VFD-M Series Preface Thank you for choosing DELTA’s high-performance VFD-M Series. VFD-M Series are manufactured by adopting high-quality components, material and incorporating the latest microprocessor technology available. Getting Started This manual will be helpful in the installation, parameter setting, troubleshooting, and daily maintenance of the AC motor drives. To guarantee safe operation of the equipment, read the following safety guidelines before connecting power to the AC motor drives.
VFD-M Series TABLE OF CONTENTS CHAPTER 1 RECEIVING AND INSPECTIONS 1.1 Nameplate Information ..................................................................... 1-1 1.2 Model Explanation ............................................................................ 1-1 1.3 Serial Number Explanation ............................................................... 1-1 1.4 External Parts and Labels................................................................. 1-2 CHAPTER 2 STORAGE AND INSTALLATION 2.
VFD-M Series CHAPTER 6 MAINTENANCE AND INSPECTIONS 6.1 Periodic Inspection ........................................................................... 6-1 6.2 Periodic Maintenance ....................................................................... 6-1 CHAPTER 7 TROUBLESHOOTING AND FAULT INFORMATION .......... 7-1 CHAPTER 8 SUMMARY OF PARAMETER SETTING .............................. 8-1 APPENDIX A STANDARD SPECIFICATIONS .......................................... A-1 APPENDIX B ACCESSORIES B.
VFD-M Series CHAPTER 1 RECEIVING AND INSPECTION This VFD-M AC drive has gone through rigorous quality control tests at the factory before shipment. After receiving the AC motor drive, please check for the following: Receiving Check to make sure that the package includes an AC drive, the User Manual, and rubber bushings. Inspect the unit to insure it was not damaged during shipment. Make sure that the part number indicated on the nameplate corresponds with the part number of your order. 1.
VFD-M Series 1.4 External Parts and Labels 1-2 DELTA ELECTRONICS, INC.
VFD-M Series CHAPTER 2 STORAGE AND INSTALLATION 2.1 Storage The AC drive should be kept in the shipping carton before installation. In order to retain the warranty coverage, the AC drive should be stored properly when it is not to be used for an extended period of time. Some storage suggestions are: Store in a clean and dry location free from direct sunlight or corrosive fumes. Store within an ambient temperature range of -20 °C to +60 °C.
VFD-M Series 2.3 Installation: Improper installation of the AC drive will greatly reduce its life. Be sure to observe the following precautions when selecting a mounting location. Failure to observe these precautions may void the warranty! Do not mount the AC drive near heat-radiating elements or in direct sunlight. Do not install the AC drive in a place subjected to high temperature, high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic particles.
VFD-M Series CHAPTER 3 WIRING DANGER Hazardous Voltage Before accessing the AC drive: 3 Disconnect all power to the AC drive. Wait five minutes for DC bus capacitors discharge. Any Electrical or mechanical modification to this equipment without prior written consent of Delta Electronics, Inc. will void all warranties and may result in a safety hazard in addition to voiding the UL listing.
VFD-M Series 3.1 Basic Wiring Diagram Users must connect wiring according to the following circuit diagram shown below. Braking resistor (optional) Main Circuit Power NFB R/L1 S/L2 T/L3 Recommended Circuit when power supply is turned OFF by a fault output R/L1 B1 S/L2 T/L3 SA MC OFF ON MC The spec. of main circuit terminal is M3.
VFD-M Series 3.2 External Wiring Items Explanations Please follow the specific power Power supply requirement shown in supply APPENDIX A. There may be inrush current during Fuse/NFB power up. Please check the chart of APPENDIX B and select the correct (Optional) fuse with rated current. NFB is optional.
VFD-M Series 3.3 Control Terminal Wiring (Factory Settings) Wire Type: Copper Only Wire Gauge: 22-16 AWG Torque: 2.5kgf-cm (2.2 in-lbf) Wire Type: 75 C, Copper Only Wire Gauge: 24-12 AWG Torque: 4kgf-cm (3.
VFD-M Series 3.4 Main Circuit Wiring Wire Type: 75 oC Copper Only 002M11A 004M11A 007M11A 004M21B(1-phase) 004M21B(3-phase) 007M21B(1-phase) 007M21B(3-phase) 015M21B(1-phase) Max. Current (input / output) 6A 9A 16A 6.3A 2.9A 11.5A 7.6A 15.7A 015M21B(3-phase) 8.8A 022M21A(1-phase) 27A 022M21A(3-phase) 12.5A 037M23A 19.6A 055M23A 007M43B 015M43B 022M43B 28A 4.2A 5.7A 6.0A 037M43A 8.5A 055M43A 14A 075M43A 23A 007M53A 015M53A 022M53A 037M53A 055M53A 2.4A 4.2A 5.9A 7.0A 10.5A 075M53A 12.
VFD-M Series Terminal Explanations Terminal Symbol Explanation of Terminal Function R/L1, S/L2, T/L3 AC line input terminals (three phase) U/T1, V/T2, W/T3 Motor connections B1 – B2 Connections for Braking Resistor (optional) Earth Ground 3.5 Wiring Notes: PLEASE READ PRIOR TO INSTALLATION. 1. 2. CAUTION: Do not connect the AC power to the U/T1, V/T2, W/T3 terminals, as it will damage the AC drive. ! ! WARNING: Ensure all screws are tightened to the proper torque rating. 3.
VFD-M Series 9. Make sure that the power source is capable of supplying the correct voltage and required current to the AC drive. 10. Do not attach or remove wiring when power is applied to the AC drive. 11. Do not inspect components unless inside “CHARGE” lamp is turned off. 12. Do not monitor the signals on the circuit board while the AC drive is in operation. 13. For the single-phase rated AC drives, the AC power can be connected to any two of the three input terminals R/L1, S/L2, T/L3.
VFD-M Series CHAPTER 4 DIGITAL KEYPAD OPERATION 4.1 Description of Digital Keypad The digital keypad includes two parts: Display panel and keypad. The display panel provides the parameter display and shows the operation status of the AC drive and the keypad provides programming and control interface. 4 DIGITAL KEYPAD Program/Function mode key Selects normal mode/ program mode. Displays the AC drive status, such as output freq., selects the parameters.
VFD-M Series Function / Program MODE Pressing the “mode” key repetitively displays the AC drive status such as the reference frequency, output frequency, and output current. Enter ENTER Pressing the “ENTER” key will store or display parameter settings. Run RUN Starts AC drive operation. This key has no effect when the drive is controlled by the External Control Terminals. Stop / Reset STOP RESET Used to stop AC drive operation.
VFD-M Series 4.3 Explanations of Display Messages Displayed Message Descriptions The AC drives Master Frequency. The Actual Operation Frequency present at terminals U, V, and W. The custom unit (v), where v = H x Pr.-65. The counter value (c). The output current present at terminals U, V, and W The internal PLC process step currently being performed. The specified parameter. The actual value stored within the specified parameter. The AC drive forward run status. The AC drive reverse run status.
