CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Preface Thank you for choosing DELTA’s high-performance VFD-V Series. VFD-V Series are manufactured by adopting high-quality components, material and incorporating the latest microprocessor technology available. Getting Started This manual will be helpful in the installation, parameter setting, troubleshooting, and daily maintenance of the AC motor drives.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series CHAPTER 1 RECEIVING AND INSPECTION 1.1 Nameplate Information ...........................................................................................1 - 1 1.2 Model Explanation..................................................................................................1 - 1 1.3 Serial Number Explanation.....................................................................................
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.6 Group 5: Motor Modulation Parameter ...................................................................5 - 4 0 5.7 Group 6: Protection Parameter...............................................................................5 - 4 5 5.8 Group 7: Special Parameter ...................................................................................5 - 5 2 5.9 Group 8: High-Performance Parameter....................
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series CHAPTER 1 RECEIVING AND INSPECTION This VFD-V AC drive has gone through rigorous quality control tests at the factory before shipment. After receiving the AC drive, please check for the following: 1 Receiving Check to make sure that the package includes an AC drive, the User Manual, dust covers and rubber bushings. Inspect the unit to insure it was not damaged during shipment.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 1.3 Serial Number Explanation 037V23A0T 0 10 9999 Production Number Production Week Production Year Production Factory Production Model 230V 3-PHASE 5HP(3.7kW) ●Please contact the dealers immediately should any discrepancy occurred. 1-2 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series CHAPTER 2 STORAGE AND INSTALLATION 2.1 Storage The AC drive should be kept in the shipping carton before installation. In order to retain the warranty coverage, the AC drive should be stored properly when it is not to be used for an extended period of time. 2 Ambient Conditions: Operation Air Temperature: -10oC to +40oC (14oF to 104oF) +50oC (122oF) without dust cover.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 2.2 Installation CAUTION The control, power supply and motor leads must be laid separately. They must not be fed through the same cable conduit / trunking. High voltage insulation test equipment must not be used on cables connected to the drive. Improper installation of the AC drive will greatly reduce its life. following precautions when selecting a mounting location.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series CHAPTER 3 WIRING DANGER Hazardous Voltage Before accessing the AC drive: Disconnect all power to the AC drive. Wait five minutes for DC bus capacitors discharge. 3 Any electrical or mechanical modification to this equipment without prior written consent of Delta Electronics, Inc. will void all warranties and may result in a safety hazard in addition to voiding the UL listing.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 3.1 Basic Wiring Diagram For wiring of the inverter, it is divided into the main circuit and the control circuit. Users could open the case cover, and could inspect the main circuit terminal and the control circuit terminal; users connect the circuit in compliance with the following wiring method. The following diagram is the standard wiring diagram for the VFD-V inverter. Wiring Diagram 1 10HP(7.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Wiring Diagram 2 15HP(11kW) and above DC chock (optional) Fuse/NFB(None Fuse Breaker) +1 R/L1 S/L2 T/L3 E R/L1 S/L2 T/L3 Recommended Circuit when power supply is turned OFF by a fault output Factory Default: SINK Mode SA MC ON OFF REV/STOP Sw1 Multi-step 1 Source Please refer to wiring of SINK mode and SOURCE mode.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 3.2 External Wiring Items Explanations Please follow the specific power Power supply requirement shown in supply APPENDIX-A. There may be inrush current during Fuse/NFB power up. Please check the chart of APPENDIX B and select the correct (Optional) fuse with rated current. NFB is optional.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 3.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 3.5 Component Explanations 1 HP to 5 HP (VFD007V23A/43A, VFD015V23A/43A, VFD022V23A/43A, VFD037V23A/43A) +1 +2 B1 - B2 U/T1 V/T2 W/T3 Screw Torque : 18Kgf-cm Wire Gauge : 18~10AWG R/L1 S/L2 T/L3 Control Terminal Torque: 8Kgf-cm (6.9 in-lbf) Wire: 22-14 AWG Power Terminal Torque: 18 kgf-cm (15.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 7.5 HP to 15 HP (VFD055V23A/43A, VFD075V23A/43A, VFD110V43B) 3 POWER IM 3 MOTOR Control Terminal Torque: 8Kgf-cm (6.9 in-lbf) Wire: 22-14 AWG Power Terminal Torque: 30 kgf-cm (26 in-lbf) Wire Gauge: 12-8 AWG Wire Type: Stranded Copper only, 75°C Note: If wiring of the terminal utilizes the wire with a 6AWG-diameter, it is thus necessary to use the Recongnized Ring Terminal to conduct a proper wiring.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 15HP to 30HP (VFD110V23A/43A, VFD150V23A/43A, VFD185V23A/43A, VFD220V23A/43A) R/L1 S/L2 T/L3 +1 POWER +2 DC (+) - DC ( - ) V/T2 W/T3 IM 3 MOTOR Control Terminal Torque: 8Kgf-cm (6.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 40 to 50 HP 230V (VFD300V23A, VFD370V23A) 3 POWER ALARM CHARGE R/L1 S/L2 T/L3 POWER +1 +2 Screw Torque: 200kgf-cm (173in-lbf) U/T1 V/T2 W/T3 IM 3 MOTOR Control Terminal Torque: 8Kgf-cm (6.9 in-lbf) Wire: 22-14 AWG Power Terminal Torque: 200 kgf-cm (173.6 in-lbf) Wire Gauge: 1/0 – 4/0 AWG Wire Type: Stranded Copper only, 75°C DELTA ELECTRONICS, INC.