User manual

10
Address Setting Content Explanation
1035H
Executing number
of reading current
pattern
0~7
1037H 1000
Upper-limit of
proportional output
0~100% max. analog output is upper limit, unit: 0.1%
1038H 0
Lower-limit of
proportional output
0~100% max. analog output is lower limit, unit: 0.1%
1040H~
1043H
7
Actual step number
setting inside the
correspond pattern
0~7 = N means the pattern is executed from step from
0 to N.
1050H~
1053H
0
Cycle number of
repeating executing
pattern 0~7
0~199 means the pattern is executed for 1~200 times.
1060H~
1063H
0
Link pattern number
setting of the
current pattern
0~8, 8 means program end. 0~7 means the next
execution number after completing current pattern.
1068H 1
Control
execution/Stop
setting
0: Stop, 1: execute, 2: program end, 3: program hold
1069H 0
Output 1: control
selection
0: heating, 1: cooling, 2: alarming, 3: proportional
output
106AH 0
Output2: control
selection
0: heating, 1: cooling, 2: alarming
106BH 0
Dismiss level 1
Read/write allowed
Shall be same as level 1 password setting (106E)
106CH 0
Dismiss level 2.
Use level 3.
Shall be same as level 2 password setting (106F)
106DH 0
Dismiss level 3.
Use level 2
Shall be same as level 3 password setting (1070)
106EH 0
Dismiss level 1/Set
password
Clear old password before new password setting
106FH 0
Dismiss level 2/Set
password
Clear old password before new password setting
1070H 0
Dismiss level 3/Set
password
Clear old password before new password setting
1071H 1
Read/Write
communication
address
1~247
1072H 0
Read/Write
communication
format
RTU:1, ASCII:0
1073H 2
Baud rate setting of
communication
0~4: 2400~38400
1074H 1
Data length setting
of communication
0: 8bit 1: 7bit
1075H 1 Parity bit setting 0: None 1:Even 2: Odd
1076H 1 Stop bit setting 0: 2 stop bit 1: 1stop bit
2000H~
203FH
0
Pattern 0~7 to set
target temperature
Pattern 0:
2000H~2007H
Temperature measure unit: 0.1 degree
2080H~
20BFH
0
Pattern 0~7 to set
execution time.
Pattern 0:
2080H~2087H
Time 0~900 (1 minute for each scale)