VFD-M Series 4.4 Explanation of Digital Keypad LC-M02E Operation To view parameters: Indication after power on Parameter values setting monitor Output frequency Output current FWD/REV monitor Press Press Press Press Key Key Key Key Press key Display the freq. setting monitor.
VFD-M Series To change frequency, proceed as follows: Note: The Pr.00 has to be set to d00 in order to operate via digital keypad. Freq. value setting monitor Freq. set at 59.9 Hz. Increasing freq. value to 60.0 Hz. Decreasing freq. value to 0.0 Hz. Press Press Press Key Key Key still Frequency setting monitor. 4 The value will be decreased with 3.5 Hz/sec, if press key still. Press key to select the monitor operating frequency. The value will be increased with 3.5 Hz/sec, if press key still.
VFD-M Series CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS a: The parameter can be set during operation. Pr.00 Source of Frequency Command Settings a 00 Master Frequency determined by digital keypad. (LC-M02E) 01 Master frequency determined by 0 to +10 V input 02 Master frequency determined by 4 to 20mA input 03 Master frequency determined by RS-485 Communication port 04 Master frequency determined by potentiometer on digital keypad. (LC-M02E) Pr.
VFD-M Series 2. Coast: The AC drive will stop the output instantly, and the motor will coast to stop. Hz Hz Freq. Freq. Motor Speed Motor Speed Operation command Stops according to deceleration time ON Time Time Free running to stop ON OFF Coast Ramp Note: OFF The motor stop method is usually determined by the application or system requirements. Pr.03 Maximum Output Frequency Factory Setting: 60.00 Settings 50.00 to 400.0 Hz Unit: 0.
VFD-M Series This parameter determines the Maximum Output Voltage of the AC drive. The Maximum Output Voltage setting must be smaller than or equal to the rated voltage of the motor as indicated on the motor nameplate. Setting of Pr.05 must be equal to or greater than setting of Mid-Point Voltage (Pr.07). Pr.06 Mid-Point Frequency Factory Setting: 1.50 Settings 0.10 to 400.0Hz Unit: 0.1Hz The parameter sets the Mid-Point Frequency of V/F curve.
VFD-M Series Voltage Pr.05 Pr.07 Pr.09 0 Frequency Pr.06 Pr.08 Pr.03 Pr.04 Voltage Pr.05 Pr.07 Pr.09 Pr.08 Pr.06 Pr.04 Frequency Pr.03 Custom V/F Curve Voltage Pr.05 Pr.07 Pr.09 Pr.08 Pr.06 Pr.04 Frequency Pr.03 Fan/Pump V/F Curve Commonly used V/F Setting 5-4 DELTA ELECTRONICS, INC.
VFD-M Series (1) General Purpose Factory Settings Motor Spec. 60Hz V 220 10 1.5 60.0 f No. Set value Pr.03 60.0 Pr.04 60.0 Pr.05 Pr.06 220.0 1.5 Pr.07 10.0 Pr.08 Pr.09 1.5 10.0 50 10 1.5 30 1.5 3 Pr.04 Pr.05 Pr.06 Pr.07 Pr.08 10 1.5 60.0 220.0 30 50.0 1.5 10.0 50.0 f Motor Spec. 50Hz V 220 50 10 1.3 25 (3) High Starting Torque Motor Spec. 60Hz Factory Settings V No. Set value 60.0 220 Pr.03 23 18 Pr.03 220 60.0f Pr.04 Pr.05 Pr.06 Pr.07 Pr.08 Pr.09 No.
VFD-M Series Pr.10. This parameter is used to determine the time required for the AC drive to ramp from 0 Hz to its Maximum Output Frequency (Pr.03). The rate is linear unless the S-Curve (Pr.14) is “Enabled”. Pr.11. This parameter is used to determine the time required for the AC drive to decelerate from the Maximum Output Frequency (Pr.03) down to 0 Hz. The rate is linear unless the S-Curve (Pr.14) is “Enabled”. Pr.12 and Pr.13: Provide an additional Accel/Decel time although Time 1 is the default.
VFD-M Series Freq. Acceleration/Deceleration characteristics (1), (2) Disabling S curve (3), (4) Enabling S curve Pr.15 Jog Accel / Decel Time a Settings 0.1 to 600.0 sec or 0.01 to 600.0 sec Factory Setting: 1.0 sec Unit: 0.1 or 0.01 sec This parameter sets the acceleration or deceleration time for Jog operation. Pr.16 Jog Frequency a Settings 0.00 to 400.0 Hz Factory Setting: 6.00 Hz Unit: 0.
VFD-M Series Frequency Jog Freq. Pr.16 Time Pr. 15 Pr. 15 Acceleration Time Deceleration Time Jog operation command OFF ON Pr.17 1st Step Speed Frequency a Factory Setting: 0.00 Hz Pr.18 2nd Step Speed Frequency a Factory Setting: 0.00 Hz Pr.19 3rd Step Speed Frequency a Factory Setting: 0.00 Hz Pr.20 4th Step Speed Frequency a Factory Setting: 0.00 Hz Pr.21 5th Step Speed Frequency a Factory Setting: 0.00 Hz Pr.22 6th Step Speed Frequency a Factory Setting: 0.00 Hz Pr.
VFD-M Series Pr.25 Over–Voltage Stall Prevention Settings 115V/230V series 330-450Vdc Factory Setting: 390 460V series 660-900Vdc Factory Setting: 780 575V series 825-1025Vdc Factory Setting: 975 00 disable During deceleration, the DC bus voltage may exceed its maximum allowable value due to motor regeneration. When this function is enabled, the AC drive will stop decelerating, and maintain a constant output frequency to prevent from over-voltage tripping.
VFD-M Series During a steady-state operation with the motor load rapidly increasing, the AC drive output current may exceed the limit specified in Pr.27. When this occurs, the output frequency will decrease to maintain a constant motor speed. The drive will accelerate to the steady-state output frequency only when the output current drops below the setting for Pr.27. output current Output current over-current detection level over-current detection level Pr.27 time time output frequency output freq.
VFD-M Series Pr.31 Start-Point for DC Braking Factory Setting: 0.00 Settings 0.00 to 60.00Hz Unit: 0.1sec This parameter sets the frequency at which the DC Braking will begin during deceleration. Master Frequency Min. output Freq. Operation command Pr.31 Pr.29 Start-point for DC braking time(s) Pr.30 OFF ON 5 DC Braking Current % Pr.28 Notes: 1. DC Braking during starting is used for loads that may move before the AC drive starts, such as hoists and cranes.
VFD-M Series Pr.34 Base-Block Time for Speed Search Factory Setting: 0.5 sec Settings 0.3 to 5.0 sec Unit: 0.1sec When a momentary power loss is detected, the AC drive will stop its output and will wait during a specified time interval called Base Block (entered in Pr.34) before resuming operation. Setting of this parameter should make the residual output voltage due to regeneration almost zero, before the drive resumes operation.
