Chapter 5 Description of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
79
8 - 08 Skip Frequency 1 Upper Bound Factory Setting: d 0.0
8 - 09 Skip Frequency 1 Lower Bound Factory Setting: d 0.0
8 - 10 Skip Frequency 2 Upper Bound Factory Setting: d 0.0
8 - 11 Skip Frequency 2 Lower Bound Factory Setting: d 0.0
8 - 12 Skip Frequency 3 Upper Bound Factory Setting: d 0.0
8 - 13 Skip Frequency 3 Lower Bound Factory Setting: d 0.0
Settings d 0.0 d 400Hz Unit: 0.1Hz
& These parameters determine Skip frequency. It will cause the AC drive to
skip operation at these frequency ranges with continuous frequency output.
& Pr.8-9, Pr.8-11,Pr.8-13 are for Lower Bound setting, and the settings should
follow as Pr.8-9Pr.8-11Pr.8-13.
8 - 14 Auto Restart After Fault Factory Setting: d 0
Settings d 0 to d 10
& After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC
drive can be reset/restarted automatically up to 10 times. Setting this
parameter to 0 will disable the reset/restart operation after any fault has
occurred. When enabled, the AC drive will restart with speed search, which
starts at the Master Frequency. To set the fault recovery time after a fault,
please see (Pr.8-06) Baseblock Time for speed search.
8 - 15 Automatic Voltage Regulation (AVR) Factory Setting: d 2
Settings d 0 AVR function enabled
d 1 AVR function disabled
d 2 AVR function disabled for deceleration