User manual

Chapter 5 Description of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
35
2 - 01 Source of Operation Command Factory Setting: d 0
Settings d 0 Controlled by the keypad
d 1 Controlled by the external terminals, keypad STOP
enabled.
d 2 Controlled by the external terminals, keypad STOP
disabled.
d 3 Controlled by the RS-485 communication interface,
keypad STOP enabled.
d 4 Controlled by the RS-485 communication interface,
keypad STOP disabled.
& When the AC drive is controlled by an external source, please refer to
parameter group 4 for detailed explanations on related parameter settings.
2 - 02 Stop Method Factory Setting: d 0
Settings d 0 Ramp stop
d 1 Coast stop
& The parameter determines how the motor is stopped when the AC drive
receives a valid stop command.
1. Ramp: the AC drive decelerates the motor to Minimum Output Frequency
(Pr.1-05) and then stops according to the deceleration time set in Pr.1-10 or
Pr.1-12.
2. Coast: the AC drive stops output instantly upon command, and the motor
free runs until it comes to a complete stop.