8 - 05 Maximum Allowable Power Loss Time Factory Setting: d 2.0
Settings d 0.3 to d 5.0Sec Unit: 0.1Sec
& During a power loss, if the power loss time is less than the time defined by
this parameter, the AC drive will resume operation. If the Maximum
Allowable Power Loss Time is exceeded, the AC drive output is then turned
off.
8 - 06 Base-Block Time for Speed Search Factory Setting: d 0.5
Settings d 0.3 to d 5.0Sec Unit: 0.1Sec
& When a momentary power loss is detected, the AC drive turns off for a
specified time interval determined by Pr.8-06 before resuming operation. This
time interval is called Base-Block. This parameter should be set to a value
where the residual output voltage is nearly zero, before the drive resumes
operation.
& This parameter also determines the searching time when performing external
Base-Block and Fault Reset (Pr.8-14).
8 - 07 Maximum Speed Search Current Level Factory Setting: d 150
Settings d 30 to d 200 Unit: 1%
& Following a power failure, the AC drive will start its speed search operation,
only if the output current is greater than the value determined by Pr.8-07.
When the output current is less than that of Pr.8-07, the AC drive output
frequency is at a “speed synchronization point”. The drive will start to
accelerate or decelerate back to the operating frequency at which it was
running prior to the power failure.