STEP 10. MAKING ADJUSTMENTS
Since some sink types (i.e. stainless steel) are made of a conductive material, and some installations may be near other foreign
conductive materials. Adjustments to the sensitivity of the electrical field may be required to ensure a consistent operation. If
you find that after ensuring all electrical and mechanical connections are firm and rigid that the product is still not performing
consistently, the default sensitivity settings of the driver board may be adjusted. Follow these steps to make sensitivity adjust-
ments.
1. Turn off the power to the driver board by disconnecting the driver board from the battery pack or hardwire converters.
NOTE: When disconnecting power - grab the battery connection and wait at least one second before disconnecting the
power. When the battery connection is touched, it trips the electronics and turns on the solenoid. Waiting for at least one
second before disconnecting the power will allow the electronics to reset themselves and shut off the solenoid.
2. Locate the sensitivity selector switch located on the driver board (Fig. 7).
3. Using a finger or small screwdriver, gently set the sensitivity level one step up or down from its current position. Use the
sensitivity selection chart (Fig. 7) to ensure the correct setting is chosen.
4. Once the selection has been made, re-apply power to the driver board and allow for calibration as per Step 7a and 7b.
5. Test for operation and repeat steps 1-4, if necessary.
INSTALLATION AND SET UP INSTRUCTIONS
Installation should be in accordance with local plumbing and electrical codes.
FLUSH ALL PIPES THOROUGHLY BEFORE INSTALLATION.
NOTE: Fig. 7 depicts a driver board with
the LOW Sensitivity setting selected.
Sensitivity Levels:
As a rule of thumb, the High sensitivity
level will produce a sensing range of
approximately 3.5”. The Low sensitivity
level will reduce the electrical field so
that the spout must be touched in order
to operate.
Fig. 7
Switch 1
ON
ON
OFF
OFF
Switch 2
ON
OFF
ON
OFF
Sensitivity
HIGH
MEDIUM HIGH
MEDIUM LOW
LOW
This Delta Commercial faucet is designed and engineered in accordance with the highest quality and performance standards.
With proper care, it will give you years of trouble free service. Care should be given to the cleaning of this product. Although
the chrome finish is extremely durable, it can be DAMAGED by ACIDIC CLEANERS (i.e., cleaners designed specifically for
vitreous china lavatories and water closets), HARSH ABRASIVES or POLISH. To clean, simply wipe the surface with a damp
cloth and blot dry with a soft towel.
CARE INSTRUCTIONS