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 40HP to 60HP 460V (VFD300V43A, VFD370V43A, VFD450V43A) POWER ALARM CHARGE R/L1 S/L2 T/L3 +1 +2 - POWER U/T1 V/T2 2/T3 IM 3 MOTOR Control Terminal Torque: 8Kgf-cm (6.9 in-lbf) Wire: 22-14 AWG Power Terminal Torque: 57 kgf-cm (49.5 in-lbf) Wire Gauge: 4-2 AWG Wire Type: Stranded Copper only, 75°C 3-12 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 75-100 HP 460V (VFD550V43A, VFD750V43A) 3 R/L1 S/L2 T/L3 POWER +1 +2 S c rew T orque: 200k gf-cm U/T1 V/T2 W/T3 MOT OR Control Terminal Torque: 8Kgf-cm (6.9 in-lbf) Wire: 22-14 AWG Power Terminal Torque: 200 kgf-cm (173.6 in-lbf) Wire Gauge: 1/0 – 4/0 AWG Wire Type: Stranded Copper only, 75°C DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CALL NOW 800-985-6929 3-13 http://www.automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 3.6 Wiring Notice 1. There are corresponding ring terminals which will be included with each unit (15-30HP), and please use the proper crimping tool by KST INC. P/N: KST-HDC38A for securing the conductor. 2. When wiring up, and that the wiring route specifications are settled, please conduct the wiring following the electrician regulations. 3.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 10. Be sure of the power voltage and the greatest current possible supplied. 11. When the “Digital Hand-held Programming Panel” is displayed, please do not disconnect or dissemble any wiring. 12.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series CHAPTER 4 DIGITAL KEYPAD (VFD-PU05) OPERATION 4.1 Description of the Digital Keypad VFD-PU05 LED Display Display frequency, current, voltage and error, etc. F H U Part Number VFD-PU05 EXT PU MODE Selection key Press this key to view different operating values JOG PU Status Display Display the driver's current status When "PU" lights, RUN/STOP is controlled by PU05.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Messages Displayed Descriptions Output current Parameter duplication function: press PROG/DATA and hold still for about 2~3 seconds, it will start blinking and will duplicate the parameter to PU-05. Press the “Up” or “Down” key to switch to the “SAVE” function Parameter duplication function: press PROG/DATA and hold still for about 2~3 seconds, it will start blinking and will write the parameter into the drive.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 4.3 Operation steps of the Digital Keypad VFD-PU05 VFD-PU05 Operation Flow Chart Or XX 4 Press UP key to select SAVE: save parameters READ: copy parameters Press PROG/DATA for about 2 seconds or until it is flashing, then save/copy data from AC drive to PU05. XX-XX XXXXX -ERR- -ENDSucceed to Write in Cannot write in DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CALL NOW 800-985-6929 4-3 http://www.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS 5.1 Group 0: System Parameter 00-00 Identity Code Settings Read Only Factory setting Read Only Based on the model type 00-01 Rated Current Display Settings Factory setting Based on the model type 230V Series Power [HP] 0.75 1.5 [1] [2] 2.2 [3] 3.7 5.5 7.5 11 15 18.5 22 30 37 [5] [7.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 00-02 Parameter Reset Settings Bit settings Factory setting 10 Parameter reset (for 60Hz input) 9 Parameter reset (for 50Hz input) 0 20 1 Bit 0 1 Parameters are read only Bit 1 1 Disable Frequency and Torque Command changes. 21 2 22 4 Bit 2 1 Keypad disable This parameter offers several functions. 1) The user may reset all parameters to their original factory settings.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 00-03 Start-up Display of the Drive Settings a Factory setting 0 0 F (Master frequency command) 1 H (Output frequency) 2 U (multi-function display of Pr. 00-04) 3 Output current This parameter allows the start-up display to be customized. The display may still be changed, but during each power on, the display will default to the setting in this parameter.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 44 46 51 53 60 84 86 torque limit (Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Pr. 00-07: This parameter allows the user to input their password and disable the parameter lockout. An incorrect password may be entered 3 times and then a “Pcode” will flash on the display, alerting the user the password is incorrect. The drive must be powered off and then powered on again to clear the Pcode display. Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Bit1 = This setting allows the frequency/torque commands of PU05 and RS485 to either be retained or forgotten after power has been removed. Bit2 = This setting allows the frequency/torque commands of the UP/DOWN external terminals to either be retained or forgotten after power has been removed. Bit3 = This setting allows the FWD/REV direction to either be retained or forgotten after power has been removed.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 4: Torque control: Enables Torque (current) Control. Torque control allows the user to run the AC drive based on current instead of frequency. 5: Torque control + PG: Enables the Closed Loop Torque Control. This will increase the torque accuracy throughout the speed range and disabled Pr. 05-04. Note: PI values for PG (closed loop), vector control (open loop) and torque control are determined by Pr. 05-21~05-25.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series This parameter may also be used in Vector control to determine if the drive will skip the zero point. If the drive skips the zero point, it will stop at the frequency determined by Pr.01-09 and then start again in the opposite direction at Pr.01-09. The Vector control will generate its own V/F curve, therefore please select 0 or 1 for this parameter setting when in Vector mode.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 00-15 Carrier Frequency Upper Bound Settings a Factory setting 10 a Factory setting 10 a Factory setting 3 0: soft pwm 1~15KHz 00-16 Carrier Frequency Lower Bound Settings 1-15KHz (disabled during soft PWM) 00-17 Center Frequency of Soft pwm Settings 1~7KHz This parameter is utilized in setting the carrier frequency of the PWM output.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series If the carrier frequency’s lower bound (Pr. 00-16) > the carrier frequency’s upper bound (Pr. 00-15), then the carrier frequency will be operated at the upper bound level. 00-18 Auto Voltage Regulation (AVR) Function Settings a Factory setting 0 0 AVR function enabled 1 AVR function disabled 2 AVR function disabled during deceleration This parameter selects the AVR mode. the motor.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Ramp to stop: The drive will ramp down from maximum output frequency (Pr. 01-00) to minimum output frequency (Pr. 01-09) based on the deceleration time (Pr. 01-13). Coast to stop: the drive will stop the output instantly upon a STOP command and the motor will coast to stop according to its inertia (time unknown).