VFD-M Series Pr.37 Lower Bound of Output Frequency Factory Setting: 0 Hz Settings 0.00 Hz to 400.0 Hz Unit: 0.1Hz Setting of this parameter must be equal to or less than the Upper Bound of Output Frequency If the Lower Bound of Output Frequency is 10Hz, and the Minimum Output Frequency (Pr.08) is set at 1.0Hz, then any command frequency between 1-10Hz will generate a 10Hz output from the drive. output frequency Pr.36 5 Pr.37 Input Freq. Pr.
VFD-M Series 01: Two wire operation: Only Pr.38 can be set to “1”. RUN/STOP M0 "Open": Stop, "Close": Run M1 "Open": FWD, "Close":REV REV/FWD GND Note: Multi-function Input Terminal M0 does not have its own parameter designation. M0 must be used in conjunction with M1 to operate two and three wire control. 02 Three Wire Control: Only Pr.38 can be set to “2”.
VFD-M Series Value Function 08 Multi-Step Speed Command 3 10 Accel/Decel Speed Inhibit 14 16 18 20 22 External Base Block (N.O.) (Normally Open Contact Input) Increase Master Frequency Run PLC Program Counter Trigger Signal No Function Control source: External Terminal 24 Control source: Communication 26 30 PID Disable (N.O.
VFD-M Series RESET Mx "Close": Operation avalilable setting by 5 GND Note: the External Reset has the same function as the Reset key on the Digital keypad. It will reset the drive after a fault. 06, 07, 08 Multi-Step Speed Command: Parameter values 06, 07,and 08 program any three of the following Multi-Function Input Terminals: M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42) for Multi-step Speed Command function.
VFD-M Series Mx "Close": Operation available 9 jog operation command GND Note: Jog operation programmed by 9 can only be initiated while the motor is stop. (Refer to Pr.15, Pr.16.) 10 Accel/Decel Speed Inhibit: Parameter value 10 programs Multi-Function Input Terminal: M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42) for Accel/Decel Inhibit. After receiving this command, the AC Drive stops accelerating or decelerating and maintains a constant speed.
VFD-M Series Frequency Master Frequency Pr.10 Pr.11 Pr.12 1st Accel 2nd Accel/ Decel 1st Accel/ Decel Pr.13 Pr.13 Pr.10 2nd Decel Time Mx-GND operation command ON ON ON ON ON OFF 12, 13 External Base Block: Parameter values 12, 13 program Multi-Function Input Terminals: M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42) for external Base Block control. Value 12 is for normally open (N.O.) input, and value 13 is for a N.C. input. B.B.(N.O.) setting by 12 B.B.(N.C.
VFD-M Series 14, 15 Increase/Decrease Master Frequency: Parameter values 14, 15 program the Multi-Function Input Terminals: M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42) to incrementally increase/ decrease the Master Frequency each time an input is received. UP Mx "Close": Freq. will increase by one unit. setting by 14 DOWN Mx "Open":Freq. will decrease by one unit. setting by 15 GND 16, 17 PLC Function Control: Parameter value 16 programs Multi-Function Input Terminal: M1 (Pr.
VFD-M Series Note: The Counter Trigger input can be connected to an external Pulse Signal Generator when counting a process step or unit of material. See the diagram below. 2ms Indication value (Pr.64=1) Counter trigger signal Multi-function input terminal (Pr.38 to Pr.42 =18) 2ms The trigger timing can't be less than 2ms.(<250Hz) (Pr.97=3) counter value is attained. (Pr.45/46=13) Signal output with Pr.97 (Pr.96=5) counter value is attained. (Pr.45/46=14) Signal output with Pr.
VFD-M Series 26 PID Disable (N.O.) / 27 PID Disable (N.C.) This function pause the PID control. It is commonly used for manual operation or function testing, and to recover the PID function when the system is normal. 28 Second Source of Frequency Command This function is used with Pr. 142 to select a different frequency source for control. 29 Forward (contact is open) / Reverse (contact is close) This function has top priority to set the direction for running (If “Pr.
VFD-M Series This parameter sets the voltage range of the analog output signal on output terminal AFM. AFM AFM GND + - GND + Analog Frequency Meter - Analog Current Meter The analog output voltage is directly proportional to the output frequency of the AC drive. A setting of 100% on Pr.44 makes the Maximum Output Frequency (Pr.03) of the AC drive to correspond to the +10VDC analog voltage output. (The actual voltage is about +10VDC, and can be adjusted by Pr.
VFD-M Series Setting 04 05 06 07 08 09 10 11 12 Functions Setting Base-Block (B.B.
VFD-M Series 11 PLC Program completed: terminal output is activated for 0.5 sec. when the PLC program cycle has completed. 12 PLC Program Operation Paused: terminal output is activated when PLC operation is paused. 13 Top Count Value Attained: terminal output is activated when counter reaches the Top Count Value. See diagram for Pr.38 to Pr.42=18. 14 Preliminary Count Value Attained: terminal output is activated when counter reaches the Preliminary Count Value. See diagram for Pr.38 to Pr.42=18.
VFD-M Series AC/DC Power source Multi-function indication output terminals. AC 250V 2A DC 30V 2A RA Faults indication. RB Power indication. BZ LT RC Multi-function PHC output terminals. LT MO1 Pre-set freq. attained PHC 480VDC 50mA MCM Plus terminals Power 48VDC 50mA Minus terminal 5 Pr.47 Desired Frequency Attained a Factory Setting: 0.00 Settings 0.00 to 400.0 Hz Unit: 0.
VFD-M Series Pr.49 Potentiometer Bias Polarity Settings 00 Positive Bias 01 Negative Bias a Factory Setting: 00 This parameter sets the potentiometer Bias Frequency to be positive or negative. Pr.50 Potentiometer Frequency Gain a Factory Setting: 100.0 Settings 0.10 to 200.0% Unit: 1% This parameter sets the ratio of analog input vs frequency output. Pr.
VFD-M Series Max. Output Pr.03 Freq. 60Hz 10Hz Bias Adjustment 0Hz 0V 4mA 40 Factory Settings Pr.03=60Hz--Max. output Freq. Pr.48=16.7%-- bias adjustment Pr.49=0 -- bias polarity Pr.50=100% -- pot. freq. gain Pr.51=0 -- REV motion disable in negative bias 5V 12mA 60 10 0V Hz 10V Potentiometer Scale 10V 20mA It is 60Hz in this range. Example 3: The whole scale of the potentiometer may be used as desired.
VFD-M Series Example 5: In this example, a 6 Hz (10% of 60 Hz) negative bias is used. This setting is used to provide a noise margin (1V in this example) in noisy environments. Note that the top frequency is reduced to 54 Hz. Max. Output Pr.03 Freq. 60Hz 54Hz 0Hz Negative 0V 1V bias 6Hz Factory Settings Pr.03=60Hz--Max. output Freq. Pr.48=10.0% -- bias adjustment Pr.49=1 -- bias polarity Pr.50=100% -- pot. freq. gain Pr.51=0 -- Rev. motion disable in negative bias 24 It's 0Hz within 0 this range.
