User's Manual

Chapter 5 Troubleshooting|
Revision August 2008, 03VE, SW V2.04 5-5
5.7 Display of KPV-CE01 is Abnormal
Abnormal display or no display
Turn the power off and power
on again after display is off
No
Ye s
Ye s
Ye s
No
Display normal?
AC motor drive works normally
Fix connector and eliminate noise
Check if all connectors are connected
well and if there is no noise
AC motor drive has malfunction.
Please contact DELTA.
5.8 Phase Loss (PHL)
Phase loss
No
Yes
Check if the wiring of terminals R, S and T is OK
Connect all three
phase well
Check if the screws of terminals are tightened
No
Tighten all screws
Maybe AC motor drive has malfunction or misoperation
due to noise. Please contact DELTA.
No
Yes
Yes
Please check the wiring
and power system for
abnormal power
Check if the input voltage of R, S, T is unbalanced
Yes
Yes
Please check the wiring
and power system for
abnormal power
Check if the input voltage of R, S, T is unbalanced
No
Yes
Please check the fuse
at AC side
Check if it is 40hp and above