Specifications

VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-22
This parameter sets the voltage range of the analog output signal on output terminal
AFM.
+-
AFM
GND
A
nalog Frequency Meter
+-
AFM
GND
A
nalog Current Meter
The analog output voltage is directly proportional to the output frequency of the AC drive. A
setting of 100% on Pr.44 makes the Maximum Output Frequency (Pr.03) of the AC drive to
correspond to the +10VDC analog voltage output. (The actual voltage is about +10VDC, and
can be adjusted by Pr.44)
The analog output voltage is also directly proportional to the output current of the AC drive. A
setting of 100% on Pr.44 makes the 2.5 times rated current of the AC drive to correspond to
the +10 VDC analog voltage output. (The actual voltage is about +10 VDC, and can be
adjusted by Pr.44)
Note: Any type of voltmeter can be used. If the meter reads full scale at a voltage less than 10
volts, then Pr.44 should be set by the following formula:
Pr.44 = ((meter full scale voltage)/10)×100%
For Example: When using a meter with a full scale of 5 volts, adjust Pr.44 to 50%
Pr.45
Multi-function Output Terminal 1 (Photocoupler output) Factory Setting: 00
Pr.46
Multi-function Output Terminal 2 (Relay output) Factory Setting: 07
Settings 00 to 24
Function Table List:
Setting Functions Setting Functions
00 AC Drive Operational 13 Top Count Value Attained
01
Maximum Output Frequency
Attained
14 Preliminary Counter Value Attained
02 Zero speed 15
Warning (PID feedback loss,
communication error)
03 Over-Torque detection 16 Below the Desired Frequency