User manual
Chapter 5 Description of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
31
1 - 14 Jog Frequency Factory Setting : d 6.0
Settings d 1.0 to d 400Hz Unit: 0.1Hz
This parameter can be set during operation.
& The JOG function can be selected using Multi-function Input terminals (Pr.4-
04 to Pr.4-08) if programmed for Jog (d10). When the Jog terminal is
“closed”, the AC drive will accelerate from Minimum Output
FrequencyPr.1-05 to Jog Frequency Pr.1-14. When the Jog
terminal “open”, the AC drive will decelerate from Jog Frequency to zero.
The accel/decel time is decided by the Jog accel/decel time Pr.1-13.
During operation, the AC drive can not perform Jog command. And during
Jog operation, other operation commands can not be accepted, except
command of FORWARD, REVERSE and STOP keys on the digital keypad.