& The accel/decel time 2 determines the time for the AC drive to accel/decel
from 0Hz to Maximum Output Frequency (Pr.1-00) (accel/decel time 1 is the
default). A Multi-Function Input terminals must be programmed to select
accel/decel time 2 and the terminals must be closed to select accel/decel
time 2. See Pr.4-04 to Pr.4-08.
& In the diagram shown below, the accel/decel time of the AC drive is the time
between 0 Hz to Maximum Output Frequency (Pr.1-00). Suppose the
Maximum Output Frequency is 60 Hz, start-up frequency (1-05) is 1.0 Hz,
and accel/decel time is 10 seconds. The actual time for the AC drive to
accelerate from start-up to 60 Hz is 9.83 seconds and the deceleration time
is also 9.83 seconds.
1 - 13 Jog Accel/Decel Time Factory Setting: d 10.0
Settings d 0.1 to d 600Sec Unit: 0.1Sec
This parameter can be set during operation.