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.2 Group 1: Basic Parameter 01-00 Maximum Output Frequency Settings Factory setting 60.00/50.00 50.0~400.00Hz This parameter determines the drive’s maximum output frequency. 01-01 Maximum Voltage Frequency (Base Frequency) Settings Factory setting 60.00/50.00 0.00~400.00 Hz This parameter must be set to the motor’s nameplate frequency rating. 01-02 Maximum Output Voltage Settings 230V: 0.0~255.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series When setting the V/F curve, please follow this hierarchy for frequency: 01-01≥01-03≥01-05≥01-07. There is no hierarchy for the voltage setting, but a high voltage at low output frequencies may cause motor failure. At low frequencies, always use the lowest voltage necessary for the application. 01-09 Startup Frequency Settings a Factory setting 0.50 0.00~400.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 01-12 1st Acceleration Time a Factory setting 10.00/60.00 st 01-13 1 Deceleration Time a Factory setting 10.00/60.00 01-14 2nd Acceleration Time a Factory setting 10.00/60.00 nd 01-15 2 Deceleration Time a Factory setting 10.00/60.00 rd 01-16 3 Acceleration Time a Factory setting 10.00/60.00 01-17 3rd Deceleration Time a Factory setting 10.00/60.00 th a Factory setting 10.00/60.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 01-00 Maximum Operation Frequency Set Point of the Operation Frequency Time 01-12 01-16 01-20 01-14 01-18 01-13 01-16 01-21 01-15 01-19 Definition of the Acceleration/Deceleration Time 01-22 JOG Frequency a Factory setting 6.00 Settings 0.00Hz~400.00Hz This parameter determines the Jog frequency. The Jog function may be selected by the JOG key on the PU05 keypad or the external I/O terminals.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Frequency 1st Acceleration Time 01-23 1st/4th Acceleration /Deceleration Freq. 1st Deceleration Time 4th Deceleration Time 4th Acceleration Time 1st/4th Acceleration/Deceleration Switching 01-24 S-Curve for Acceleration Departure Time a Factory setting 0.00 01-25 S-Curve for Acceleration Arrival Time a Factory setting 0.00 01-26 S-Curve for Deceleration Departure Time a Factory setting 0.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 01-28 Skip Frequency 1 (upper limit) Factory setting 0.00 01-29 Skip Frequency 1 (lower limit) Factory setting 0.00 01-30 Skip Frequency 2 (upper limit) Factory setting 0.00 01-31 Skip Frequency 2 (lower limit) Factory setting 0.00 01-32 Skip Frequency 3 (upper limit) Factory setting 0.00 01-33 Skip Frequency 3 (lower limit) Factory setting 0.00 Settings 0.00~400.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.3 Group 2: Digital Output/Input Parameter 02-00 2-Wire/3-Wire Operation Control Factory setting 0 0 FWD/STOP, REV/STOP Settings 1 FWD/STOP, REV/STOP (Line Start Lockout) 2 RUN/STOP, REV/FWD 3 RUN/STOP, REV/FWD (Line Start Lockout) 4 3-wire (momentary push button) 5 3-wire (momentary push button and Line Start Lockout) The VFD-V drive offers six types of external operation control.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Settings Functions Explanations 21 Digital Down Command 22 Auto procedural operation function disabled 23 Auto procedural operation suspended 24 PID function disabled When this terminal is functioning, the currently displayed counter value will be cleared and “0” is then displayed; the drive could only accept the trigger signals to keep counting upward after this signal disappeared.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Settings Functions Explanations 40 P2P Hold P2P is pause. AC drive keeps outputting at this moment. It will keep on unfinished jog after terminal is closed. 41 FWD Home Search In speed mode, it will do FWD home search according to the setting of 10-09. P2P FWD Limit In P2P mode, it is used with FWD limit sensor. When it reaches FWD limit during running, it will stop free running.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 02-10 Digital Input Operation Direction Settings a Factory setting 0 0~65535 Bit 0~7 1 High active This parameter determines the level of the input signal operation.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Example: If Pr.02-10 is 1 (AC Drive running), and Relay 1 is set to N.O., then R1 close when the drive has an output and will open when the drive has stopped. Settings Bit content Relay 1 03-07 Relay 2 03-08 MO1 03-09 MO2 03-10 0 0000 N.O. N.O. N.O. N.O. 1 0001 N.O. N.O. N.O. N.C. 2 0010 N.O. N.O. N.C. N.O. 3 0011 N.O. N.O. N.C. N.C. 4 0100 N.O. N.C. N.O. N.O. 5 0101 N.O.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 0.5ms Display (Pr.00-04=07) TRG Counter Trigger (Output signal) Multi-function output terminal Pr. 02-10~02-13 02-12=22 Desired Counter Value Attained output Preset Counter Value Attained output 0.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.4 Group 3: Analog Output/Input Parameter 03-00 Analog Input 1 (AVI) a Factory setting 1 03-01 Analog Input 2 (ACI) a Factory setting 0 03-02 Analog Input 3 (AUI) a Factory setting 0 Settings Function 0 no function (analog input disabled) 1 frequency/torque command (See Pr.00-10) 2 torque limitations (increase or decrease torque limit Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 03-09 Analog Input 1 Gain (AVI) Settings a Factory setting 125.0 a Factory setting 100.0 -500.0~+500.0% 03-11 Analog Input 3 Gain (AUI) Settings 100.0 -500.0~+500.0% 03-10 Analog Input 2 Gain (ACI) Settings a Factory setting -500.0~+500.0% Pr.03-09 to 03-11 are used to adjust the 10V or 20mA corresponding frequency value. Example: If Pr.03-00 = 10, Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Example 3: 60Hz 03-06=1 03-09= Example 4: 9V 10V 60Hz X=10.8 9-10.8=-1.8 03-06=1 03-09= 0V 60 X100%=83.3% 10 50 10 03-03 50 60 = 10 X 10Hz Example 5: 60 X100%=92.5% 10 03-03 50 60 = 9 X 10Hz 0V 50 9 10V 5 X=12 10-12=-2 60Hz 03-03=1 03-06=1 60 9 1V Example 6: 10V 60Hz 03-03=0 03-06=d0 30Hz 30 10 0V 60 X100%=50% 10 10V DELTA ELECTRONICS, INC.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Example 7: 60Hz 03-03=5 03-06=3 0V Example 8: 5V 60 X100%=200% 10 120 20 10V 60Hz 03-03=10 03-06=0 03-09=-100% 10V Example 9: 60Hz FWD 03-03=5 03-06=d 0 0V 5V REV 10V 60 X100%=200% 10 120 10 60Hz Example 10: 60Hz FWD 03-05=0 03-08=0 -10V 0V REV 10V 60 X100%=100% 10 60Hz 5-32 CALL NOW 800-985-6929 120 20 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 03-13 Analog Input Noise Filter Settings a Factory setting 0.10 0.00~2.00 Sec Interferences commonly exist with analog signals, such as those entering AVI, ACI and AUI. These interferences constantly affect the stability of analog control and using the Input Noise Filter will create a more stable system. If Pr. 03-13 is large, the control will be stable, yet the response to the input will be slow. If Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series If the meter reads full scale at a voltage less than 10 volts, then Pr.03-16 should be set by the following formula: Pr.03-16 = ((meter full scale voltage)/10) ×100% For Example: When using the meter with full scale of 5 volts, adjust Pr.03-16 to 50%. 