User manual
Chapter 5 Description of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
42
& Function Explanations
d 0 Not Used.
d 1 AC drive operational: the output of output terminal will be activated when
there is an output from the drive.
d 2 Maximum Output Frequency Attained: the output will be activated when
the AC drive attains Maximum Output Frequency.
d 3 Zero speed: the output will be activated when Command Frequency is lower
than the Minimum Output Frequency.
d 4 Over-Torque Detection: the output will be activated as long as the over-
torque is detected. Pr.6-04 determines the Over-Torque detection level.
d 5 Base-Block (B.B.) Indication: the output will be activated when the output of
the AC drive is shut off by external Baseblock.
d 6 Low Voltage Indication: the output will be activated when low voltage is
detected.
d 7 AC Drive Operation Mode: the output will be activated when the operation of
the AC drive is controlled by External Control Terminals.
d 8 Fault Indication: the output will be activated when faults occur (oc, ov, oH,
oL, oL1, EF, cF3, HPF, ocA, ocd, ocn, GF).
d 9 Desired Frequency Attained: the output will be activated when the desired
frequency (Pr.3-02)is attained.
d10 PLC Program Running: the output will be activated when the PLC program
is running.
d11 PLC Program Step Completed: the output will be activated for 0.5 sec.
when each multi-step speed is attained.
d12 PLC Program completed: the output will be activated for 0.5 sec. when the
PLC program cycle has completed.
d13 PLC Program Operation Paused: the output will be activated when PLC
operation is paused.
d14 Terminal Count Value Attained: counter reaches Terminal Count Value.
d15 Preliminary Count Value Attained: counter reaches Preliminary Count
Value.
d16 All Functions Normal: a When the AC Drive is in a normal state, the contact
will be closed. If there is a fault or the AC drive is not functioning normally,
the contact will be open.