Specifications
B
VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
B-1
ACCESSORIES
B.1 Non-fuse Circuit Breaker Chart
Per UL 508C, paragraph 44.8.6, part a,
1. For 1-phase drives, the current rating of the breaker shall be four times maximum of input
current rating.
2. For 3-phase drives, the current rating of the breaker shall be four times maximum of output
current rating.
(Note: Please select enough current capacity of NFB.)
1-phase 3-phase
Model
Input Current (A)
Model
Output Current (A)
VFD002M11A 6.0 VFD004M23A 2.5
VFD004M11A 9.0 VFD007M23A 5.0
VFD007M11A 16 VFD015M23A 7.0
VFD004M21A 6.3 VFD022M23B 10.0
VFD007M21A 11.5 VFD037M23A 17
VFD015M21A 15.7 VFD055M23A 25
VFD004M21B 6.3 VFD007M43B 3.0
VFD007M21B 11.5 VFD015M43B 4.0
VFD015M21B 15.7 VFD022M43B 5.0
VFD022M21A 27 VFD037M43A 8.2
VFD055M43A 13
VFD075M43A 18
VFD007M53A 1.7
VFD015M53A 3.0
VFD022M53A 4.2
VFD037M53A 6.6
VFD055M53A 9.9
VFD075M53A 12.2