VFD-M Series Example 8: This example shows how to set up the “anti-slope”, which is an inversely proportional variation of frequency to the input analog signal, required for some applications in process control. A sensor will generate a large signal (such as 20mA or 10V) and the AC Drive will slow or stop. Max. Output Pr.03 Freq. 60Hz 30 Factory Settings anti-slope 0Hz 0V 4mA Pr.03=60Hz--Max. output Freq. Pr.48=100%--bias adjustment Pr.49=1 -- bias polarity Pr.50=100% -- pot. freq. gain Pr.
VFD-M Series This parameter can be used to compensate motor slip. Although no linear, it typically adds 6 Hz for a setting of 10 if Pr.03=60 Hz. When the output current of the AC drive is greater than the motor no-load current (Pr.53), the AC drive will adjust its output frequency according to this parameter. Pr.56 Reserved Pr.57 Rated Current Display of the AC motor drive Factory Setting: ##.# Settings Read Only Pr.57 displays the rated current of the AC motor drive.
VFD-M Series Pr.60 Over-Torque Detection Mode Settings 00 01 Factory Setting: 00 Over-Torque detection disabled. Enabled during constant speed operation until the allowable time for detection (Pr.62) elapses. 02 Enabled during constant speed operation and halted after detection. 03 Enabled during acceleration until the allowable time for detection (Pr.62) elapses. 04 Enabled during acceleration and halted after detection. Pr.
VFD-M Series 04 PV (i) 05 Displays the value of the internal counter (c) 06 Displays the setting Frequency (F) 07 Displays the parameter setting (P) 08 Reserved 09 Output Current (A) 10 Display program operation (0. xxx), Fwd, or Rev The parameter can be set to display the user-defined value. (where v = H x Pr.65 Coefficient K a Settings 0.01 to 160.0 Pr.65 ) Factory Setting: 1.00 Unit: 0.01 The coefficient K determines the multiplying factor for the user-defined unit.
VFD-M Series This parameter defines the Master Frequency when the AC drive is controlled by the communication interface. Pr.67 Skip Frequency 1 Factory Setting: 0.00 Pr.68 Skip Frequency 2 Factory Setting: 0.00 Pr.69 Skip Frequency 3 Factory Setting: 0.00 Settings 0.00 to 400.0 Hz Unit: 0.1 Hz These three parameters determine the three Skip Frequencies that in conjunction with Pr.70, Skip Frequency Band, will cause the AC drive to skip operating in each frequency band. Note: Pr.67 > Pr.68 > Pr.69.
VFD-M Series The parameter defines the carrier frequency of the PWM (Pulse-Width Modulated) output. Electromagnetic Carrier Frequency Acoustic Noise Noise, Leakage Current Heat Dissipation 1KHz Significant Minimal Minimal 15KHz Minimal Significant Significant From the above table, we see that the carrier frequency of PWM output has a significant influence on the electromagnetic noise, heat dissipation of the AC drive, and the acoustic noise to the motor. Pr.
VFD-M Series 10 Over-current during acceleration (OCA) 11 Over-current during deceleration (OCd) 12 Over-current during steady state operation (OCn) 13 Ground fault or fuse failure (GFF) 14 Low voltage (not record) 15 3 Phase Input Power Loss 16 CPU Failure (CF2) 17 External Base-Block (bb) 18 Overload 2 (oL2) 19 Auto Adjustable accel/decel failure (cFA) 20 Software protection code (codE) Pr.
VFD-M Series 04 Continuously execute program cycles step by step (separated by “STOP”) This M drive can be programmed to execute a sequence of operations named “PLC mode”. The PLC program can be used in lieu of any external controls, relays or switches. The AC drive will change speeds and directions according to the user’s desired programming. This parameter selects the PLC operation mode for the drive. Please review the following examples: Example 1 (Pr.78 =01): Execute one cycle of the PLC program.
VFD-M Series Note: The above diagram shows one complete PLC cycle. Program input off and then back on. To restart the cycle, turn the PLC Example 2 (Pr.78 = 02) Continuously executes program cycles: The diagram below shows the PLC program stepping through each speed and then automatically starting again. To stop the PLC program, either pause or stop the program. (Refer to Pr.38 to Pr.42 value 17 and 18) Frequency Pr.20 60Hz Pr.21 50Hz Pr.19 40Hz 30Hz Master freq.=10Hz Pr.17=10 Hz Pr.42=16 Pr.
VFD-M Series Example 4 (Pr.78 = 04) Continuously executes program cycles step by step: In this explanation, the PLC program runs continuously step by step. Also shown are examples of steps in the reserve direction. Note: operating time for each step is 10 times the settings of Pr.81 to Pr.87. Pr.17=10 Hz Pr.42=16 Pr.81=1.0 Pr.18=20 Hz Pr.45=09 Pr.82=1.2 Pr.19=40 Hz Pr.46=10 Pr.83=1.5 Pr.21 Pr.20=60 Hz * Pr.78=04 Pr.84=1.5 Pr.21=50 Hz * Pr.79=34 Pr.85=0.8 Pr.86=1.7 Pr.22=30 Hz Pr.87=1.7 Pr.
VFD-M Series Application Note: PLC program execution will be interrupted when values for JOG parameters 15 and 16 are changed. Pr.79 PLC Forward/Reverse Motion Factory Setting: 00 Settings 00 to 127 This parameter determines the direction of motion for the multi-speed Pr.17 to Pr.23 and Master Frequency. The original direction of Master Frequency will become invalid. Note: A 7-bit binary number is used to program the forward/reverse motion for each of the 8 speed steps (including Master Frequency).
VFD-M Series kW HP Model Number (Pr.80) Rated Output Current (A) Max. Carrier Frequency (kHz) 115V series 0.2 0.4 0.75 0.25 0.5 1.0 0.4 0.5 0.75 1 230V series 1.5 2.2 2 3 3.7 5 5.5 7.5 20 22 24 00 02 04 06 08 10 1.6 2.5 4.2 2.5 5.0 7.0 10 17 25 kW 0.75 HP 1 Model Number 03 (Pr.80) Rated Output 3.0 Current (A) Max. Carrier Frequency (kHz) 15kHz 460V series 1.5 2.2 3.7 5.5 2 3 5 7.5 575V series 1.5 2.2 3.7 5.5 2 3 5 7.5 7.5 10 0.75 1 7.
VFD-M Series Pr.89 Transmission Speed (Baud rate) Settings 00 4800 bps 01 9600 bps 02 19200 bps 03 38400 bps Factory Setting: 01 This parameter sets the transmission speed for communication on the RS-485 serial port Pr.90 Transmission Fault Treatment Settings Factory Setting: 03 00 Warn and Continue Operating 01 Warn and RAMP to Stop 02 Warn and COAST to Stop 03 Keep Operation without Warning Pr.91 Time Out Detection Settings 5 Factory Setting: 0.0 0.1 to 120.0 sec 0.
VFD-M Series Either ASCII or RTU Modbus protocols are used for communication. Users can select the desired mode along through parameters Pr.92 and Pr.113. Each VFD-M AC drive has a pre-assigned communication address specified by Pr.88. The master controller communicates with each AC drive according to its particular address. Code Meaning: ASCII mode: Each 8-bit data is the combination of two ASCII characters.
