& AVR function automatically regulates the AC drive output voltage to the
Maximum Output Voltage (Pr.1-02). For instance, if Pr.1-02 is set at 200 VAC
and the input voltage is at 200V to 264VAC, then the Maximum Output Voltage
will automatically be regarded to 200 VAC.
& Without AVR function, the Maximum Output Voltage may vary between 180V
to 264VAC, due to the input voltage varying between 180V to 264 VAC.
& Selecting program value d2 enables the AVR function and also disables the
AVR function during deceleration. This offers a quicker deceleration.
8 - 16 Dynamic Braking Voltage Factory Setting: d 380*
Settings d 350 to d 450V* Unit: 1Volt*
*Twice value for 460V class
& During deceleration, the DC-bus voltage will increase due to motor
regeneration. When DC bus voltage level exceeds the Dynamic Braking
Voltage, the DC brake output pins (B1, B2) will be activated.
8 - 17 DC Braking Inhibit Frequency Factory Setting: d 0
Settings d 0 to d 400 Unit: 0.1 Hz
& This parameter determines the frequency range (from Pr.8-17 to 0 Hz) where
DC injection braking will be inhibited. If the output frequency during stopping
is at or below Pr.8-03, but above Pr.8-17 then DC braking is applied. 0DC
braking will always be inhibited if Pr.8-17 is equal to or greater than Pr.8-03.