d3: Three Wire Control: Restricted to Pr.4-04 control terminals M0, M1, M2.
M1 REV/FWD Run select
Note: When value d3 is selected for Pr. 4-04, this will over ride any value
entered in Pr.4-05, since Pr.4-05 must be used for three wire control as shown
above.
d4, d5 External Faults:
Parameter values d4, d5 programs Multi-Function Input Terminals: M1 (Pr. 4-
04), M2 (Pr. 4-05), M3 (Pr. 4-06), M4 (Pr. 4-07) or M5 (Pr. 4-08) to be External
Fault (E.F.) inputs.
When an External Fault input signal is received, the AC drive will stop all output
and display E.F. on Digital Keypad, the motor will free run. Normal operation
can resume after the External Fault is cleared and the AC drive is reset.