03-17 Analog Output Bias Voltage Settings a Factory setting 0.00 -10.00~10.00V This parameter determines the output voltage value corresponding to 0Hz.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.5 Group 04: Multi-Step Speed and Process Control Operation (PCO) 04-00 The 1st Step Speed a Factory setting 0.00 nd 04-01 The 2 Step Speed a Factory setting 0.00 04-02 The 3rd Step Speed a Factory setting 0.00 th a Factory setting 0.00 th 04-04 The 5 Step Speed a Factory setting 0.00 04-05 The 6th Step Speed a Factory setting 0.00 04-03 The 4 Step Speed th a Factory setting 0.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 0=Forward 1=Reverse Direction of 1st speed for Pr.04-00 Weights Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Direction of 2nd speed for Pr.04-01 Direction of 3rd speed for Pr.04-02 Direction of 4th speed for Pr.04-03 Direction of 5th speed for Pr.04-04 Direction of 6th speed for Pr.04-05 Direction of 7th speed for Pr.04-06 Direction of 8th speed for Pr.04-07 Direction of 9th speed for Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 04-33 Process Control Operation Mode Bit setting Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 a Factory setting 00000 0 direction determined by Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 04-35 Disable Skip Frequency Width a Factory setting 0.00 a Factory setting 0.00 Settings 0.00~400.00Hz 04-36 Interfere Jump Width Settings 0.00~400.00Hz Frequency 04-35 Center Frequency 04-36 04-36 04-35 Time 5-40 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.6 Group 5: Motor Parameters 05-00 Motor Auto Tuning Settings Factory setting 0 0 no function 1 measures (R1, R2, Lm, Lc, no-load current) 2 measures (R1, R2, Lc) 3 measures (R1, R2, Lc, Lm, calculated by the motor’s no-load current) This parameter automatically measures the motor’s characteristics and enters the values into Pr.05-02, Pr.05-06~09, Pr.05-12, Pr.05-16~19, respectively. Note 1.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 6. Set Pr.00-10 = 2~5 after any errors are eliminated. based on the requirement of the application. If needed, now adjust other parameters 05-01 Full-Load Current of Motor 1 Settings Factory setting A(100%) XXXA(30~120%) This parameter will limit the AC drive output current in order to prevent the motor from overheating. The value entered must be in Amps, and should be found on the motor nameplate.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 05-05 Number of Poles for Motor 1 Settings Factory setting 4 2~20 This parameter sets the number of poles of your motor (must be an even number).
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 05-19 LC of Motor 2 Settings Factory setting XX MH 05-20 Iron Loss of Motor 2 Settings a Factory setting 1.5 0.0~10.0% For parameters 05-11~20, please refer to parameters 05-01~05-10. 05-21 ASR (Auto Speed Regulation) P (Gain) 1 Settings a Factory setting 25.0 0.0~500.0% This parameter determines the error value gain while in vector, or vector w/PG control mode.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 05-26 Low-Speed Excitation Magnet Compensation Settings a Factory setting 10 0~100% This parameter determines the amount of current applied to the motor to excite the magnetic field during vector control. 05-27 The Pre-Controlled Torque Feedback Settings a Factory setting 0~100% Used with the vector control to help with low speed torque control. gain and should be increased as more torque is needed.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.7 Group 6: Protection Parameter 06-00 Low Voltage Level Settings 160~220V a Factory setting 180 360~440V a Factory setting 360 This parameter determines the level for “LV” fault. Input voltage 06-00 15V LV 06-01 Over-Voltage Stall Prevention Settings 350.0~450.0V a Factory setting 380.0 700.0~900.0V a Factory setting 760.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 06-02 Phase-Loss Protection 0 warn and keep operating Settings a Factory setting 0 1 warn and ramp to stop 2 warn and coast to stop The phase-loss protection is for the input side of the power phase-loss protection. The drive will have influence on control characteristics and driver life when it operates the input phase-loss. But it can be operated if its’ output current is less than 50% of rated current.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 06-04 Over-Current Stall Prevention during Operation a Factory setting 170 Settings 10~250% This parameter sets the current limit for the Over-Current Stall Prevention during Operation function. If the load on the motor causes the current to rise above the value set in this parameter, the drive will lower its output frequency (therefore lowering current) to avoid the motor from stalling.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 06-08 Over-Torque Detection Time (oL2) a Factory setting 0.1 Settings 0.0-60.0 Second These parameters define the current level and detection time for the Over Torque Detection function. The Over Torque Detection level is a percentage of the rated drive current. The factory setting is 150% of the drives rated current.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 06-12 Over-Torque limit a Factory setting 150 Settings 0~250% This parameter sets the over torque limit used during torque control, V/F control, and Vector control. When using an analog input set for “Torque Limit”, this parameter will set the actual limit. The value in this parameter is based on the AC drive output current in %.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 28 pid error 29 ACI error 30 P2P Over Limit 31 CC 33 VEC R1 out of range (Pr. 05-30) 34 keypad error 35 RS 485 watchdog timer 36 FAN failure 37 input phase loss 5-52 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.8 Group 7: Special Parameter 07-00 Software Braking Level Settings 350.0~450.0VDC a Factory setting 380.0 700.0~900.0VDC a Factory setting 760.0 This parameter sets the level for dynamic braking to enable. The value must be higher than the steady state DC-BUS voltage, otherwise the braking transistor will have a 100% duty. At 100% duty the transistor and resistor will most likely fail.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Output Frequency Startup Frequency 01-09 OFF ON RUN/STOP Time This parameter determines the frequency point of DC braking for both Pr. 07-02 and Pr. 07-03. During deceleration, the drive will begin to output a DC current once the frequency reaches the value set in this parameter.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 07-06 Re-activate after Momentary Power Loss 0 disable Settings a Factory setting 0 1 begins from command frequency 2 begins from minimum output frequency This parameter selects the speed search type after a momentary power loss. 07-07 Maximum Allowable Power Loss Time Settings a Factory setting 2.0 0.1~5.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Maximum Allowable Power Loss Time Maximum Allowable Power Loss Time Input Power 07-07 Speed Search 07-06=01 Output Frequency Speed Synchronization Detection 07-07 07-06=02 Baseblock Time Baseblock Time 07-08 07-08 Output Voltage The Procedure Diagram of "Re-activate after Momentary Power Loss" 07-10 Deceleration Time for Speed Search Settings a Factory setting 3.00 0.50~600.