VFD-M Series ( 8.N.2:Pr.92=3) Start bit 0 1 2 3 4 5 6 7 Stop Stop bit bit 6 7 Even Stop parity bit 6 7 Odd Stop parity bit 8-data bits 11-bits character frame ( 8.E.1:Pr.92=4) Start bit 0 1 2 3 4 5 8-data bits 11-bits character frame ( 8.O.1:Pr.92=5) Start bit 0 1 2 3 4 5 8-data bits 11-bits character frame 3. 3.1 STX Communication Protocol Communication Data Frame: ADR ADR CMD CMD 0 1 0 02H 3.
VFD-M Series 3.3 ADR (Communication Address) Valid communication addresses are in the range of 0 to 254. An address equals to 0 means a broadcast to all AC drives (AMD) in the network. In this case, the AMD will not reply to the master device. For example, communication to AMD with address 16 decimal: ASCII mode: (ADR 1, ADR 0)=’1’,’0’ => ‘1’=31H, ‘0’=30H RTU mode: (ADR)=10H 3.4 CMD (Command code) and DATA (data characters) The format of data characters depends on the command code.
VFD-M Series RTU mode: Command message: Response message: ADR 01H ADR 01H CMD 03H CMD 03H 21H 02H 00H 02H 6FH F7H Number of data (Count by byte) Content of data address 2102H Content of data address 2103H CRC CHK Low CRC CHK High 04H Starting data address Number of data (count by word) CRC CHK Low CRC CHK High 17H 70H 00H 00H FEH 5CH Command code: 06H, write 1 word For example, writing 6000(1770H) to address 0100H of AMD with address 01H.
VFD-M Series 3.5 CHK (check sum) ASCII mode: LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the values of the bytes from ADR1 to last data character then calculating the hexadecimal representation of the 2’s-complement negation of the sum.
VFD-M Series Step 5: Repeat step 3 and 4 until eight shifts have been performed. When this is done, a complete 8-bit byte will have been processed. Step 6: Repeat steps 2 to 5 for the next 8-bit byte of the command message. Continue doing this until all bytes have been processed. The final contents of the CRC register is the CRC value. When transmitting the CRC value in the message, the upper and lower bytes of the CRC value must be swapped, i.e. the lower order byte will be transmitted first.
VFD-M Series Content Address 2000H Command Read/Write 2001H 2002H Status monitor Read only 2100H 2101H Functions 00: No function 01: Stop Bit 0-1 10: Run 11: Jog + Run Bit 2-3 Reserved 00: No function 01: FWD Bit 4-5 10: REV 11: Change direction Bit 6-15 Reserved Freq.
VFD-M Series Content Address Functions Bit 5-7 Reserved Bit 8 1: Main freq. Controlled by communication Bit 9 1: Main freq. Controlled by external terminal Bit 10 1: Operation command controlled by communication Bit 11 1: Parameters have been locked Bit 12 0: Stop 1: Run Bit 13 1: Jog command Bit 14-15 Reserved 2102H Frequency command F (XXX.XX) 2103H Output Frequency H (XXX.XX) 2104H Output Current A (XXX.X) 2105H DC-BUS Voltage U (XXX.X) 2106H Output Voltage E (XXX.
VFD-M Series #define RDR 0x0000 #define BRDL 0x0000 #define IER 0x0001 #define BRDH 0x0001 #define LCR 0x0003 #define MCR 0x0004 #define LSR 0x0005 #define MSR 0x0006 unsigned char rdat[60]; /* read 2 data from address 2102H of AC drive with address 1 */ unsigned char tdat[60]={':','0','1','0','3','2','1','0',’2', '0','0','0','2','D','7','\r','\n'}; void main(){ int i; outportb(PORT+MCR,0x08); /* interrupt enable */ outportb(PORT+IER,0x01); /* interrupt as data in */ outportb(PORT+LCR,(inportb(PORT+LCR) |
VFD-M Series Pr.93 Accel 1 to Accel 2 Frequency Transition Factory Setting: 0.00 Pr.94 Decel 1 to Decel 2 Frequency Transition Factory Setting: 0.00 Settings 0.01 to 400.0 Hz Unit: 0.10 Hz 0.00 disable These functions are used to change acceleration or deceleration depending on attained frequency and not by closing contacts on the external terminals. The priority of this parameter is higher than the time of Accel/Decel 1 and Accel/Decel 2. Pr.
VFD-M Series Pr.97 Preset Count Down Completion Settings Factory Setting: 00 00 to 9999 This parameter sets a preliminary count value for the internal counter. Counter is incremented by a low-to-high transition on one of the programmed Multi-Function Input Terminals: M1 or M2 (see Pr.44 or Pr.45, setting 14). Count starts at 01. Upon completion the selected Multi-Function Output Terminal will close. Preliminary Count could be used to initiate an external event before the “terminal count” is reached.
VFD-M Series 04 If this parameter is set to 04, Accel/Decel time will be equal to or more than parameter Pr.10 ~Pr.13. This parameter should not be used when a braking unit is installed. Pr.102 Auto Voltage Regulation (AVR) Settings Factory Setting: 00 00 AVR function enabled 01 AVR function disabled 02 AVR function disabled when stop 03 AVR function disabled for deceleration AVR function automatically regulates the AC drive output voltage to the Maximum Output Voltage (Pr.03).
VFD-M Series Pr.106 Rated Slip Factory Setting: 3.0 Settings 0.00 to 10.00 Hz Unit: 0.01Hz Example of Slip calculation: The rated speed of 4 poles/3 φ/ 60Hz/ 220V on the nameplate is 1710RPM. The rated slip is then: 60-(1710/(120/P))=3Hz. (being P the number of poles) Pr.107 Vector Voltage Filter Factory Setting: 10 Settings 5 to 9999 Unit: 2ms Pr.108 Vector Slip Compensation Filter Factory Setting: 50 Settings 25 to 9999 Unit: 2ms This parameter sets the low-pass filter in vector control.
VFD-M Series Pr.112 External Terminal Scanning Time Factory Setting: 01 Settings 01 to 20 Unit: 2msec This function screens the signal on I/O terminals for CPU malfunctions due to external transients. A setting of 02, makes the scanning time to be 2 x 2 = 4 msec. Set Pr.77 to 02 before changing settings in Pr.112. Pr.
VFD-M Series Targeted + value - P I Pr.117 Pr.118 + Upper Bound + of Integral + Value Pr.120 Limit of PID Output Frequency Pr.122 One Time Delay Pr.121 Frequency Command D Pr.119 LPF Pr.135 Definition of Detection Value AVI( Pr.128~Pr.130) ACI( Pr.131~Pr.133 ) Pr. 116 PID Feedback Terminal Selection Settings Selection of Detection value Pr.
