NOTE: 1. DC Braking during Start-up is used for loads that may move before AC
drive starts, such as fans and pumps. These loads may also be moving
in the wrong direction. Under such circumstances, DC Braking can be
executed to hold the load in position before applying a forward motion.
2. DC Braking during stopping is used to decrease stopping time and also
to hold a stopped load in position. For high inertial loads, a dynamic
braking resistor may be needed for quick decelerations.
8 - 04 Momentary Power Loss Operation Selection Factory Setting: d 0
Settings d 0 Operation stop after momentary power loss
d 1 Operation continue after momentary power loss
Speed search start with the Master Frequency
reference value
d 2 Operation continue after momentary power loss
Speed search start with the min frequency