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 07-15 Gear Gap Acceleration-Interruption Time Settings a Factory setting 6.00 a Factory setting 0.00 a Factory setting 6.00 0.00~400.00Hz 07-17 Gear Gap Deceleration-Interruption Time Settings 0.00 0.00~400.00 Sec 07-16 Gear Gap Acceleration-Interruption Frequency Settings a Factory setting 0.00~400.00 Sec 07-18 Gear Gap Deceleration-Interruption Frequency Settings 0.00~400.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.9 Group 8: High-Performance Parameter 08-00 PID Feedback Terminal Selection Settings 0 Disable 1 AVI (0~10V) 2 ACI (4~20mA) 3 AUI (+/-10V) 4 Clock (F/R--master speed) 5 Clock (F/R--A/B direction) a Factory setting Select an input terminal to serve as the PID feedback position. feedback position is different from the Frequency Set Point position.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 08-05 PID Frequency Output Command limit Settings a Factory setting 100.0 0.0~100.0% This parameter determines the limit of the PID Command frequency. If this parameter is set to 120%, then the maximum output frequency while in the PID operation will be (120% x Pr.01-00) 72%. 08-06 PID Deviation Range Settings a Factory setting 0.000 0.000~0.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series PD Control: when deviation occurred, the system will immediately generate some operation load that is greater than the load generated single handedly by the D action to restrain the increment of the deviation. If the deviation is small, the effectiveness of the P action will be decreasing as well.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series These parameters determine Dwell (sleep) functions of the AC drive. If the command frequency falls below the Dwell frequency, for the specified time in Pr. 08-12, then the drive will shut off the output and wait until the command frequency rises above Pr. 08-11. Please see the below diagram.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.10 Group 9: Communication Parameter 09-00 Communication Address Settings a Factory setting 1 1-254 When the system is controlling or monitoring with the RS-485 series connection communication interface, every drive has to be determined with one communication address then and that the address connected to the network should be specific and could not be repeated.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Data Format 7.N.2 Start bit 0 1 3 2 4 5 6 Stop Stop bit bit 5 6 Even Stop parity bit 5 6 Odd Stop parity bit 7-data bits 10-bit word frame Data Format 7.E.1 Start bit 0 1 2 4 3 7-data bits 10-bit word frame Data Format 7.O.1 Start bit 0 1 2 4 3 7-data bits 10-bit word frame 1.2 5 11-bit Word Frame (For RTU) Data Format 8.N.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series The ASCII Mode: Start Word = ‘:’ (3AH) STX Communication Address: The 8-bit address is composed of 2 ASCll codes Address Hi Address Lo Function Hi Function Code: The 8-bit function code is composed of 2 ASCll codes Function Lo Data Contents: n×8-bit, the data contents is composed of 2n DATA (n-1) …….
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 3.3 Function Code and Data Contents 03H: read the contents of the register 06H: write one WORD into the register 3.3.1 Function Code 03H: read the contents of the register. e.g.: When the address of the drive is set as 01H, read 2 data contents that exist successively within the register, as shown follows: the address of the start register is 2102H.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series The RTU Mode: Inquiry message: Response message: Address 01H Address 01H Function 03H Function 03H Starting data address 21H Number of data (count by byte) 04H Number of data (count by word) 00H Content of data address 8102H 17H CRC CHK Low 6FH CRC CHK High F7H 02H 02H 70H Content of data address 8103H 00H CRC CHK Low FEH CRC CHK High 5CH 00H 3.3.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series The RTU Mode: Inquiry message: Response message: Address 01H Address 01H Function 06H Function 06H Data address 01H Data address 01H 00H Data content 00H 17H Data content 70H 17H 70H CRC CHK Low 86H CRC CHK Low 86H CRC CHK High 22H CRC CHK High 22H 3.4 The LRC Check of the ASCII Mode The LRC Check is the added sum from “Address” to “Data Contents”. For example, in 3.3.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series unsigned int crc_chk(unsigned char* data, unsigned char length) { int j; unsigned int reg_crc= 0Xffff; while(length--){ reg_crc ^= *data++; for(j= 0;j<8;j++){ if(reg_crc & 0x01){ /* LSB(b0)= 1 */ reg_crc= (reg_crc>>1) ^ 0Xa001; }else{ reg_crc= reg_crc >>1; } } } return reg_crc; // the value that sent back to the CRC register finally } 4.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Definition Parameter Address Command toward 2000H the drive Bit8~9 00B: no function 01B: operation commands controlled by the digital keypad 10B: operation commands controlled by the RS485 communication or the external terminal command (Pr. 02-01) 11B: source change for the operation command Bit6~7 Reserved Bit12~15 Reserved 5 2001H frequency/torque command 2002H Bit0 1: E.F.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Definition Parameter Address Function 2104H output current (XX.XX) 2105H DC-BUS voltage (XXX.X) 2106H output voltage (XXX.XX) 2107H presently-executed step speed 2109H residual time after procedural operating the step speed 2116H multi-function display (Pr. 00-04) 2120H 2122H 217EH (00-04=0) (00-04=1) (00-04=47) 5.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Meaning of the Error Codes: Error Codes Explanations 1 Data Contents Error: If the value of the data contents is great, it is then not recognizable by the drive. 2 Parameter Address Error: Parameter addresses not recognizable by the drive.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 5.11 Group 10: Speed Feedback Parameter 10-00 PG (encoder) Pulses Settings Factory setting 600 Factory setting 0 1~20000 This parameter sets the encoder pulse per revolution. 10-01 Encoder Input Setting (channel 1) Phase A leads in a forward run command and phase B leads in a reverse run command.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Phase B is a forward run pulse, then phase A is High. Phase A is a reverse run pulse, then phase B is High. FWD 5 REV A B Phase A leads in a forward run command and phase B leads in a reverse run command. (level trigger) FWD 6 REV A B Phase B leads in a forward run command and phase A leads in a reverse run command.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series This parameter determines the PG feedback filter time for the AC drive to process the motor’s rotation speed. 10-05 PG Slip Range a Factory setting 10.0 Settings 0.0~50.0% This parameter determines the maximum slip range (deviation) for the PG feedback signal. The slip range is calculated as follows (Pr. 10-05 x Pr. 01-00 = slip frequency).
