiometer is programmed to run a motor is both forward and reverse direction. A motor will be idle when the potentiometer position is at mid-point of its scale. Using Pr.4-03 will disable the external FWD and REV controls. M ax. O u tp u t P r.1 - 0 0 F re q. 60H z FW D 30H z 0H z 0V 5V 30H z REV 0 P a r a m e te r S e tti n g s FW D. R E V. P r.1 - 0 0 = 6 0 H z - - M a x . o u tp u t F r e q . P r.
VFD-L Series Parameters & Functions table: Value Function Value d 0 (input not used) d11 M0: FWD / STOP M1: REV / STOP M0: RUN / STOP d2 M1: FWD / REV d12 d1 d13 d3 3-Wire Operation Control mode (M0,M1,M2) d4 d5 d6 d7 d8 d9 d10 External Fault ( Normally Open) External Fault ( Normally Closed ) External Reset Multi-Step Speed Command 1 Multi-Step Speed Command 2 Jog operation Accel/Decel Speed Inhibit Function First or Second Accel/Decel Time Selection External Base Block (N.O.
VFD-L Series Note: Multi-function Input Terminal M0 does not have its own parameter designation. M0 must be used in conjunction with M1 to operate two and three wire control. d3: Three Wire Control: Restricted to Pr.4-04 control terminals M0, M1, M2.
VFD-L Series Note: the External Reset has the same function as the MODE/RESET key on the Digital keypad. After external fault such as O.H., O.C. and O.V. are clear, this input can be used to reset the drive. d7, d8 Multi-Step Speed Command: Parameter values d7, d8 programs any two of the following Multi-Function Input Terminals: M1 (Pr.4-04), M2 (Pr.4-05), or M3 (Pr.4-06) for multi-step speed command function.
VFD-L Series Note: Jog operation programmed by d9 can only be initiated while the motor is stopped. (Refer to Pr.1-13, Pr.1-14.) d10 Accel/Decel Speed Inhibit: Parameter value d10 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05) or M3 (Pr.4-06) for Accel/Decel Inhibit. When the command is received, acceleration and deceleration is stopped and the AC drive maintains a constant speed.
VFD-L Series d12, d13 External Base Block: Parameter values d12, d13 program Multi-Function Input Terminals: M1 (Pr.4-04), M2 (Pr.4-05) or M3 (Pr.4-06) for external Base Block control. Value d12 is for normally open (N.O.) input, and value d13 is for a normally closed (N.C.) input. B .B .(N .O .) M x " C lo s e " : O p e ra tio n a v a ila b le . s e ttin g b y d 1 2 B .B .(N .C .) M x " O p e n " :O p e ra tio n a v a ila b le .
VFD-L Series d16, d17 PLC Function Control: Parameter value d16 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05) or M3 (Pr.4-06) to enable the AC drive internal PLC program. Parameter value d17 programs an input terminal to pause the PLC program. P L C o p e ra tio n M x " C lo s e " : R u n P L C . s e ttin g b y d 1 6 M x " O p e n " :P a u s e P L C . s e ttin g b y d 1 7 GND Note: Pr.5-00 to Pr.5-08 define the PLC program.
VFD-L Series d19 Counter Reset: Parameter value d19 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05) or M3 (Pr.4-06) to reset the counter. R e s e t c o u n te r M x " c lo s e " : re s e t c o u n te r. d 1 9 re s e t th e c o u n te r v a lu e . GND d20 Select ACI / Deselect AVI: Parameter value d20 allows the user to select the input type ACI or AVI via an external switch. AVI is selected when the contact is open and ACI is selected when the contact is closed.
VFD-L Series Group 5: Multi-step Speed, Process Logic Control Parameters 5 - 00 5 - 01 5 - 02 1st Step Speed Frequency 2nd Step Speed Frequency 3rd Step Speed Frequency Settings Factory Setting: d 0.0 Factory Setting: d 0.0 Factory Setting: d 0.0 d 0.0 to d 400 Hz Unit: 0.1Hz This parameter can be set during operation. The Multi-Function Input Terminals (refer to Pr.4-04 to 4-06) are used to select one of the AC drive Multi-Step speeds. The speeds (frequencies) are determined by Pr.
VFD-L Series F re que nc y P r.5 - 0 2 40H z M a s te r f r e q .= 5 H z 5-0 0=1 0 H z 4-0 6=d 16 5-0 1=2 0 H z 5-0 3=d 1 5-0 2=4 0 H z 5-0 4=d 0 5-0 5=1 0 5-0 6=1 0 5-0 7=1 2 5-0 8=1 5 Sec Sec Sec Sec 30H z P r.5 - 0 1 20H z 15H z M a s te r 1 0 H z F re q. 5H z 0H z P r o g r a m o p e r a tio n com mand P r.
