CH 5-5 Group 4: Input Function Parameters
4 - 00 Potentiometer Bias Frequency Factory Setting:
d0.0
Settings d 0.0 to d 350Hz Unit: 0.1Hz
This parameter can be set during the operation.
4 - 01 Potentiometer Bias Polarity Factory Setting: d 0
Settings d 0 Positive bias
d 1 Negative bias
This parameter can be set during the operation.
4 - 02 Potentiometer Frequency Gain Factory Setting: d 100
Settings d 1 to d 200% Unit: 1%
This parameter can be set during the operation.
4 - 03 Potentiometer Reverse Motion Enable Factory Setting: d 0
Settings d 0 Forward motion only
d 1 Reverse motion enable (must be negative bias)
& Pr.4-00 to Pr.4-03 are used when the source of frequency command is the
analog signal (0 to +10V DC or 4 to 20 mA DC). Refer to the following
examples.