VFD-M Series Pr. 119 Differential Time (D) Factory Setting: 0.00 Settings 0.00 to 1.00 sec Unit: 0.01sec This parameter determines the damping effect for the PID feedback loop. If the differential time is long, any oscillation will quickly subside. If the differential time is short, the oscillation will subside slowly. Pr.
VFD-M Series Pr. 122 PID Frequency Output Command limit Factory Setting: 00 Settings 00 to 110 % This parameter sets a limit of the PID Command frequency. If this parameter is set to 20%, then the maximum output frequency for the PID operation will be (20% x Pr.01-00). Pr. 123 Feedback Signal Detection Time Factory Setting: 60.0 Settings 0.1 to 3600 sec Unit: 0.1sec 0.0 disable This parameter defines the detection time for the loss of a feedback analog signal.
VFD-M Series This parameter is used to set the AVI input voltage that corresponds to minimum frequency. Pr. 129 Maximum Reference Value Factory Setting: 10.0 Settings 0.0 to 10.0 V This parameter is used to set the AVI input voltage that corresponds to maximum frequency. Pr. 130 Invert Reference Signal AVI (0-10V) Settings 00 Not Inverted 01 Inverted Factory Setting: 00 If this parameter is set to 01, the reference signal is inverted: 0V corresponds to 60Hz in Pr.
VFD-M Series Pr. 134 Analog Input Delay Filter for Set Point Factory Setting: 50 Settings 00 to 9999 Unit: 2ms Pr. 135 Analog Input Delay Filter for Feedback Signal Factory Setting: 5 Settings 00 to 9999 Unit: 2ms These two parameters are used to set the analog input delay filter in set point or feedback signal. Pr. 136 Sleep Period Factory Setting: 0.0 Settings 0.0 to 6550. sec Unit: 0.1sec Pr. 137 Sleep Frequency Factory Setting: 0.0 Settings 0.00 to 400.0 Hz Unit: 0.10Hz Pr.
VFD-M Series Pr. 140 External Up/Down Selection Settings Factory Setting: 00 00 Fixed Mode (keypad) 01 By Accel or Decel Time 02 Reserved This parameter is used to change the Master Frequency externally with the Multifuction Input Terminals. If any two parameters in the group Pr.39-Pr.42 are set to 14 and 15, and Pr.140 is set to 01, the up/down frequency operation is initiated as the contact closes and according to the time of acceleration/deceleration. Pr.
VFD-M Series Pr. 144 Accumulative Motor Operation Day Read Only Settings 00-65535 Days Pr. 145 Accumulative Motor Operation Time (Min.) Read Only Settings 00-1440 Minutes These parameters display accumulative time of motor operation. They will not reset to zero due to parameter reset to factory and will not re-calculate if the 65535 days limit is exceeded. Pr.
VFD-M Series Example: 5 Pr. 152 Skip Frequency Width Factory Setting: 0.00 Settings 0.00 to 400.00Hz Pr. 153 Bias Frequency Width Factory Setting: 0.00 Settings 0.00 to 400.00Hz Frequency of Δ top point Fup= master frequency F + Pr.152 + Pr.153. Frequency of Δ down point Fdown= master frequency F – Pr.152 – Pr.153. Fup Pr.152 Double Pr. 153 Master Pr.10, 12 Frequency (F) Pr.11, 13 Fdown DELTA ELECTRONICS, INC.
VFD-M Series Pr. 154 Reserved Pr.155 Compensation Coefficient for Motor Instability a Factory Setting: 0.0 Settings 0.1 to 5.0 (recommended setting 2.0) 0.0 Disable This parameter is used to improve a condition of unstable current in any specific area. For higher frequencies, you can adjust this parameter to 0.0, and increase the setting value in Pr.155 for 30HP and above (a setting of 2.0 is recommended). Pr.
VFD-M Series CHAPTER 6 MAINTENANCE AND INSPECTIONS Modern AC drives are based on solid state electronics technology. Preventive maintenance is required to operate this AC drive in its optimal condition, and to ensure a long life. It is recommended to perform a monthly check-up of the AC drive by a qualified technician. Before the check-up, always turn off the AC Input Power to the unit.
VFD-M Series CHAPTER 7 TROUBLESHOOTING AND FAULT INFORMATION The AC drive has a comprehensive fault diagnostic system that includes several different alarms and fault messages. Once a fault is detected, the corresponding protective functions will be activated. The following faults are displayed as shown on the AC drive digital keypad display. The three most recent faults can be read on the digital keypad display by viewing Pr.73 to Pr.
VFD-M Series Fault Name Fault Descriptions Corrective Actions 1. Ensure that the ambient temperature falls within the specified temperature range. The AC drive temperature sensor detects excessive heat. 2. Make sure that the ventilation holes are not obstructed. 3. Remove any foreign objects on the heat sinks and check for possible dirty heat sink fins. 4. Provide enough spacing for adequate ventilation.
VFD-M Series Fault Name Fault Descriptions Over-current during acceleration: 1. Short-circuit at motor output. 2. Torque boost too high. 3. Acceleration time too short. 4. AC drive output capacity is too small. Corrective Actions 1. Check for possible poor insulation at the output line. 2. Decrease the torque boost setting in Pr.54. 3. Increase the acceleration time. 4. Replace with the AC drive with one that has a higher output capacity (next HP size). 1.
VFD-M Series Fault Name Fault Descriptions Corrective Actions 1. Switch off power supply. Drive’s internal circuitry abnormal. 2. Check whether the input voltage falls within the rated AC drive input voltage. Switch on the AC drive. The external terminal EF-GND goes from OFF to ON. When external terminal EF-GND is closed, the output will be turned off (under N.O. E.F.). Auto accel/decel failure Don’t use the function of auto acceleration/ deceleration.
VFD-M Series CHAPTER 8 SUMMARY OF PARAMETER SETTINGS a: The parameter can be set during operation Parameter Explanation a Pr.00 Source of Frequency Command a Pr.01 Source of Operation command Pr.02 Pr.03 Pr.04 Stop Method Maximum Output Frequency Maximum Voltage Frequency (Base Frequency) Pr.05 Maximum Output Voltage (Vmax) Pr.06 Mid-point Frequency Pr.07 Mid-point Voltage Pr.08 Minimum Output Freq DELTA ELECTRONICS, INC.
VFD-M Series Parameter Pr.09 a a a a a a a a a a a a a Pr.10 Pr.11 Pr.12 Pr.13 Pr.14 Pr.15 Pr.16 Pr.17 Pr.18 Pr.19 Pr.20 Pr.21 Pr.22 Pr.23 Pr.24 Pr.25 Pr.26 Pr.27 Pr.28 Pr.29 Pr.30 Pr.31 Explanation Minimum Output Voltage Acceleration Time 1 Deceleration Time 1 Acceleration Time 2 Deceleration Time 2 Accel S-curve Jog Accel/Decel Time Jog Frequency 1st Step Speed Freq. 2nd Step Speed Freq. 3rd Step Speed Freq. 4th Step Speed Freq. 5th Step Speed Freq. 6th Step Speed Freq. 7th Step Speed Freq.
