User manual

Brick Controller User Manual
PinOuts and Software Setup 133
The calculated Ixx69 specifies the maximum command output value which corresponds to the maximum
PFM Frequency:
I6826=3 ; MACRO IC Channel 2 Output Mode Select. C PFM
M8000->Y:$7841C,8,16,S ; Supplementary Channel 2* Output C Command Value
; Min=0, Max= Calculated Ixx69
M8001->X:$7841D,21 ; Invert C Output Control. 0=no inversion, 1=invert
M8001=0 ;
Testing the J9 PFM Output
Writing directly to the suggested M-variable (i.e. M8000) values proportional to the calculated Ixx69,
produces corresponding frequencies:
M8000
PFM [KHz]
0
0
1213
11
2427
22