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Phase A is a forward run pulse, then phase B is High. Phase B is a reverse run pulse, then phase A is High. FWD 2 REV A B Phase B is a forward run pulse, then phase A is High. Phase A is a reverse run pulse, then phase B is High. FWD 3 REV A B Phase A is a pulse input, phase B is a direction input, (low = reverse , high = forward) FWD 4 REV A B Phase A is a pulse input, phase B is direction input.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 10-18 Loop Speed Settings a Factory setting 1.00 a Factory setting 10 a Factory setting 1 0.00~400.00 Hz 10-19 Loop Point Settings 0~20000 10-20 Division (scaling) factor for PG04/05 Settings 1~128 Parameter 10-20 is used when the drive must follow a second encoder for speed reference. The main encoder (A) is a factor of the second encoder (B) as follows. If Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series There are speed LOOP and position LOOP in position mode. This parameter is used to adjust gain of speed LOOP (FX 10-22). 10-23 PG Position Attained 2 a Factory setting 100 Settings 0~20000 It is used to set the range of position attained in P2P mode. 10-24 P2P Acceleration Time Settings a Factory setting 1.00 0.00~100.00 s 10-25 P2P Deceleration Time Settings a Factory setting 1.00 0.00~100.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 10-32 REV Limit of Absolute P2P Settings 0: No Limit a Factory setting 0 1~60000 10-31 and 10-32 are protective parameters. When the settings of 02-01~02-06 / 02-23~02-30 are set to d42 P2P FWD Limit/d 43 REV Limit and it is ON, AC drive will free stop when it is over the limit.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series The distance that each pulse moves (mm) should use with 10-33~10-40 (8-point P2P command) for application. 5-82 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series CHAPTER 6 MAINTENANCE AND INSPECTIONS Modern AC drives are based on solid state electronics technology, preventive maintenance is required to operate this AC drive in its optimal condition, and to ensure a long life. It is recommended to perform a monthly check up of the AC drive by a qualified technician. Before the check up, always turn off the AC Input Power to the unit.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series CHAPTER 7 ERROR MESSAGE AND TROUBLESHOOTING The AC drive has a comprehensive fault diagnostic system that includes various alarms and fault messages such as over-voltage, low-voltage and over-current. Once a fault is detected, the corresponding protective functions will be activated, and the AC drive will stop the output and the motor will then coast to stop.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Code Displayed Error Explanations Treatments OL: AC drive overload Output current exceeds the AC drive-bearable current; e.g. could sustain for 60 seconds if the output is 150% of the AC drive rated current. OL1: motor overload Internal electronic thermal relay protections Decrease the loading Check whether the motor is overloaded Check whether the rated current value of the motor (Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series CHAPTER 8 PARAMETER SUMMARY Group 0: System Parameter Parameters Functions Settings 00-00 Identity Code Based on the model type 00-01 Rated Current Display Based on the model type 00-02 a 00-03 a 00-04 10: Parameter reset (for 60Hz input) 9: Parameter reset (for 50Hz input) bit 0=1: Parameters are read only Parameter Reset bit 1=1: Disable Frequency and Torque Command changes.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Group 1: Basic Parameter Parameters 01-00 01-01 01-02 01-03 a 01-04 Functions Settings Maximum Operation 50.0~400.00Hz Frequency Maximum Voltage Frequency 0.00~400.00Hz (Base Frequency) 230V: 0.0~255.0V Maximum Output Voltage 460V: 0.0~510.0V Upper Midpoint Output 0.00~400.00Hz Frequency 230V: 0.0~255.0V Upper Midpoint Output Voltage 460V: 0.0~510.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Parameters a 02-19 a 02-20 a 02-21 a 02-22 Functions Pre-set Arrival Frequency 1 Pre-set Arrival Frequency 1 Width Pre-set Arrival Frequency 2 Pre-set Arrival Frequency 2 Width 0.00~400.00HZ 60.00/ { { { { { { 50.00 0.00~400.00HZ 2.00 { { { { { { 0.00~400.00HZ 60.00/ { { { { { { 50.00 0.00~400.00HZ 2.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Parameters a 03-08 a 03-09 a 03-10 a 03-11 a 03-12 a 03-13 a 03-14 a 03-15 Functions Settings 0: zero bias 1: value lower than bias = bias (AUI) 2: value greater than bias = bias Positive/Negative 3: the absolute value of the bias Bias Mode voltage while serving as the center Analog Input 1 -500.0~+500.0% Gain (AVI) Analog Input 2 -500.0~+500.0% Gain (ACI) Analog Input 3 -500.0~+500.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Group 4: Multi-Step Speed and Process Control Operation (PCO) Parameter Parameters a a 04-00 04-01 Functions Control Mode Factory Setting VF VG SV SG T TG Settings The 1st Step Speed 0.00~400.00Hz 0.00 { { { { ° ° nd 0.00~400.00Hz 0.00 { { { { ° ° rd The 2 Step Speed a 04-02 The 3 Step Speed 0.00~400.00Hz 0.00 { { { { ° ° a 04-03 The 4th Step Speed 0.00~400.00Hz 0.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Parameters a 04-27 a 04-28 a 04-29 a 04-30 a 04-31 a 04-32 a 04-33 Functions Settings Control Mode Factory Setting VF VG SV SG T TG Time Duration of PCO 0.0~65500 Sec 0.0 Step 12 Time Duration of PCO 0.0~65500 Sec 0.0 Step 13 Time Duration of PCO 0.0~65500 Sec 0.0 Step 14 Time Duration of PCO 0.0~65500 Sec 0.