Chapter 5 Description of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
32
1 - 15 Auto-Acceleration / Deceleration Factory Setting : d 0
Settings d 0 Linear acceleration / deceleration.
d 1 Auto acceleration, linear Deceleration.
d 2 Linear acceleration, auto Deceleration.
d 3 Auto acceleration / deceleration
d 4 Linear acceleration/deceleration, and stall prevention
during deceleration.
d 5 Auto acceleration, linear deceleration, and stall
prevention during deceleration
& If the auto accel/decel is selected, the AC drive will accel/ decel in the
fastest and smoothest means possible by automatically adjusting the time
of accel/decel.
1 - 16 Acceleration S-Curve Factory Setting: d 0
Settings d 0 to d 7
1 - 17 Deceleration S-Curve Factory Setting: d 0
Settings d 0 to d 7
& These two parameters allow you to configure whether the acceleration
and/or deceleration ramps are linear or S-shaped. The S-curve is enabled
when set at d1-d7. Setting d1 offers the quickest S-curve and d7 offers the
longest and smoothest S-curve. The AC drive will not follow the accel/decel
time in Pr.1-09 to Pr.1-12. To Disable the S-curve, set Pr.1-16 and Pr.1-17
to d0.
& From the diagram shown below, the original setting accel/decel time will be
for reference when the function of the S-curve is enabled. The actual
accel/decel time will be determined based on the S-curve selected (d1 to
d7).