CH 5-9 Group 8: Special Parameters
8 - 00 DC Braking Voltage Level Factory Setting: d 0
Settings d 0 d30% Unit: 1%
& This parameter determines the level of DC Braking Voltage Level output to
the motor during start-up and stopping. When setting DC Braking Voltage,
the Maximum Output Voltage (Pr.1-02) is regarded as 100%. It is
recommended to start with a low DC Braking Voltage Level and then increase
until proper holding torque has been attained.
8 - 01 DC Braking Time during Start-up Factory Setting: d
0.0
Settings d 0.0 to d 60.0Sec Unit: 0.1Sec
& This parameter determines the duration of time that the DC Braking Current
will be applied to the motor during the AC drive start-up. DC Braking will be
applied for the time set in this parameter until the Minimum Frequency is
reached during acceleration.
8 - 02 DC Braking Time during Stopping Factory Setting: d
0.0
Settings d 0.0 to d 60.0Sec Unit: 0.1Sec
& This parameter determines the duration of time that the DC braking voltage
will be applied to the motor during stopping. If stopping with DC Braking is
desired, then Pr.2-02 must be set to RAMP stop (d 0).
8 - 03 Start-Point for DC Braking Factory Setting: d 0.0
Settings d 0.0 to d 400Hz Unit: 0.1Hz
& This parameter determines the frequency when DC Braking will begin during
deceleration.