VFD-M Series Parameter Explanation Settings Factory Customer Setting Pr.32 Momentary Power Loss Operation Selection 00: Stop operation after momentary power loss 01: Continues after momentary power loss, speed search starts with Master Frequency 02: Continues after momentary power loss, speed search starts with Minimum output Frequency Pr.33 Maximum Allowable Power Loss Time 0.3 to 5.0 sec 2.0 Pr.34 Base-Block Time for Speed Search 0.3 to 5.0 sec 0.5 Pr.
VFD-M Series Parameter Explanation a Pr.43 Analog Output Signal a Pr.44 Analog Output Gain Pr.45 Pr.46 Settings Factory Customer Setting 20: No function 21: RESET command (N.C) 22: Control source: External Terminal 23: Control source: Keypad 24: Control source: Communication 25: Parameter Lock (Write disable, Read is always 0) 26: PID Disable (N.O.) 27: PID Disable (N.C.
VFD-M Series Parameter Explanation Settings 21: Over Voltage stall supervision 22: Forward command 23: Reverse command 24: Zero Speed (Includes Drive Stop) Desired Frequency Attained Adjust Bias of External Input Frequency a Pr.47 a Pr.48 a Pr.49 Potentiometer Bias Polarity 00: Positive Bias 01: Negative Bias a Pr.50 Potentiometer Frequency Gain 0.10 to 200.0% Pr.51 Potentiometer Reverse Motion Enable a a a a Pr.52 Pr.53 Pr.54 Pr.55 Pr.56 Pr.57 Pr.58 a Pr.59 Pr.
VFD-M Series Parameter Pr.61 Pr.62 Explanation Over-Torque Detection Level Over-Torque Detection Time Settings Factory Customer Setting 30 to 200 % 150 0.0 to 10.0 seconds 0.1 00: Decelerate to 0 Hz 01: Stop immediately and display "EF" 02: Continue operation by last frequency command 00: Display AC drive output Frequency (Hz) 01: Display User-defined output Frequency (H*Pr.
VFD-M Series Parameter Explanation Settings Factory Customer Setting 00: No fault occurred Pr.73 Pr.74 Pr.75 Pr.76 Pr.77 Pr.78 Pr.79 Pr.80 Pr.
VFD-M Series Parameter Explanation Settings Factory Customer Setting Pr.82 Time Duration of 2nd Step Speed 00 to 9999 sec 00 Pr.83 Time Duration of 3rd 00 to 9999 sec Step Speed 00 Pr.84 Time Duration of 4th 00 to 9999 sec Step Speed 00 Pr.85 Time Duration of 5th 00 to 9999 sec Step Speed 00 Pr.86 Time Duration of 6th 00 to 9999 sec Step Speed 00 Pr.87 Pr.88 Pr.89 Pr.90 Pr.91 Pr.92 Pr.93 Pr.94 Pr.95 Pr.96 Pr.
VFD-M Series Parameter Pr.98 Pr.99 Pr.
VFD-M Series Parameter Pr.114 Pr.115 Pr.116 Pr.117 Pr.118 Pr.119 Pr.120 Pr.121 Pr.122 Pr.123 Pr.124 Pr.125 Pr.126 Pr.127 Pr.128 Pr.129 Explanation Settings 00: Fan Off when the drive stop after 1 Min. 01: AC Drive Runs and Fan On, AC Drive Cooling Fan Control Stops and Fan Off 02: Always Run 03: Reserved 00: Disable 01: Keypad (based on Pr.00 setting) PID Set Point 02: AVI (external 0-10V) Selection 03: ACI (external 4-20mA) 04: PID et point (Pr.
VFD-M Series Parameter Explanation Settings Factory Customer Setting 00: Not inverted 01: Inverted 00 0.0 to 20.0mA 4.0 0.0 to 20.0mA 20.0 Pr.136 Invert Reference Signal AVI (0-10V) Minimum Reference Value (4-20mA) Maximum Reference Value (4-20mA) Invert Reference Signal (4-20mA) Analog Input Delay Filter for Set Point Analog Input Delay Filter for Feedback Signal Sleep Period 0.0 to 6550. sec 0.0 Pr.137 Sleep Frequency 0.00 to 400.0 Hz 0.00 Pr.138 Wake Up Frequency 0.00 to 400.0 Hz 0.
VFD-M Series Parameter Pr.149 Pr.150 Pr.151 Pr.152 Pr.153 Pr.154 a Pr.155 a Pr.156 a Pr.157 Explanation Gear Ratio for Simple Index Function Index Angle for Simple Index Function Deceleration Time for Simple Index Function Skip Frequency Width Bias Frequency Width Reserved Compensation Coefficient for Motor Instability Communication Response Delay Time Communication Mode Selection Settings 4 to 1000 Factory Customer Setting 200 00.0 to 360.0 180.0 0.00 to 100.00 sec 0.00 0.00 to 400.
VFD-M Series STANDARD SPECIFICATIONS Voltage Class 115V Class Input Rating Output Rating Model Number VFD-XXXM Max. Applicable Motor Output (kW) Max. Applicable Motor Output (hp) Rated Output Capacity (kVA) Rated Output Current (A) Maximum Output Voltage (V) Output Frequency (Hz) Carrier Frequency (kHz) 1-15 Rated Input Current (A) Rated Voltage, Frequency Voltage Tolerance Frequency Tolerance Cooling Method Weight (kg) 002 004 007 0.2 0.4 0.75 0.25 0.5 1.0 0.6 1.6 1.0 2.
VFD-M Series Input Rating Voltage Class Rated Input Current (A) Rated Voltage Voltage Tolerance Frequency Tolerance Cooling Method Weight (kg) Input Rating Output Rating Voltage Class Model Number VFD-XXXM Max. Applicable Motor Output (kW) Max. Applicable Motor Output (hp) Rated Output Capacity (kVA) Rated Output Current (A) Maximum Output Voltage (V) Output Frequency (Hz) Carrier Frequency (kHz) Rated Input Current (A) 5.7 1.5 1.5 007 015 575V Class 022 037 055 075 0.75 1.5 2.2 3.7 5.
VFD-M Series General Specifications External M0 to M5 can be combined to offer various modes of operation, RS-485 serial Signal interface (MODBUS).
VFD-M Series ACCESSORIES B.1 Non-fuse Circuit Breaker Chart Per UL 508C, paragraph 44.8.6, part a, 1. For 1-phase drives, the current rating of the breaker shall be four times maximum of input current rating. 2. For 3-phase drives, the current rating of the breaker shall be four times maximum of output current rating. (Note: Please select enough current capacity of NFB.) 1-phase 3-phase Input Current (A) Output Current (A) Model Model VFD002M11A 6.0 VFD004M23A 2.5 VFD004M11A 9.0 VFD007M23A 5.