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Parameters Functions Control Mode Factory Setting VF VG SV SG T TG Settings Bit0=0: direction determined by 04-32 Bit0=1: direction determined by the master speed Bit1=0: continuously execute multi-step speed Bit1=1: execute multi-step 00001 { { { { ° ° speed based on time (Pr.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Parameters Functions Control Mode Factory Setting VF VG SV SG T TG Settings 05-18 LM of Motor 2 MH Xx ° ° { { { { 05-19 LC of Motor 2 MH Xx ° ° { { { { a 05-20 0.0~10.0% 1.5 ° ° { { { { a 05-21 0.0~500.0% 25.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Group 6: Protection Parameter Parameters Functions a 06-00 Low Voltage Level a 06-01 Over-Voltage Stall Prevention a 06-02 Phase-Loss Protection a 06-03 a 06-04 a 06-05 a 06-06 a 06-07 a 06-08 Settings 160-220V 320-440V 350.0-450.0V 700.0-900.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Parameters Functions Settings 06-09 0: Disable 1: over-torque detection during constant speed operation, continue to operate after detection 2: over-torque detection during Over-Torque constant speed operation, Detection stop operation after detection. Selection 2 (OL3) 3: over-torque detection during operation, continue operation after detection.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Parameters a 07-12 a 07-13 a 07-14 a 07-15 a 07-16 a 07-17 a 07-18 a 07-19 Functions Settings 3: REV-speed search only (motor only runs in REV direction) 4: FWD/REV speed search enabled in both directions (fwd first) 5: REV/FWD speed search enabled in both directions (rev first) Speed Search Type Speed Search Frequency 0.00~400.00Hz (FWD direction) Speed Search Frequency 0.00~400.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Group 8: High-Performance Parameter Parameters a 08-00 a 08-01 a 08-02 a 08-03 a 08-04 a 08-05 a 08-06 a 08-07 a 08-08 a 08-09 a 08-10 a 08-11 a 08-12 a 08-13 Functions Settings 0: Disable 1: AVI (0~10V) PID Feedback 2: ACI (4~20mA) Terminal 3: AUI ( +/-10V) Selection 4: Clock (F/R--master speed) 5: Clock (F/R--A/B direction) Proportional Gain 0.0~500.0% (P) 0.00~100.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Group 9: Communication Parameter Parameters a 09-00 a 09-01 Functions Communication Address Transmission Speed of the Communication Settings 1~254 4.8~115.2 Kbits/Sec Control Mode Factory Setting VF VG SV SG T TG 1 { { { { { { 9.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Group 10: Speed Feedback Parameter Parameters 10-00 10-01 a 10-02 a 10-03 a 10-04 Functions PG (encoder) Pulses Control Mode Factory Setting VF VG SV SG T TG Settings 1~20000 600 ° { ° { ° { 0: Phase A leads in a forward run command and phase B leads in a reverse run command.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Parameters Functions a 10-05 a 10-06 a 10-07 a 10-08 a 10-09 a 10-10 a 10-11 PG Slip Range PG Stall Level (overspeed protection) PG Electrical Gear A PG Electrical Gear B PG Position Control Point (Home) Range for PG Position Attained (Home range) PG Encoder input Filter Time a 10-12 PG04 encoder input selection (channel 2) Settings Control Mode Factory Setting VF VG SV SG T TG 0.0~50.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Parameters Functions a 10-15 a 10-16 Differential (D) Time Orient Speed a 10-17 a Control Mode Factory Setting VF VG SV SG T TG Settings 0.00~1.00 Sec 0.25 ° { ° { ° { 0.00~400.00 Hz 5.00 ° { ° { ° { Creep point 0~20000 100 10-18 Loop Speed 0.00~400.00 Hz 1.00 ° { ° { ° { a 10-19 0~20000 10 ° { ° { ° { a 10-20 1~128 1 ° { ° { ° { a 10-21 0.0~100.0% 0 ° { ° { ° { a 10-22 0.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Specifications 230V Class Environment Protection Characteristics Control Characteristics Input Rating Output Rating Model Number VFD-xxxV23A 007 015 022 037 055 230V Class 075 110 150 185 220 300 370 Max. Applicable Motor 0.7 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 output (kW) Max. Applicable Motor 1 2 3 5 7.5 10 15 20 25 30 40 50 output (HP) Constant Torque Output 5.0 7.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series 460V Class Environment Protection Characteristics Control Characteristics Input Rating Output Rating Model Number VFD-xxxV43x Max. Applicable Motor output (kW) Max.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series ACCESSORIES B.1 Non-fuse Circuit Breaker Chart Per UL 508C, paragraph 45.8.4, part a, For 3-phase drives, the current rating of the breaker shall be four times maximum of output current rating. (Note: According to our experience, we suggest to use 1.5 – 2 times maximum of output current rating.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series B.2 All Braking Resistors & Braking Units Use in AC Drives 460V Series 230V Series Voltage Note: Please only use DELTA resistors and recommended values. Other resistors and values will void Delta’s warranty. Please contact your nearest Delta representative for use of special resistors.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Braking Resistors & Braking Units B-4 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Braking Resistors & Braking Units B DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CALL NOW 800-985-6929 B-5 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series Braking Resistors & Braking Units Braking resistors model no.: BR1K0W050, BR1K2W008, BR1K2W6P8, BR1K5W005, BR1K5W040 B-6 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series B.