User's Manual

5
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-19
5.5 Group 4: Input Function Parameters
04 - 00 Multi-function Input terminal 1
Factory Setting: 01
04 - 01 Multi-function Input terminal 2
Factory Setting: 02
04 - 02 Multi-function Input terminal 3
Factory Setting: 03
04 - 03 Multi-function Input terminal 4
Factory Setting: 04
04 - 04 Multi-function Input terminal 5
Factory Setting: 05
04 - 05 Multi-function Input terminal 6
Factory Setting: 07
04 - 06 Multi-function Input terminal 7
Factory Setting: 08
04 - 07 Multi-function Input terminal 8
Factory Setting: 09
Settings 00~31
Setting Functions Descriptions
00 No function
All unused terminals should be set to 00, to
assure they have no effect on drive operation.
01 Multi-Speed terminal 1
02 Multi-Speed terminal 2
03 Multi-Speed terminal 3
04 Multi-Speed terminal 4
Allows selection of the 15 multi-step speeds.
Please refer to 05-00 to 05-14 to program the
15 step speeds.
05 Reset (NO)
06 Reset (NC)
Clears (Reset) a fault and returns the AC drive
to normal operation.
07 Jog operation (JOG)
Enables the JOG command. Works identical
to the JOG key on the digital keypad.
08 Accel/Decel disable
Stops the acceleration or deceleration of the
AC drive. AC drive then maintains a constant
speed.
09 Accel/Decel 2 selection
10 Accel/Decel 3 selection
A corresponding terminal set to value 09 and
closed selects Accel/Decel time 2. A
corresponding terminal set to value 10 and
closed selects Accel/Decel time 3.
Accel/Decel time 4 is selected when both
terminals are closed.
11 B.B. (NO) input
12 B.B. (NC) input
Enables the base block (pause) function.
Please refer to Pr.08-08, for base block
functions.
13 Increase Frequency
14 Decrease Frequency
Enables the external terminals to increase or
decrease the Master Frequency command
each time an input is received. Terminals are
not active during a stop command.
15 Emergency stop (NO)
16 Emergency stop (NC)
Generates an external fault (EF1). The
function is identical to the external terminal
(EF).