User manual
Chapter 5 Description of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
49
Parameters & Functions table:
Value Function Value Function
d 0 Parameter Disable d11
Accel/Decel Speed Inhibit
d 1
M0: FWD / STOP
M1: REV / STOP
d12
First or Second Accel/Decel
Time Selection
d 2
M0: RUN / STOP
M1: FWD / REV
d13
External Base Block (N.O.)
(Normally Open Contact Input)
d 3
3-Wire Operation Control mode
(M0,M1,M2)
d14
External Base Block (N.C.)
(Normally Close Contact Input)
d 4 External Fault ( Normally Open) d15
Increase Master Frequency
d 5
External Fault ( Normally
Closed )
d16
Decrease Master Frequency
d 6 External Reset d17 Run PLC Program
d 7 Multi-Step Speed Command 1 d18 Pause PLC Program
d 8
Multi-Step Speed Command 2
d19 Counter Trigger Signal
d 9
Multi-Step Speed Command 3
d20 Counter Reset
d10
Jog operation
d21 ACI / AVI Selection
Explanations:
d0 Parameter Disable:
Enter value (d0) to disable any Multi-Function Input Terminal: M1 (Pr.4-04), M2
(Pr.4-05), M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08)
Note: The purpose of this function is to provide isolation for unused Multi-Function
Input Terminals. Any unused terminals should be programmed to d0 to insure
they have no effect on drive operation.