104 PMAC I-Variable Specifiation
For systems with PMAC2 digital current loop closure, the commutation/feedback polarity
match is independent of the servo/feedback polarity. Once Ix72 has been set for proper
commutation/feedback polarity, the proper position-loop servo/feedback polarity must still
be established.
See Also
I-variables Ix70, Ix71
Encoder I-Variable 0
Setting Up PMAC Commutation
Getting Started Section, Setting Up A PMAC-Commutated Motor
Ix73 Motor x Phase Finding Output Value
Range
-32,768 .. 32,767
Units
Bits of 16-bit DAC
Default
0
Remarks
WARNING:
An unreliable phasing search method can lead to a runaway
condition. Test your phasing search method carefully to make sure
it works properly under all conceivable conditions. Make sure your
Ix11 fatal following error limit is active and as tight as possible so
the motor will be killed quickly in the event of a serious phasing
search error.
Ix73 defines the magnitude of the open-loop output to be used if a power-on phasing
search is done for a PMAC-commutated motor (Ix01=1). A phasing search is required for
a synchronous motor (Ix78=0) such as a permanent-magnet brushless motor with no
absolute position sensor (Ix81=0). The phasing search is done automatically as part of the
power-on phasing search if Ix80 is 1 or 3; if Ix80 is 0 or 2, the on-line $ command must be
used must be used to initiate the phasing search.
If Ix80 is 0 or 1, the two-guess phasing search is used, and Ix73 controls the “vector”
magnitude of the open-loop output that is distributed among the phases according to the
guessed phasing angle.
If Ix80 is 2 or 3, the stepper-motor phasing search is used, and Ix73 controls the magnitude
of current forced into individual phase(s) to lock the motor to a position like a stepper
motor. In this method, if the PMAC2 is not performing current loop closure for the motor
(Ix82 = 0) and Ix72 > 128, then Ix73 should be set to a negative number of the desired
magnitude. In all other cases it should be set to a positive number. If the sign of Ix73 is
wrong for your setup, the motor will run away when the loop is closed.
Values of 2000 to 6000 are typically used for Ix73 in either method.
See Also
Power-Up Phasing Search (Setting Up PMAC Commutation)
I-Variables Ix01, Ix74, Ix78, Ix80, Ix81
Ix74 Motor x Phase Finding Time
Range
0 .. 255
Units
Servo Interrupt Cycles (for Ix80 = 0 or 1)
or
Servo Interrupt Cycles * 256 (for Ix80 = 2 or 3)
Default
0