Specifications

VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-34
The parameter defines the carrier frequency of the PWM (Pulse-Width Modulated)
output.
Carrier Frequency Acoustic Noise
Electromagnetic
Noise, Leakage
Current
Heat Dissipation
1KHz
15KHz
Significant
Minimal
Minimal
Significant
Minimal
Significant
From the above table, we see that the carrier frequency of PWM output has a significant
influence on the electromagnetic noise, heat dissipation of the AC drive, and the acoustic
noise to the motor.
Pr.72
Auto Restart Attempts After Fault Factory Setting: 00
Settings 00 to 10
When this parameter is enabled (set different to zero), the AC Drive will restart/reset
automatically up to 10 times after the occurrence of certain type of faults (over-current
OC, over-voltage OV). If enabled, the AC drive will restart on “speed search”, which
begins at Master Frequency. Setting this parameter to 0 will disable this operation. To set
the fault recovery time after a fault, please see base-block time for speed search (Pr.34).
Pr.73
Present Fault Record Factory Setting: 00
Pr.74
Second Most Recent Fault Record Factory Setting: 00
Pr.75
Third Most Recent Fault Record Factory Setting: 00
Settings 00
(no fault occurred )
01
Over-current (oc)
02
Over-voltage (ov)
03
Overheat (oH)
04
Overload (oL)
05
Overload 1 (oL1)
06
External Fault (EF)
07
CPU failure 1 (CF1)
08
CPU failure 3 (CF3)
09
Hardware Protection Failure (HPF)