VFD-M Series B.2 Fuse Specification Chart Smaller fuses than those shown in the table are permitted. Model VFD002M11A VFD004M11A VFD007M11A VFD004M21A VFD004M21B VFD007M21A VFD007M21B Input Current (A) Output Current (A) 6 9 16 6.3 6.3 11.5 Line Fuse 1.6 2.5 4.2 2.5 2.5 5.0 5.0 I (A) 15 20 30 15 15 20 20 Bussmann P/N JJN-15 JJN-20 JJN-30 JJN-15 JJN-15 JJN-20 JJN-20 7.0 30 JJN-30 VFD015M21A 11.5 15.7 VFD015M21B 15.7 7.0 30 JJN-30 VFD022M21A 27 10 50 JJN-50 VFD004M23A 2.9 7.6 2.
VFD-M Series B.3 All Braking Resistors & Braking Units Use in AC Drives 575V Series 460V Series 230V Series 115V Series Voltage Note: Please only use DELTA resistors and recommended values. Other resistors and values will void Delta’s warranty. Please contact the nearest Delta representative near you for use of the special resistors. There should be at least 10 cm away from AC drive to avoid possible noise.
VFD-M Series Braking Resistors & Braking Units B-4 DELTA ELECTRONICS, INC.
VFD-M Series Braking Resistors & Braking Units B DELTA ELECTRONICS, INC.
VFD-M Series Braking Resistors & Braking Units B-6 DELTA ELECTRONICS, INC.
VFD-M Series B.
VFD-M Series EMI Filter (RF015M21AA / RF022M43AA) 50 (1.97) 28 (1.1) 100 (3.94) 70 (2.76) 212 226 (8.35) (8.9) 212 (8.35) 15 (0.59) 26 (1.02) 4.5 (0.18) B-8 DELTA ELECTRONICS, INC.
VFD-M Series EMI Filter (RF022M21BA / RF075M43BA) 60 (2.36) 30 (1.18) 125 (4.82) 80 (3.15) 295 282 (11.1) (11.61) 282 (11.1) 15 (0.59) 30 (1.18) 5.5 (0.22) B DELTA ELECTRONICS, INC.
VFD-M Series EMI Filter (16TDT1W4S) Used on 0.5-3 HP/230V Three Phase Models. EMI Filter (40TDS4W4B) Used on 5-7.5 HP/230V Three Phase Models. B-10 DELTA ELECTRONICS, INC.
VFD-M Series B.5 Din Rail-DR01 Adapter Units: mm (inch) Models VFD004M21A/23A, VFD007M21A/23A, VFD015M21A/23A To mount the drive on a Din Rail adapter, place the drive and mounting plate on the rail and push the lever toward the rail. B DELTA ELECTRONICS, INC.
VFD-M Series Din Rail-DR02 Adapter Units: mm (inch) Models VFD002M11A, VFD004M11A/21B, VFD007M11A/21B/43B/53A, VFD015M21B/43B/53A, VFD022M23B/43B/53A To mount the drive on a Din Rail adapter, place the drive and mounting plate on the rail and push the lever toward the rail. B-12 DELTA ELECTRONICS, INC.
VFD-M Series B.6 Remote Controller RC-01 Unit: mm (inch) B 8 6 5 4 16 15 14 13 11 RC-01 terminal block (wiring connections) AFM GND AVI +10V GND M2 M0 M1 M3 VFD-M I/O block VFD-M Programming Pr.00 set to d01 (jumper #5 must be across pins 2&3) Pr.01 set to d01 (external controls) Pr.38 set to d01 (M0, M1 set as run/stop and fwd/rev) Pr.39 set to d05 (M2 set for reset) Pr.40 set to d09 (M3 set for jog select) DELTA ELECTRONICS, INC.
VFD-M Series B.7 Zero Phase Reactor RF220X00A UNIT: mm(inch) Cable type (600V Insulated unshielded Cable) Single-core Three-core Recommended Wire Size Nominal AWG mm2 (mm2) Qty. Wiring Method ≦10 ≦5.3 ≦5.5 1 Diagram A ≦2 ≦33.6 ≦38 4 Diagram B ≦12 ≦3.3 ≦3.5 1 Diagram A ≦1 ≦42.4 ≦50 4 Diagram B Diagram A Please wind each wire 4 times around the core. The reactor must be put at inverter side as close as possible.
VFD-M Series DIMENSIONS Digital Keypad Unit: mm [inches] C DELTA ELECTRONICS, INC.
VFD-M Series Digital Keypad – Mounting Panel A Unit: mm [inches] C-2 DELTA ELECTRONICS, INC.
VFD-M Series Digital Keypad – Mounting Panel B Unit: mm [inches] C DELTA ELECTRONICS, INC.
VFD-M Series VFD004M21A VFD004M23A VFD007M21A VFD007M23A VFD015M21A VFD015M23A 0.4 kW (0.5 HP) 0.4 kW (0.5 HP) 0.75 kW (1.0 HP) 0.75 kW (1.0 HP) 1.5 kW (2.0 HP) 1.5 kW (2.0 HP) 230V / 1-phase or 3-phase 230V / 3-phase 230V / 1-phase or 3-phase 230V / 3-phase 230V / 1-phase or 3-phase 230V / 3-phase Unit: mm [inches] 5.0 [ ] 0.2 10.0 [0.39] 113.0 [4.45] 10.0 [0.39] 130.5 [5.14] 141.5 [5.57] 85.0 [3.35] 74.0 [2.91] 14.0 [0.55] 2.0 [0.08] 10.0 [0.39] 30.5 [1.20] C-4 49.0 [1.
VFD-M Series VFD002M11A VFD004M11A VFD004M21B VFD007M11A VFD007M21B VFD007M43B VFD007M53A VFD015M21B VFD015M43B VFD015M53A VFD022M23B VFD022M43B VFD022M53A 0.2 kW (0.25 HP) 0.4 kW (0.5 HP) 0.4 kW (0.5 HP) 0.75 kW (1.0 HP) 0.75 kW (1.0 HP) 0.75 kW (1.0 HP) 0.75 kW (1.0 HP) 1.5 kW (2.0 HP) 1.5 kW (2.0 HP) 1.5 kW (2.0 HP) 2.2 kW (3.0 HP) 2.2 kW (3.0 HP) 2.2 kW (3.
VFD-M Series VFD022M21A VFD037M23A VFD037M43A VFD037M53A VFD055M23A VFD055M43A VFD055M53A VFD075M43A VFD075M53A 2.2 kW (3.0 HP) 230V / 1-phase or 3-phase 3.7 kW (5.0 HP) 230V / 3-phase 3.7 kW (5.0 HP) 460V / 3-phase 3.7 kW (5.0 HP) 575V / 3-phase 5.5 kW (7.5 HP) 230V / 3-phase 5.5 kW (7.5 HP) 460V / 3-phase 5.5 kW (7.5 HP) 575V / 3-phase 7.5 kW (10 HP) 460V / 3-phase 7.5 kW (10 HP) 575V / 3-phase Unit: mm [inches] 15.0 [0.59] 3] 8.2 [0.32] 166.3 [6.55] 10.5 [0.41] 220.0 [8.66] 205.0 [8.07] 235.
VFD-M Series DELTA ELECTRONICS, INC.
VFD-M Series DELTA ELECTRONICS, INC.