VFD-L Series Example 3 (Pr. 5-03 = d3) Execute one cycle step by step: The example shows how the PLC can perform one cycle at a time, within a complete cycle. Each step will use the accel/decel times in Pr.1-09 to Pr.1-12. It should be noticed that the time each step spends at its intended frequency is diminished, due to the time spent during accel/decel. M a s te r f r e q .
VFD-L Series 5 - 04 PLC Forward/Reverse Motion Settings Factory Setting: d 0 d 0 to d 15 This parameter controls the direction of motion for the Multi-Step Speed Pr.5-00 to Pr.5-02 and the Master Frequency. The original direction of Master Frequency will become invalid. The equivalent 4-bit number is used to program the forward/reverse motion for each of the 4 speed steps (including Master Frequency). The binary notation for the 4-bit number must be translated into decimal notation and then be entered.
VFD-L Series 5 – 05 5 – 06 5 – 07 5 – 08 Time Duration Step 0 Time Duration Step 1 Time Duration Step 2 Time Duration Step 3 Settings Factory Setting: d 0 Factory Setting: d 0 Factory Setting: d 0 Factory Setting: d 0 d 0 to d 65500 Unit: 1 sec Pr.5-05 to Pr.5-08 correspond to operation time of each multi-step speed defined by parameters 5-00 to 5-02. The maximum value of these parameters is 65500 sec., and it’s displayed as d 65.5.
VFD-L Series Group 6: 6 - 00 Protection Parameters Over-Voltage Prevention Level Settings d0 Disable Over-Voltage Prevention d 350 to d 410 Factory Setting: d 390 Unit: 1 VAC During deceleration, the motor DC bus voltage may exceed its Maximum Allowable Value due to motor regeneration. When this function is enabled, the AC drive will stop decelerating. Maintaining a constant output frequency when it happens. The AC drive will only resume deceleration when the voltage drops below preset value.
VFD-L Series 6 - 02 Over-Torque Detection Mode Settings 6 - 03 Factory Setting: d 0 d0 Over-Torque detection disabled. d1 Over-Torque detection enabled during constant speed operation (OL2), and operation continues until the continuous operation limit (Pr.6-04) is reached. d2 Over-Torque detection enabled during constant speed operation, and operation halted after over-torque detection.
VFD-L Series 6 – 06 Electronic Thermal Characteristic Settings Factory Setting: d 60 d 30 to d 600Sec Unit: 1 Sec This parameter can be set during operation. The parameter determines the time required activating the I2t electronic thermal protection function. The graph below shows I2t curves for 150% output power for 1 minute.
VFD-L Series Group 7: Motor Parameters 7 - 00 Motor Rated Current Factory Setting: d 85 Settings d 30 to d 120% This parameter can be set during operation. Unit: 1% This parameter will limit the AC drive output current in order to prevent the motor from overheating. 7 - 01 Motor No-load Current Settings d 0 to d 90 Factory Setting: d 50 ¦ Unit: 1% This parameter can be set during operation. The rated current of the AC drive is regarded as 100%.
VFD-L Series Group 8: Special Parameters 8 - 00 DC Braking Voltage Level Factory Setting: d 0 Settings d 0 ⇔ d30% Unit: 1% This parameter determines the level of DC Braking Voltage Level output to the motor during start-up and stopping. When setting DC Braking Voltage, the Maximum Output Voltage (Pr.1-02) is regarded as 100%. It is recommended to start with a low DC Braking Voltage Level and then increase until proper holding torque has been attained.
VFD-L Series 2. DC Braking during stopping is used to decrease stopping time and also to hold a stopped load in position. For high inertial loads, a dynamic braking resistor may be needed for quick decelerations.
