Specifications
VFD-M Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-62
Pr. 144
Accumulative Motor Operation Day
Read Only
Settings 00-65535 Days
Pr. 145
Accumulative Motor Operation Time (Min.)
Read Only
Settings 00-1440 Minutes
These parameters display accumulative time of motor operation. They will not reset to
zero due to parameter reset to factory and will not re-calculate if the 65535 days limit is
exceeded.
Pr. 146
Line Start Lockout
Factory Setting: 00
Settings 00 Disable
01 Enable
When Line Start Lockout is disabled (also known as Auto-Start), the drive will start when
powered-up with run commands applied. To start in Line Start Lockout mode, the AC
drive must see the run command go from stop to run after power up. When enabled, the
AC drive will not start when powered up if run commands were applied.
Pr. 147
Decimal Number of Accel / Decel Time
Factory Setting: 00
Settings 00 One Decimal
01 Two Decimals
It sets the number of decimals in the accel/decel time. It can be used for Acceleration /
Deceleration Time 1, Acceleration / Deceleration Time 2 and JOG Acceleration /
Deceleration Time.
Pr. 148
Number of Motor Poles
Factory Setting: 04
Settings 02 to 20
Pr. 149
Gear Ratio for Simple Index Function
Factory Setting: 200
Settings 4 to 1000
Pr. 150
Index Angle for Simple Index Function
Factory Setting: 180.0
Settings 00.0 to 360.0
Pr. 151
Deceleration Time for Simple Index Function
Factory Setting: 0.00
Settings 0.00 to 100.00 sec 0.00 Disable
This parameter should be used with Pr. 39-Pr.42 (setting 31).