CH 5-6 Group 5: Multi-step Speed and PLC (Process Logic Control)
Parameters
5 - 00 1st Step Speed Frequency Factory Setting: d
0.0
5 - 01 2nd Step Speed Frequency Factory Setting: d
0.0
5 - 02 3rd Step Speed Frequency Factory Setting: d
0.0
5 - 03 4th Step Speed Frequency Factory Setting: d
0.0
5 - 04 5th Step Speed Frequency Factory Setting: d
0.0
5 - 05 6th Step Speed Frequency Factory Setting: d
0.0
5 - 06 7th Step Speed Frequency Factory Setting: d
0.0
Settings d 0.0 to d 400 Hz Unit: 0.1Hz
This parameter can be set during operation.
& The Multi-Function Input Terminals (refer to Pr.4-04 to 4-08) are used to
select one of the AC drive Multi-Step speeds. The speeds (frequencies) are
determined by Pr.5-00 to 5-06 shown above.
5 – 07 PLC Mode Factory Setting: d 0
Settings d 0 Disable PLC operation
d 1 Execute one program cycle
d 2 Continuously execute program cycles
d 3 Execute one program cycle step by step
d 4 Continuously execute program cycles step by step
& This parameter selects the mode of PLC operation for the AC drive. The PLC
program can be used in lieu of any External Controls, Relays or Switches. The