d20 Counter Reset:
Parameter value d20 programs Multi-Function Input Terminal: M1 (Pr.4-04),
M2 (Pr. 4-05), M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) to reset the counter.
d21 ACI / AVI Selection:
Parameter value d21 allows the user to select the input type ACI or AVI via an
external switch. AVI is selected when the contact is open and ACI is selected
when the contact is closed. Please note: The use of this feature will override
Pr. 2-00 programming and the jumper on the front of the drive must be moved
to the correct location either across the AVI or ACI pin heads.
4- 09 Line Start Lockout Factory Setting: d 0
Settings: d0 Disable
d1 Enable
& When enable, the AC drive will not start when powered up with run
commands applied. To start in Line Start Lockout mode, the AC drive must
see the run command go from stop to run after power up. When Line Start
Lockout is disable (also known as Auto-Start), the drive will start when
powered-up with run commands applied.