Chapter 8 Summary of Parameter Settings
© 1999 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
108
Group 4 Input Function Parameters
Parameters Explanation Settings
Factory
Setting
4-00
Potentiometer Bias
Frequency H
0.0 to 350 Hz 0.0
d0: Positive Bias
4-01
Potentiometer Bias
Polarity H
d1: Negative Bias
0
4-02
Potentiometer
Frequency Gain H
1 to 200 % 100
d0: Forward Motion Only
4-03
Potentiometer Reverse
Motion Enable
d1: Reverse Motion enabled
0
4-04
Multi-Function Input
Terminal 1 (M0, M1)
d0: Parameter Disable 1
4-05
Multi-Function Input
Terminal 2 (M2)
d1: FWD/STOP, REV/STOP 6
4-06
Multi-Function Input
Terminal 3 (M3)
d2: FWD/REV, RUN/STOP 7
4-07
Multi-Function Input
Terminal 4 (M4)
d3: 3-wire Operation Control Mode 8
d4: E.F. External Fault Input (N.O)
d5: E.F. External Fault Input (N.C)
d6: Reset
d7: Multi-Step Speed Command 1
d8: Multi-Step Speed Command 2
d9: Multi-Step Speed Command 3
d10: Jog Operation
d11: Accel/Decel Speed Inhibit
d12: First or Second Accel/Decel Time
Selection
d13: Base-Block (B.B.) (N.O.)
d14: Base-Block (B.B.) (N.C.)
d15: Increase Master Frequency
d16: Decrease Master Frequency
d17: Run PLC Program
d18: Pause PLC
d19: Counter Trigger Signal
d20: Counter Reset
4-08
Multi-Function Input
Terminal 5 (M5)
d21: ACI / AVI Selection
9