Specifications

VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-24
11
PLC Program completed:
terminal output is activated for 0.5 sec. when the PLC
program cycle has completed.
12 PLC Program Operation Paused:
terminal output is activated when PLC operation is
paused.
13
Top Count Value Attained:
terminal output is activated when counter reaches the Top
Count Value. See diagram for Pr.38 to Pr.42=18.
14
Preliminary Count Value Attained:
terminal output is activated when counter reaches
the Preliminary Count Value. See diagram for Pr.38 to Pr.42=18.
15
Warning (PID feedback loss, communication error):
the contact will be “close” when
PID feedback loss or communication is error.
16
Below the Desired Frequency:
the contact will be “close” when output frequency is
less than desired frequency.
17
PID supervision:
the contact will be “close” when PID offset exceeds the setting of
P126 and P127.
18
Over voltage supervision:
the contact will be “close” before over voltage. It will be
activated at 370Vdc in 230V series and at 740Vdc in 460 series.
19
Over Heat supervision:
the contact will be “close” before 90
°
C.
20
Over Current stall supervision:
the contact will be “close” before exceeding the
setting of P26/P27.
21
Over voltage stall supervision:
the contact will be “close” before exceeding the
setting of P25.
22
Forward command:
the contact will be “close” with forward command.
23
Reverse command:
the contact will be “close” with reverse command.
24
Zero Speed (Includes Drive Stop):
the contact will be “close” when the setting
frequency is less than min. frequency or drive stop.