Datasheet
TECHNICAL DATASHEET
CliQ DIN Rail
Power
Supply
12V 15W 1
Phase
/ DRP012V015W1A□
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 03)
3
Environment
Surrounding Air Temperature Operating -20°C to +75°C
Storage -25°C to +85°C
Power De-rating
> 50°C de-rate power by 2.5% / °C
> 70°C de-rate power by 4% / °C
Operating Humidity < 95% RH (Non-Condensing)
Operating Altitude 3,000 Meters
Shock Test (Non-Operating) IEC60068-2-27, 30G (300m/S²) for a duration of 18ms
Vibration (Non-Operating) IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak);
90 min per axis for all X, Y, Z direction
Bump IEC60068-2-29; 11ms / 10gn
Pollution Degree 2
Protections
Overvoltage 16V +10% / -5%, SELV Output, Hicc-up Mode,
Non-Latching (Auto-Recovery)
Overload / Overcurrent > 150% of rated load current, Hicc-up Mode,
Non-Latching (Auto-Recovery)
Over Temperature < 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Short Circuit Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Degree of Protection IPX0
Protection Against Shock Class I without PE* connection
*PE: Primary Earth
Reliability Data
MTBF > 1,000,000 hrs. as per Telcordia SR-332
Expected Cap Life Time 10 years (115Vac & 230Vac, 50% load @ 40°C)