Installation Sheet

Ļ
Fig. 11
Page 5
www.specselect.com
Cover
Fig. 10
Valve
Spacer
(Replace
with
SOLENOID
Valve and
washers
after system
is flushed)
Solenoid Valve
(INSTALL:
replacing
SPACER after
system is
flushed.)
SOLENOID
may be
ROTATED to
ALLOW for installation
of COVER ASSEMBLY.
209493 Rev. A
STEP 5. TEST FOR OPERATION
Test for operation. If OK, then close lid - Use caution not to damage wires or components on
electronic driver board. Route wires through notches/openings in the box. See Fig 8.
Secure lid using screws.
If faucet leaks from spout outlet:
SHUT OFF WATER SUPPLIES. Check proper solenoid connection. Replace solenoid if problem
persists.
If faucet exhibits very low flow:
A) Remove and clean Aerator, or
B) SHUT OFF WATER SUPPLY. Clean or replace Screen Assembly.
If unit does not work properly, see Trouble Shooting Guide on pages 16 & 17.
STEP 6. BASIC OPERATION AFTER CALIBRATION
Proximity
®
sensing technology works by creating an electrical field around a conductor (the spout)
and monitoring the change in capacitance that the conductor undergoes. The change in capaci-
tance (the ability to store an electrical charge) is brought on by a 2nd conductor (a human body)
entering the Proximity
®
field. As the human hand enters and leaves the vicinity of the electrical field around
the spout, the solenoid is opened and closed accordingly. It is critical in the installation process that all
electrical and mechanical connections be as tight and rigid as possible, ensuring a smooth signal is carried
from the driver board to the spout, and back again.
591TPxxx1TR Battery Operated Control Box #1 Trim
Installation should be in accordance with local plumbing and electrical codes.
FLUSH ALL PIPES THOROUGHLY BEFORE INSTALLATION.
INSTALLATION AND SET UP INSTRUCTIONS
Fig. 9
Top Spacer
& Gasket
Washer
Nut
Spout
Bottom Spacer
Sensor
Module
After calibration, test the function of the product by placing your
hands within close proximity of the spout (ensuring hands are
moving as if washing hands). The solenoid will stay open
while hands are moving, then close once hands are removed
from the sensing zone.
Water