Reference Manual
PMAC 2 Software Reference
PMAC I-Variable Specification 81
For reference, the possible values and their meanings are:
Hex Digit Function
$0: Low-true amp fault enabled; all motors killed on fault or excess following error
(default)
$1: Amp fault disabled; all motors killed on excess following error
$2: Low-true amp fault enabled: coordinate system motors killed on fault or excess
following error
$3 Amp fault disabled; coordinate system motors killed on excess following error
$4 Low-true amp fault enabled; only this motor k8illed on fault or excess following
error
$5: Amp fault disabled; only this motor killed on excess following error
$6: Low-true amp fault enabled; only this motor killed on fault or excess following
error
$7: Amp fault disabled; only this motor killed on excess following error
$8 High-true amp fault enabled; all motors killed on fault or excess following error
(default)
$9: Amp fault disabled; all motors killed on excess following error
$A: High-true amp fault enabled; coordinate system motors killed on excess
following error
$B: Amp fault disabled; coordinate system motors killed on excess following error
$C: High-true amp fault enabled; only this motor killed on fault or excess following
error
$D: Amp fault disabled; only this motor killed on excess following error
$E: High-true amp fault enabled; only this motor killed on fault or excess following
error
$F: Amp fault disabled; only this motor killed on excess following error
Example
1. Motor 1 using flags 1 with amp-enable output, and low-true amp fault disabling all
motors: I125=$00C000 or I125=$C000
2. Motor 1 using flags 1 with direction output, and low-true amp fault disabling all
motors:
I125=$01C000
3. Motor 1 using flags 1 with amp-enable output, and low-true amp fault disabling only
coordinate system motors: I125=20C000
4. Motor 1 using flags 1 with direction output, and amp-fault disabled, with excess F.E.
disabling off C.S motors: I125=$31C000
5. Motor 1 using flags 5 with amp-enable output, and high-true amp fault disabling only
this motor: I125=$C0C010
See Also
Selecting the Flag Register (Setting up a Motor)
Homing Moves (Basic Motor Moves)
I-variables Ix02, Ix03 Ix11
Encoder/Flag I-Variables 2 and 3
Jumper(s) E17; JMACH connector flag I/O pins