VFD-L Series Power In p u t M a x im u m A llo w a b le P o w e r L o s s T im e 08 -05 Speed Search 08 -04 =d1 O u tp u t F re q u e n c y S p e e d s e a r c h s ta r ts w ith th e M a s te r F re que nc y O u tp u t V o lta g e 8 - 08 8 - 09 8 - 10 8 - 11 8 - 12 8 - 13 Speed S y n c h r o n iz a tio n D e te c tio n 08 -06 B a s e b lo c k T im e Skip Frequency 1 Upper Bound Skip Frequency 1 Lower Bound Skip Frequency 2 Upper Bound Skip Frequency 2 Lower Bound Skip Frequency 3 Upper Bound Skip
VFD-L Series 8 - 15 Automatic Voltage Regulation (AVR) Settings d0 AVR function enabled d1 AVR function disabled Factory Setting: d 2 d2 AVR function disabled when deceleration AVR function automatically regulates the AC drive output voltage to the Maximum Output Voltage (Pr.1-02). For instance, if Pr.1-02 is set at 200 VAC and the input voltage is at 200V to 264VAC, then the Maximum Output Voltage will automatically be regarded to 200 VAC.
VFD-L Series Group 9: 9 - 00 Communication Parameters Communication Address Settings Factory Setting: d 1 d 1 to 247 This parameter can be set during operation. If the AC drive is controlled by RS-485 serial communication, the communication address must be set via this parameter.
VFD-L Series 9 - 03 Modbus Communication Watchdog Timer Settings d0 Factory Setting: d 0 Disable d1 to d20 Unit: 1 sec 1 to 20 sec This parameter can be set during operation. If the Watchdog timer function is enabled, the timer will start counting once the first valid Modbus communication signal is received after power-up or reset. The timer will reset to 0 after each valid Modbus communication message is received. If the watchdog timer reaches the value set in Pr.
VFD-L Series VFD-L can be setup to communicate on Modbus networks using one of the following modes: ASCII (American Standard Code for Information Interchange) or RTU (Remote Terminal Unit). Users can select the desired mode along with the serial port communication protocol in Pr. 9-04. Code Meaning: ASCII mode: Each 8-bit data is the combination of two ASCII characters. For example, a 1-byte data: 64 Hex, shown as ‘64’ in ASCII, consists of ‘6’ (36Hex) and ‘4’ (34Hex).
VFD-L Series 2.2 11-bit character frame (For 8-bit character): ( 8 . N .2 : P r.9 - 0 4 = 3 o r 6 ) S ta rt bit 0 1 2 3 4 5 6 7 S top S top b it b it 6 7 E ven S t o p parity b i t 6 7 O dd S t o p parity b i t 8 - b i t c h a r a c te r 11 - b i t c h a r a c t e r f r a m e ( 8 .E .1 :P r. 9 - 0 4 = 4 o r 7 ) S ta rt bit 0 1 2 3 4 5 8 - b i t c h a r a c te r 11 - b i t c h a r a c t e r f r a m e ( 8 . O .1 : P r.
VFD-L Series 3.2 ADR (Communication Address) Valid communication addresses are in the range of 0 to 254. Communication address equals to 0 means broadcast to all AC drives (AMD), in this case, the AMD will not reply any message to the master device. For example, communication to AMD with address 16 decimal: ASCII mode: (ADR 1, ADR 0)=’1’,’0’ => ‘1’=31H, ‘0’=30H RTU mode: (ADR)=10H 3.3 CMD (Command code) and DATA (data characters) The format of data characters depends on the command code.
VFD-L Series RTU mode: Command message: Response message: ADR 01H ADR 01H CMD 03H CMD 03H Starting data address Number of data (count by word) CRC CHK Low CRC CHK High 21H 02H 00H 02H 6FH F7H Number of data (count by byte) Content of data address 2102H Content of data address 2103H CRC CHK Low CRC CHK High 04H 17H 70H 00H 00H FEH 5CH Command code: 06H, write 1 word For example, writing 6000(1770H) to address 0100H of AMD with address 01H.
VFD-L Series RTU mode: Command message: Response message: ADR 01H ADR 01H CMD 06H CMD 06H Data address 01H 00H 17H 70H 86H 22H Data address 01H 00H 17H 70H 86H 22H Data content CRC CHK Low CRC CHK High Data content CRC CHK Low CRC CHK High 3.
VFD-L Series CRC (Cyclical Redundancy Check) is calculated by the following steps: Step 1: Load a 16-bit register (called CRC register) with FFFFH. Step 2: Exclusive OR the first 8-bit byte of the command message with the low order byte of the 16-bit CRC register, putting the result in the CRC register. Step 3: Shift the CRC register one bit to the right with MSB zero filling. Extract and examine the LSB.
VFD-L Series 3.5 Address list: The contents of available addresses are shown as below: Content AC drive Parameters Address ggnnH Command 2000H 2001H 2002H Status monitor Read only 2100H Functions gg means parameter group, nn means parameter number, for example, the address of Pr 4-01 is 0401H. Referencing to chapter 5 for the function of each parameter. When reading parameter by command code 03H, only one parameter can be read at one time.
