User manual

Chapter 8 Summary of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
106
Group 2 Operation Method Parameters
Parameters Explanation Settings
Factory
Setting
d0: Digital Keypad
d1: 0 to 10V from AVI
d2: 4 to 20mA from ACI
d3: Potentiometer Control
2-00
Source of Frequency
Command
d4: RS-485 communication Interface
0
d0: by Digital Keypad
d1: by external terminals, keypad STOP
enabled
d2: by external terminals, keypad STOP
disabled
d3: by RS-485 communication interface,
keypad STOP enabled
2-01
Source of Operation
Command
d4: by RS-485 communication interface,
keypad STOP disabled
0
d0: Ramp Stop
2-02 Stop Method
d1: Coast Stop
0
d3: 3KHz
d4: 4KHz
d5: 5KHz
d6: 6KHz
d7: 7KHz
d8: 8KHz
d9: 9KHz
2-03 PWM Carrier Frequency
d10:10KHz
10
Reverse Operation d0: enable REV
2-04
Inhibition d1: disable REV
0
d0: 0 Hz, continue running
d1: Stop the frequency output2-05 ACI Input Loss Detection
d2: Last ACI input command
0