CH 5-7 Group 6: Protection Parameters
6 - 00 Over-Voltage Stall Prevention Factory Setting: d 1
Settings d 0 Disable Over-Voltage Stall Prevention
d 1 Enable Over-Voltage Stall Prevention
& During deceleration, the motor DC bus voltage may exceed its Maximum
Allowable Value due to motor regeneration. When this function is enabled, the
AC drive will stop decelerating. Maintaining a constant output frequency when
it happens. The AC drive will only resume deceleration when the voltage drops
below preset value.
Note:
With a moderate inertial load, the over-voltage during deceleration won’t
happen, and the drive will stop in programmed time. The AC drive will
automatically extend the deceleration time with high inertial loads. If
deceleration time is critical for the application, then dynamic braking resistors
should be used.