VFD-L Series Content Status monitor Read only Address 2100H 2101H 2102H 2103H 2104H 2105H 2106H 2107H 2108H 2109H 210AH DELTA ELECTRONICS, INC.
VFD-L Series 3.6 Exception response: Except for broadcast messages, the AC drive is been expected to return a normal response after receiving command messages from the master device. The following depicts the conditions that no normal response is replied to the master device. The AC drive does not receive the messages due to a communication error; thus, the AC drive has no response. The master device will eventually process a timeout condition.
VFD-L Series Error message 1 2 3 4 5 Meaning Illegal command code: The command code received in the command message is not available for the AC drive. Illegal data address: The data address received in the command message is not available for the AC drive. Illegal data value: The data value received in the command message is not available for the AC drive. Slave device failure: The AC drive is unable to perform the requested action.
VFD-L Series 3.7 Communication program of PC: The following is a simple example of how to write a communication program for Modbus ASCII mode on a PC by C language. #include #include #include #include
VFD-L Series <7,E,1>=1AH, <7,O,1>=0AH <8,N,2>=07H, <8,E,1>=1BH <8,O,1>=0BH */ for(i=0;i<=16;i++){ while(!(inportb(PORT+LSR) & 0x20)); /* wait until THR empty */ outportb(PORT+THR,tdat[i]); /* send data to THR */ } i=0; while(!kbhit()){ if(inportb(PORT+LSR) & 0x01){ /* b0==1, read data ready */ rdat[i++]=inportb(PORT+RDR); /* read data form RDR */ } } } DELTA ELECTRONICS, INC.
VFD-L Series CHAPTER 6 MAINTENANCE AND INSPECTIONS Modern AC drives are based on solid state electronics technology, preventive maintenance is required to operate this AC drive in its optimal condition, and to ensure a long life. It is recommended to perform a monthly check up of the AC drive by a qualified technician. Before the check up, always turn off the AC Input Power to the unit. Wait at least 2 minutes after all display lamps have gone out. 6.
VFD-L Series CHAPTER 7 Troubleshooting and Fault Information The VFD-L AC drive has a comprehensive fault diagnostic system that includes several different alarms and fault messages. Once a fault is detected, the corresponding protective functions will be activated. The following faults are displayed on the AC drive digital keypad. The six most recent faults can be read on the digital keypad display by viewing Pr.6-07 to Pr.6-12. NOTE: Faults can be cleared by a reset from the keypad or Input Terminal.
VFD-L Series Fault Name Fault Descriptions The AC drive temperature sensor detects excessive heat. The AC drive detects that the DC bus voltage has fallen below its minimum value. The AC drive detects excessive drive output current. Corrective Actions 1. Ensure that the ambient temperature falls within the specified temperature range. 2. Make sure that the ventilation holes are not obstructed. 3. Remove any foreign objects on the heatsinks and check for possible dirty heat sink fins. 4.
VFD-L Series Fault Name Fault Descriptions Over-current during acceleration: 1. Short-circuit at motor output. 2. Torque boost too high. 3. Acceleration time too short. 4. AC drive output capacity is too small. Over-current during deceleration: 1. Short-circuit at motor output. 2. Deceleration time too short. 3. AC drive output capacity is too small. Over-current during steady state operation: Corrective Actions 1. Check for possible poor insulation at the output line. 2.
VFD-L Series Fault Name Fault Descriptions Corrective Actions Internal memory IC can 1. Return to the factory. not be read. 2. Reset drive to factory defaults. Drive’s internal circuitry abnormal. Return to the factory. Hardware protection failure Return to the factory. Software protection failure Return to the factory. Auto accel/decel failure Don’t use the function of auto acceleration /deceleration. External Base Block. 1. When the external input terminal (B.
VFD-L Series CHAPTER 8 SUMMARY OF PARAMETER SETTINGS Group 0: User Parameters Parameters = Functions 0-00 Identity code of drive (Read only) 0-01 Rated current display (Read only) 0-02 0-03 Parameter reset Start-up display of AC drive = 0-04 User-defined Unit = 0-05 User-defined coefficient K Software version Password input Password configuration 0-06 0-07 0-08 =The parameter may be set during operation. Settings 1: 40W 2: 100W 3: 200W 4: 400W 5: 750W 6: 1.5KW 40W: 0.4A 100W: 0.
