6 - 04 Over-Torque Detection Level Factory Setting: d 150
Settings d 30 to d 200% Unit: 1%
& A setting of proportional to the Rated Output Current of the drive.
6 - 05 Continuous Output Time Limit Factory Setting: d 0.1
Settings d 0.1 to d 10.0Sec Unit: 0.1Sec
& This parameter determines the time that AC drive will run after over-torque is
detected. Over-torque detection is based on the following:
If a Multi-Function Output Terminal is set as Over-Torque Detection
Indication and the output current exceeds the Over-Torque Detection Level
(Pr.6-04, Factory Setting: 150%), the output will be activated.
6 - 06 Electronic Thermal Overload Relay Selection Factory Setting: d 2
Settings d 0 Reduce Torque Motor
d 1 Constant Torque Motor
d 2 Inactive
& This function is used to limit the output power of the AC drive when powering
a “self-cooled motor at low speed.
6 - 07 Electronic Thermal Characteristic Factory Setting: d 60
Settings d 30 to d 600Sec Unit: 1 Sec
This parameter can be set during operation.
& The parameter determines the time required activating the I
2
t electronic
thermal protection function. The graph below shows I
2
t curves for 150%
output power for 1 minute.