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series EMI Filters (26TDT1W4C) Use on 1-5 HP, 230V, Three phase Models EMI Filters (15TDT1W44) Use on 1-5 HP, 460V, Three phase Models B-8 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series EMI Filters (50TDS4W4V4) Use on 7.5-10HP/230V, VFD110V43A, Three phase Models EMI Filters (26TDT1W4B4) Use on VFD110V43B B DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CALL NOW 800-985-6929 B-9 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series EMI Filters (50TDS4W4C) EMI Filters (100TDS84C) Use on 20-25 HP, 430V, Three phase Models Use on 15-20 HP, 230V & 30-50 HP, 430V, Three phase Models B-10 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series EMI Filters (150TDS84C) Use on 25-40 HP, 230V & 60HP, 430V, Three phase Models EMI Filters (180TDS84C) Use on 50 HP, 230V & 60 HP, 430V, Three phase Models B DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CALL NOW 800-985-6929 B-11 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series EMI Filters (200TDDS84C) Use on 100 HP, 430V, Three phase Models B-12 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series B.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series B.4.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series B.4.3 Exterior of PG-03 Fj1 B/O A/O 0V 12V 0V Connect to the VFD-V Series Control Board PG-03 G B A FSW2 OC Select the input power and the output type of the Encoder TP B B A A B.4.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series B.4.5 VFD-V & VFD-B Series Speed Regulation Comparison Series Char. Speed Control Range Speed Regulation Initial Speed VFD-V Sensorless-Vector Flux Vector Mode Mode (with PG) (without PG) VFD-B Without PG With PG 1:40 1:100 1:1000 1:40 ± 0.2% 150% at 1Hz ± 0.02% 150% at 0 RPM ± 3% ± 0.05% 150% at 3Hz Note: The speed regulation is based on rated speed.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series B.5 Zero Phase Reactor (RF220X00A) 460 V Series 230 V Series Dimension Motor HP kW 1/4 0.2 1/2 0.5 1 0.75 2 1.5 3 2.2 5 3.7 7.5 5.5 10 7.5 15 11 20 15 25 18.5 30 22 40 30 50 37 1/4 0.2 1/2 0.5 1 0.75 2 1.5 3 2.2 5 3.7 7.5 5.5 10 7.5 15 11 20 15 25 18.5 30 22 40 30 50 37 60 45 75 55 100 75 Qty. 1 Recommended Wiring Wire Size (mm2) Method 0.5 - 5.5 3.5 - 5.5 5.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series DIMENSIONS VFD007V23A/43A Unit: mm (inches) 244.3 [9.63] X) (] 2 87 0. 28 .0[ DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CALL NOW 800-985-6929 .2 R3 11.3 [0.44] [ .0 2 2 160.2 [6.31] 260.0 [10.24] ] .26 0 [ 6.5 150.0 [5.91] 135.0 [5.32] ] .13 0 5[R C 6.5 [0.26] 1.1 0]( 2X ) C-1 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series VFD015V23A/43A VFD022V23A/43A Unit: mm (inches) ] .26 0 [ 6.5 X) (] 2 28 .0[ [ . 25 3 R 1.1 0 ](2 X) C-2 CALL NOW 800-985-6929 ] .13 0 R 6.5 [0.26] 11.3 [0.44] [ .0 2 2 87 0. 160.2 [6.31] 260.0 [10.24] 244.3 [9.63] 150.0 [5.91] 135.0 [5.32] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series VFD037V23A/43A Unit: mm (inches) ] .26 0 [ 6.5 1. 1 [ 0 . 28 183.7 [7.24] 272.1 [10.72] 244.3 [9.63] 150.0 [5.91] 135.0 [5.32] ) 2X ( ] 0 0.1 [R 5 .2 R3 3] 34. 0[ 1.3 4](2 X) DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CALL NOW 800-985-6929 11.3 [0.44] C 6.5 [0.26] C-3 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series VFD055V23A/43A VFD075V23A/43A VFD110V43B Unit: mm (inches) 8] 183.2 [7.22] R3 .5 [R 0. 14 ] 13.5 [0.53] [ 2 0. 323.0 [12.72] 0 7. 303.0 [11.93] 200.0 [7.88] 185.6 [7.31] 7.0 [0.28] C-4 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series VFD110V23A/43A VFD150V23A/43A VFD185V23A/43A VFD220V23A/43A Unit: mm (inches) 250.0 [9.84] 384.0 [15.12] 0] 1.1 .0[ 28 ] .20 0 R 0[ R 5. ) ](2X 5 6 . 13.0 [0.51] 4 [ 1 2.0 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CALL NOW 800-985-6929 205.4 [8.08] 403.8 [15.90] 10.0 [ 0.39] 226.0 [8.90] C 10.0 [0.39] C-5 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series VFD300V23A VFD370V23A Unit: mm (inches) 370.0 [14.57] 260.0 [10.24] 589.0 [23.19] 560.0 [22.05] 595.0 [23.43] 335.0 [13.19] 18.0 [0.71] 21.0[0.83] 132.5 [5.22] R6.5[0.25] 13.0[0.51] C-6 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series VFD300V43A VFD370V43A VFD450V43A Unit: mm (inches) 370.0 [14.57] 260.0 [10.24] 589.0 [23.19] 560.0 [22.05] 335.0 [13.19] 18.0 [0.71] 132.5 [5.22] 21.0[0.83] C R6.5[0.25] 13.0[0.51] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CALL NOW 800-985-6929 C-7 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series VFD550V43A VFD750V43A Unit: mm (inches) 425.0 [16.73] 264.0 [10.39] 660.0 [25.98] 631.0 [24.84] 385.0 [15.16] 18.0 [0.71] 130.4 [5.13] 21.0[0.83] 280.0 [11.02] R6.5[0.25] 13.0[0.51] C-8 CALL NOW 800-985-6929 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series The Apparatus Size of the Digital Hand-Held Programming Panel VFD-PU05 Unit: mm (inches) 73.0 [2.87] F H U 19.0 [0.75] 9.1 [0.36] 14.1 [0.55] VFD-PU05 17.6 [0.69] 16.0 [0.63] 6.5 [0.26] M4*O0.7(3X) VFD-PU05 RUN 119.0[4.69] 119.2[4.69] PU PROG DATA STOP RESET 14.5 [0.57] 44.0 [1.73] 6.5[0.26] FWD REV MODE 112.9 [4.44] JOG PU 132.0 [5.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series DELTA ELECTRONICS, INC.
CALL NOW 800-985-6929 http://www.automatedpt.com Email: charles@automatedpt.com VFD-V Series DELTA ELECTRONICS,INC.