Chapter 5 Description of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
69
6 - 01 Over-Current Stall Prevention during Acceleration Factory Setting: d170
Settings d 20 to d 250% Unit: 1%
& A setting of 100% is equal to the Rated Output Current of the drive.
& During acceleration, the AC drive output current may increase abruptly to
exceed the value specified by Pr.6-01 due to rapid acceleration or excessive
load on the motor. When this function is enabled, the AC drive will stop
accelerating and maintaining a constant output frequency. The AC drive will
only resume acceleration when the current drops below the maximum value.
6 - 02 Over-current Stall Prevention during Operation Factory Setting: d 170
Settings d 20 to d 250% Unit: 1%
& During the steady-state operation with motor load rapidly increasing, the AC
drive output current may exceed the limit specified in Pr.6-02. When this
occurred, the output frequency will decrease to maintain a constant motor
speed. The drive will accelerate to the steady-state output frequency only
when the output current drops below the level specified by Pr.6-02.