User's Manual
Table Of Contents
- Preface
- Table of Contents
- Chapter 1 Introduction
- 1.1 Receiving and Inspection
- 1.2 Appearances
- 1.3 Installation Steps
- 1.4 Storage
- Chapter 2 Installation and Wiring
- Chapter 3 Start Up
- Chapter 4 Digital Keypad Operation
- Chapter 5 Parameters
- Chapter 6 Fault Code Information
- Chapter 7 Troubleshooting
- 7.1 Over Current (OC)
- 7.2 Ground Fault
- 7.3 Over Voltage (OV)
- 7.4 Low Voltage (Lv)
- 7.5 Over Heat (OH)
- 7.6 Overload
- 7.7 Keypad Display is Abnormal
- 7.8 Phase Loss (PHL)
- 7.9 Motor cannot Run
- 7.10 Motor Speed cannot be Changed
- 7.11 Motor Stalls during Acceleration
- 7.12 The Motor does not Run as Expected
- 7.13 Electromagnetic/Induction Noise
- 7.14 Environmental Condition
- 7.15 Affecting Other Machines
- Chapter 8 Maintenance and Inspections
- Appendix A Specifications
- Appendix B Accessories
- Appendix C How to Select the Right AC Motor Drive
- Appendix D CE
![](/manual/delta/ac-motor-drive-vfd007s23a/user-s-manual-english/images/img-150.png)
Appendix B Accessories|VFD-S Series
B-6 Revision August 2006, SE08, SW V2.61
If the length is too long, the stray capacitance between cables will increase and may
cause leakage current. It will activate the protection of over current, increase leakage
current or not insure the correction of current display. The worst case is that AC motor
drive may damage.
If more than one motor is connected to the AC motor drive, the total wiring length is the
sum of the wiring length from AC motor drive to each motor.
B.2.1 Dimensions
Dimensions are in millimeter and (inch)
Order P/N: RF007S21AA/ RF007S43AA
60
(2.36)
200
(7.87)
85
(3.35)
200
(7.87)
50
(1.97)
27
(1.06)
24
(0.94)
15
(0.52)
4.5
(0.18)
213
(8.39)