User's Manual
Table Of Contents
- Preface
- Table of Contents
- Chapter 1 Introduction
- 1.1 Receiving and Inspection
- 1.2 Appearances
- 1.3 Installation Steps
- 1.4 Storage
- Chapter 2 Installation and Wiring
- Chapter 3 Start Up
- Chapter 4 Digital Keypad Operation
- Chapter 5 Parameters
- Chapter 6 Fault Code Information
- Chapter 7 Troubleshooting
- 7.1 Over Current (OC)
- 7.2 Ground Fault
- 7.3 Over Voltage (OV)
- 7.4 Low Voltage (Lv)
- 7.5 Over Heat (OH)
- 7.6 Overload
- 7.7 Keypad Display is Abnormal
- 7.8 Phase Loss (PHL)
- 7.9 Motor cannot Run
- 7.10 Motor Speed cannot be Changed
- 7.11 Motor Stalls during Acceleration
- 7.12 The Motor does not Run as Expected
- 7.13 Electromagnetic/Induction Noise
- 7.14 Environmental Condition
- 7.15 Affecting Other Machines
- Chapter 8 Maintenance and Inspections
- Appendix A Specifications
- Appendix B Accessories
- Appendix C How to Select the Right AC Motor Drive
- Appendix D CE
![](/manual/delta/ac-motor-drive-vfd007s23a/user-s-manual-english/images/img-124.png)
Chapter 5 Parameters|VFD-S Series
5-78 Revision August 2006, SE08, SW V2.61
the setting frequency of parameters, such as Max. operation frequency, 1
st
speed and etc.,
they are still needed to set with actual value.
P
A-02
I
A-03
A-01
+
+
+
+
Targe t
Value
Detection
Value
Gain
D
A-04
A-05
A-07
Integration's
Upper
Bound
Frequency
A-06
One-Time
Delay
Output Value
A-00
PID Frequency
Output
Command
Limit
Frequency
Command
If the input range of sensor is 0~SI_max, output range is SO_min~SO_max and then
Input
Per output
is
SI_max
SO_max-SO_min
, set drive input to sensor output
Set input range of drive is D_range= 10V(0~10V) or 16mA (4~20mA) that correspond to 0~1-00Hz
and then
Outpu
t
Per input
will be
1-00
D_range
According to the display value of F and H = actual value ¯A-13/1-00, and then
Display value of F, H
Actual value
=A-13/1-00. If you want the result to be display value = sensor output and actual value = drive output,
and then
A-13
1-00
SI_max
SO_max-SO_min
A-01
100
1-00
D_range
=
X
A-13
=
SI_max
SO_max-SO_min
A-01
100
X D_rangeX
Example:
Sensor: 0~6 psi input corresponds to 0~5V output drive AVI: 0~10V input corresponds to 0~60Hz, A-
01=100
A-13
=
6
5-0
100
100
X 10X
=
12