User manual

Chapter 5 Description of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
39
The analog output voltage is directly proportional to the output current of the AC
drive. With the factory setting of 100%, the 2.5 times rated current of the AC drive
corresponds to +10VDC analog voltage output. (The actual voltage is about
+10VDC, and can be adjusted by Pr. 3-01)
Note: Any type of voltmeter can be used. If the meter reads full scale at a voltage
less than 10 volts, then Pr.3-01 should be set by the following formula:
Pr.3-01 = ((meter full scale voltage)/10) ×100%
For Example: When using the meter with full scale of 5 volts, adjust Pr.3-01 to
50%
3 - 02 Desired Frequency Attained Factory Setting: d 1.0
Settings d 1.0 to d 400 Hz Unit: 0.1Hz
& If a Multi-function output terminal is set to function as Desired Frequency
Attained (Pr.3-05 or 3-06=d9), then the output will be activated when the
programmed frequency is attained.