VFD-L Series = = = = = = = Parameters Functions 1-06 1-07 1-08 1-09 1-10 1-11 1-12 1-13 1-14 1-15 1-16 Minimum output voltage Upper bound of freq. Lower bound of freq. Accel time 1 (Tacc1) Decel time 1 (Tdec1) Accel time 2 Decel time 2 JOG Accel time JOG Decel time JOG frequency Auto-accel/decel 1-17 1-18 Settings 2.0 ~ 255V 1 ~ 110% 0 ~ 100% 0.1 ~ 600 Sec 0.1 ~ 600 Sec 0.1 ~ 600 Sec 0.1 ~ 600 Sec 0.1 ~ 600 Sec 0.0 ~ 600 Sec 1.
VFD-L Series 2-04 Reverse operation inhibit 0: Enable reverse 1: Disable reverse 2: Disable forward 0 2-05 ACI (4 ~ 20mA) input loss detection 0: Accel to 0Hz 1: Stop immediately, display EF 2: Run with the last freq. 0 2-06 Line Start Lockout 0: Enable 1: Disable 0 Group 3: Output Function Parameters Parameters 3-00 3-01 3-02 3-03 Functions Settings Desired freq. attained Terminal count value Preliminary count value Multi-function (relay output) 1.
VFD-L Series Parameters Functions 4-04 4-05 4-06 Multi-function input terminal1 (M0, M1) (d 0 d 20) Multi-function input terminal 2(M2) Multi-function input terminal 3(M3) (d 0, d 4 d 20) Settings 0: not used 1: M0: FWD/STOP, M1:REV/STOP 2: M0: FWD/REV, M1:RUN/STOP 3: M0, M1, M2: 3-wire operation control mode 4: External fault, normally open (N.O.) 5: External fault, normally closed (N.C.
VFD-L Series Group 6: Protection Parameters Parameters 6-00 6-01 6-02 6-03 6-04 6-05 6-06 6-07 6-08 6-09 6-10 6-11 6-12 Functions Settings Over-Voltage Prevention Level Over-current Prevention Level Over-torque detection 0:disable 350~410V 0: disable 20~200% 0:disable 1:enable during constant speed operation and continues until the continuous limit is reached. 2:enabled during constant speed operation and halted after detection.
VFD-L Series Group 7: Motor Parameters Parameters = = = = Functions Settings Factory Setting 7-00 Motor rated current 30~120 % 85 7-01 Motor no-load current 0 ~ 90 % 50 7-02 Torque compensation 0 ~ 10 1 7-03 Slip compensation 0.0 ~ 10.0 0.0 Group 8: Special Parameters Parameters Functions Settings Factory Setting 8-00 DC braking voltage level 0 ~ 30% 0 8-01 DC braking time during start-up 0.0 ~ 60.0 Sec 0.0 8-02 DC braking time during stopping 0.0 ~ 60.0 Sec 0.
VFD-L Series Parameters Functions Settings Factory Setting 8-14 Auto restart after fault 0~10 0 8-15 AVR function 0: AVR function enable 1: AVR function disable 2: AVR function disable when decel 2 8-16 Dynamic braking voltage 350 ~ 450V 8-17 DC braking lower bound 0.0 ~ 400 Hz limit 380 0.
VFD-L Series SPECIFICATIONS Voltage Class 115V Model Number VFD- L A/B Output Rating Applicable Motor Output (kW) Rated Output Capacity (KVA) Rated Output Current (A) Max. Output Voltage (V) Power Input voltage Tolerance Control Characteristics Frequency tolerance Operating Characteristics 004 0.2 0.4 0.6 1.0 1.6 2.5 3-phase corresponds to double input voltage 002 004 007 015 0.2 0.6 1.6 0.4 1.0 2.5 0.7 1.6 4.2 1.5 2.7 7.
VFD-L Series ACCESSORIES B.1 Non-fuse Circuit Breaker Chart Per UL 508C, paragraph 44.8.6, part a, 1. For 1-phase drives, the current rating of the breaker shall be four times maximum of input current rating. 2. For 3-phase drives, the current rating of the breaker shall be four times maximum of output current rating. (Note: Please select enough current capacity of NFB.) 1-phase 3-phase Input Current (A) Output Current (A) Model Model 1.6 VFD002L21A VFD002L11A 6.0 2.5 VFD002L21A 4.9 VFD004L21A 4.
VFD-L Series DIMENSIONS Unit: mm (inches) C DELTA ELECTRONICS, INC.
VFD-L Series DELTA ELECTRONICS, INC.
VFD-L Series DELTA ELECTRONICS, INC.