CH 5-8 Group 7: Motor Parameters
7 - 00 Motor Rated Current Factory Setting: d 85
Settings d 30 to d 120 Unit: 1%
This parameter can be set during operation.
& This parameter will limit the AC drive output current in order to prevent the
motor from overheating. Use the following method to calculate the
percentage entered in this parameter.
Pr.7-00 = ( )*100AC drive Rated Output Current
7 - 01 Motor No-load Current Factory Setting: d 50
Settings d 0 to d 90% Unit: 1%
This parameter can be set during operation.
& The rated current of the AC drive is regarded as 100%. Motor setting of no-
load current will effect the slip compensation. The setting value must be less
than motor rated current setting Pr.7-00.
7 - 02 Torque Compensation Factory Setting: d 3
Settings d 0 to d 10 Unit: 1
This parameter can be set during operation.
& This parameter may be set so that the AC drive will increase its voltage output
during start-up to obtain a higher initial starting torque.